Schischek GmbH
Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail [email protected]
www.schischek.com
E X P L O S I O N P R O O F
ExCos-D... transducer
ExPro-C... sensor
Example: room sensor
Example: duct sensor
ExCos-D...-CT
Shown:
ExPro-...-CTF…
Description
Application
Highlights transducer
Transducer
Connectable sensors (compulsory for ExCos-D... transducer) – see separate data sheet
Highlights sensor
Electrical, explosionproof transducers only connectable to
ExPro-C...
temperature and humidity sensors.
24 VAC/DC supply, 0…10 V / (0)4…20 mA output
PTB-certified in acc. with ATEX directive 94/9/EC for zone 1, 2, 21, 22.
For all type of gas, mixtures, vapours and dust for use in zone 1, 2, 21 and 22
No addional Ex-i module required
No intrisically safe wiring/installation between panel and sensor required
No intrisically safe wiring/installation and no space in the panel required
Integrated Ex-e junction box
Power supply 24 VAC/DC
Display with backlight, can be switched off
Scalable analogue output, selectable 0…10 V / (0)4…20 mA
Compact design and small dimension (L × W × H = 180 × 107 × 66 mm)
Robust aluminium housing in protection class IP66
Down to –20°C ambient temperature applicable
Password locking
Optional IS-output (0)4…20 mA for external indicator in Ex-areas
CT versions have an excellent resistance to chemicals and seawater
For all type of gas, mixtures, vapours and dust for use in zone 1, 2, 21 and 22
Plug-and-socket connection to ExCos-D... transducer, removable
The ExPro-C... probe appropriates the function (temperature, humidity or combination)
Mounting of ExPro-C... probe (front/back side) appropriates use for duct or room application
ExCos-D
Transducer for ExPro-C... sensors (probes)
ExPro-C...
Temperature/humidity sensors (°C, %rH)
1 / 4
The
ExCos-D...
transducer generation from together with direct coupled
ExPro-C... sensors
are a revolution for measuring temperature and/or
humidity in HVAC systems, in chemical, pharmaceutical, industrial and
Offshore-/Onshore plants, for use in hazardous areas zone 1, 2 (gas)
and zone 21, 22 (dust).
Highest protection class (ATEX) and IP66 protection, small dimension,
universal functions and technical data guarantee safe operation even
under difficult environmental conditions.
The measuring ranges are scalable within the maxium ranges. The
analogue output signal is either 0...10 VDC or (0)4...20 mA and can be
selected on site. The integrated display is for actual value indication
which can be switched off.
All sensors are programmable on site without any additional tools.
ExCos-D-A
transducer are additionally equipped with a (0)4…20 mA IS
(IS = intrinsically safe) output, e.g. for an external indicator.
Subject to change!
Type of transducer:
ExCos - D
ExCos - D - A
ExCos - D... - CT
Type of sensor (probe):
ExPro - CT...
ExPro - CF...
ExPro - CTF...
Type
Supply
Installation area Connectable sensors
Function of sensors
Sensor connection
Wiring diagram
ExCos - D
24 VAC/DC zone 1, 2, 21, 22 ExPro-CT..., ExPro-CF..., ExPro-CTF...
°C, % rH, combination °C/% rH via plug-and-socket connection SB 2.0
ExCos - D - A
as above, but with additional intrisically safe analogue output to connect an external digital indicator (0)4...20 mA (Ex-i)
SB 3.0
ExCos - D...- CT
Type as above but with aluminium housing and Amercoat painting (sensor connection cable glands nickel-plated, screws in stainless steel)
Type
Function
Measuring range
Length of sensor
connectable to
Installation sensor Installation transducer
ExPro - CT…
temperature
–40...+125 °C*
50/100/150/200 mm ExCos-D..., RedCos-D... zone 1, 2, 21, 22
zone 1, 2, 21, 22 (ExCos…)
ExPro - CF…
humidity
0...100 % rH
50/100/150/200 mm ExCos-D..., RedCos-D... zone 1, 2, 21, 22
zone 1, 2, 21, 22 (ExCos…)
ExPro - CTF…
combination temp./humidity –40...+125 °C*/0...100 %rH 50/100/150/200 mm ExCos-D..., RedCos-D... zone 1, 2, 21, 22
zone 1, 2, 21, 22 (ExCos…)
* at 50 mm length –40…
+80
°C
sensor length