Installation Instructions
JOINTING SYSTEM
All joints in the ICS chimney range, which require a locking band, are made by means of a simple
push fit jointing method. This is achieved by the engineered spigot and socket system having a
pronounced lead-in-edge to ease assembly.
ICS Plus is created by adding a lip seal gasket into the inward bead on the liner of the standard
components, which are suitable for use in condensing applications with a P1 designation. When
installing ICS Plus components, Gaskets should be fitted dry and lubricant applied to the internal
of the female liner socket (see Fig.1 bottom of the page)
ICS
Locking Band
Male Spigot
Stainless Steel
Outer case
Spacer Wire
Female Socket
Insulation
Capillary
Break
Stainless Steel
Inner Liner
Lip seal
(TÜV Approved 200Pa)
ICS Plus
STANDARD CHIMNEY SECTIONS (PIPES, TEES AND ELBOWS)
Before assembling chimney sections, slip a locking band over female socket of the chimney
section. Ensure the sections are pushed tightly together, before securing the locking band by use
of the quick release clip. The clip can then be tightened into place by using the tightening bolt.
Note:-joints must NOT occur within floor or ceiling spaces.
All flue gas carrying components must be installed with the direction arrow on the product
label pointing to termination with the external male spigot of the case uppermost.
Fig. 1
Locking Band
Lip Seal
(required for
T200 P1 applications)
Lubricant
(applications
with Lip Seal)