Schaudt Electroblock EBL 211 Скачать руководство пользователя страница 4

Operating Instructions Electroblock EBL 211

4

Date: 22.01.2016

9110476 BA / EN

3 Operation

The electroblock is operated solely from the operator and control panel con-

nected (apart from battery isolation).

Operation of the electroblock is not required for daily use.

Settings only have to be configured when the battery type is changed (AGM

or lead-gel), during initial start-up or when retrofitting accessories (refer to

Section 3.2 and the installation instructions EBL 211).

3.1 Switching system on/off

Y

ATTENTION!

Incorrect electroblock settings.
Damage to connected devices. Therefore prior to starting:

F

Ensure the leisure area battery is connected.

F

Ensure that the battery selector switch (Fig. 4, Pos. 5) is set to the

correct position for the battery inserted.

F

Ensure that the AES fuse (Fig. 4, Pos. 3) is only inserted when an

AES refrigerator is connected. The leisure area battery may totally

discharge otherwise. Damage to the battery is possible.

Deactivate the battery cut-out (shutdown) as required (refer to Section 3.4)

Use the main 12 V switch (see instruction manual of relevant control and

switch panel) to switch on/off all the consumers and the control and switch

panel.

Exceptions:

F

Step

F

Frost protection valve

F

AES refrigerator

Please refer to the operating instructions for the operator and control panel

for further information.

Y

ATTENTION!

If there is no backup function for the battery, damage to devices connected

may result. So therefore:

F

Do not operate solar regulator without battery connected.

If a current generator is used for the 230V motorhome supply, the genera-

tor must not exceed the mains connection ratings (see ”Technical details”,

Section 5.2).

Y

ATTENTION!

F

To avoid voltage peaks during warm-up, do not connect the generator

until it is running in a stable manner. Otherwise the electroblock, the

12 V consumers or other devices connected could suffer damage. It is

essential the generator conforms to mains supply specifications.

Battery cut-out

12 V main switch

(on operator and control

panel)

Operation with solar

regulator

Use on a 230 V

generator or car ferries

Содержание Electroblock EBL 211

Страница 1: ...ormation 2 1 1 Meaning of safety symbols 2 1 2 General safety information 2 1 3 Liability limitation 3 2 Introduction 3 3 Operation 4 3 1 Switching system on and off 4 3 2 Changing the battery 5 3 3 Operating faults 6 3 4 Shutting down 7 4 Application and functions in detail 9 4 1 General 9 4 2 Battery functions 10 4 3 Additional functions 10 5 Technical details 11 5 1 Mechanical details 11 5 2 El...

Страница 2: ... device must be repaired immediately by specialists Y DANGER Parts carry 230V mains voltage Risk of fatal injury due to electric shock or fire F Do not carry out maintenance or repair work on the device F If cables or the device housing are damaged no longer use the device and isolate it from the power supply F Ensure that no liquids enter the device F The mains connection line may only be replace...

Страница 3: ...stalla tion guide F improper assembly and or installation F non intended use F improper repairs F technical modifications F use of unapproved spare parts 2 Introduction This instruction manual contains important information for the safe operation of equipment supplied by Schaudt Make sure you read and follow the safety instructions provided The operating instructions should always be kept in the v...

Страница 4: ...le Deactivate the battery cut out shutdown as required refer to Section 3 4 Use the main 12 V switch see instruction manual of relevant control and switch panel to switch on off all the consumers and the control and switch panel Exceptions F Step F Frost protection valve F AES refrigerator Please refer to the operating instructions for the operator and control panel for further information Y ATTEN...

Страница 5: ...r also to Section 3 4 Remove solar cell connector on the solar charge regulator if availa ble Isolate the electroblock from the mains voltage 230V AC Replace the battery After changing the battery recheck which type of battery has been inser ted Y DANGER Incorrect setting of the battery selector switch Risk of explosion due to build up of explosive gases F Move the battery selector switch to the c...

Страница 6: ... on the automatic fuse in the vehicle g g operation battery voltage constantly below 13 3 V Have the mains voltage constantly below 13 3 V Have the mains voltage checked Defective electroblock Contact customer service Leisure area battery is overcharged during 230 V operation battery voltage constantly above 14 5 V Defective electroblock Contact customer service Starter battery is not char No main...

Страница 7: ...rom Defective electroblock Contact customer service block not possible from the control panel Y The charging current is reduced automatically if the device becomes too hot due to excessive ambient temperature or lack of ventilation Always prevent the device from overheating nevertheless Y If the automatic shutdown mechanism of the battery monitor is triggered fully charge the leisure area battery ...

Страница 8: ...sure area battery is isolated from the electroblock via the battery cut out The boiler and water tank empty when the frost protection valve is open See the instruction manual for the heater system for further information The leisure area battery is also charged by the internal charger module an additional battery charger the solar charger regulator and the alterna tor when the battery cut out is a...

Страница 9: ...r etc 12V consumers Starter battery Leisure area battery Fig 2 On board power supply system The EBL 211 electroblock comprises F a charge module for charging all batteries connected F the complete 12V distribution unit F the fuses for the 12V circuits F a main switch module F battery monitor F other control and monitoring functions A control and switch panel must be connected for operation This de...

Страница 10: ... leisure area battery causes the voltage to fall so low that the automatic disconnector is triggered any non essential consumers should be switched off It may be the case that only the 12 V supply is started for a short time For this switch on the 12V main switch on the control and switch panel However if the battery voltage remains below 11 0 V you cannot switch the 12 V power supply back on Full...

Страница 11: ...2 6 V battery voltage F Battery alarm OFF F Battery cut out switch ON F Lighting for operator and control panel OFF F All consumers switched off F 12 V main switch OFF Loading of D output of the alternator by the electroblock approx 0 5 mA without current consumption on D point 12 V outputs A maximum of 90 of the nominal current of the relevant fuse may be drawn Frost protection valve output max 0...

Страница 12: ...duration of the full charge phase is based on the battery type and is set on the device U Automatic changeover to compensation charge with constant 13 7 V In the compensation charge phase the voltage at the output of the char ging module is constant Start of a new charging cycle by switching over to main charge if the battery voltage falls below 13 7 V for more than 5 seconds when loaded Start of ...

Страница 13: ...ienst schaudt gmbh de Returning a faulty device Complete and enclose the fault report see Appendix C Send it to the addressee free delivery C Fault report In the event of damage please fill in the fault report and send it with the faulty device to the manufacturer Device type _______________________ Item no _______________________ Vehicle Manufacturer _______________________ Model ________________...

Страница 14: ...panel 2 Battery switchover types gel AGM 3 Flat vehicle fuse for AES refrigerator 4 Flat vehicle fuses for consumers 5 Battery cut out 6 Step fuse 7 Flat vehicle fuse for solar regulator 8 Mains connection 9 Housing 10 Connection block solar regulator supply 11 6 3 mm consumer connectors 12 Connector block for batteries 13 Device feet 1 Fig 5 Layout of EBL 211 electroblock rear 1 Cover ...

Страница 15: ...or LF PA 401 6 3x0 8 4x 6 way Leisure area battery Starter battery D input D point sensor leisure area battery Negative leisure area battery sensor Negative leisure area battery Negative leisure area battery Starter battery Shunt battery Shunt consumer sensor leisure area battery Mains indicator 12V On 12V Off Negative leisure area battery sensor 12 V indicator Pump switch Lumberg MSFQ 0 10 way Fr...

Страница 16: ...Operating Instructions Electroblock EBL 211 16 Date 22 01 2016 9110476 BA EN Blank page ...

Отзывы: