5. Maintenance

5.1 Cleaning and inspection

The fans should be inspected and 
cleaned once a year. In environments 
with large dust concentrations short-
er intervals are recommended.
It is important that the impeller be 
cleaned as coatings on the blades 
may cause imbalance and thus vi-
brations subjecting the bearings to 
unnecessary stress. The impeller is 
cleaned by dismounting it from the 
motor side. See sections “5.4 Dis-
mounting of motor with impeller 
from the motor side” and “5.5 

Mounting of motor with impeller 
from motor side”.

5.2  Dismounting of impeller 

from the inlet side

Fig. 4. First, dismount the duct from 
the fan inlet side. Then remove duct 
connection (pos. 1), inlet cone (pos. 
3) and intermediary flange (pos. 5) 
by loosening and unscrewing the 
nuts (pos. 6). Then remove the screw 
(pos. 12) and motor disc (pos. 10) 
holding the impeller. Detach the im-
peller using a puller secured in the 
two threaded puller holes in the im-
peller hub.

5.3  Mounting of impeller from 

the inlet side

Fig. 4. Place the impeller (pos. 9) on 
the shaft, mount pos. 10-12, and 
tighten the screw (pos. 12). Mount 
duct connection (pos. 1), inlet cone 
(pos. 3) and intermediary flange 
(pos. 5). Remember to check that the 
distance between inlet cone (pos. 3) 
and impeller (pos. 9) is equally large 
everywhere, and that the seal (pos. 8) 
still is elastic. Finish by tightening 
screws (pos. 6).

5.4 Dismounting of motor with 

impeller from the motor 
side

Before the fan is dismounted, it must 
be ensured that it cannot be started 
unintentionally. This is done by se-
curing the service switch with a key.
1. When dismounting the rotor, 

first remove the bolts and nuts 
attaching the sealing plate and 
the motor bracket to the fan 
housing. See fig. 5 and 6.
The bolts attaching the motor 

bracket to the guide rails should 
only be loosened – not removed. 
See fig. 7.

Fig. 4

Fig. 5

Fig. 6

Содержание NOVENCO CAL Series

Страница 1: ...CAL INSTALLATION AND MAINTENANCE 919043 0 English CAL...

Страница 2: ...tact If the fans are stored indoors under well ventilated conditions with no risk of condensation the storage pe riod may be extended to six months The storage place must not be ex posed to vibrations...

Страница 3: ...t it cannot be exceeded 4 5 Start up procedure Start fan Check that there are no abnor mal mechanical noises or pulsa tions Check the vibration level It must not exceed 7 mm s RMS measured on bearing...

Страница 4: ...sc pos 10 holding the impeller Detach the im peller using a puller secured in the two threaded puller holes in the im peller hub 5 3 Mounting of impeller from the inlet side Fig 4 Place the impeller p...

Страница 5: ...that the sealing plate rubber seal is intact If the seal is damaged it must be replaced The impeller is dismantled and reas sembled as described in section 5 6 Shaft seal under Dismounting and Mounti...

Страница 6: ...t be centred around the shaft pos 1 Press the oil thrower pos 6 and seals pos 13 over the shaft pos 1 and mount the impeller and fasten it by means of the washers pos 14 and the screw pos 8 Tighten th...

Страница 7: ...type CAL have been manufactured in accordance to and comply with the European Council s directives 2006 42 EU regarding mutual ap proximation of the machinery laws the Machinery Directive of the membe...

Страница 8: ...WWW NOVENCO BUILDING COM CAL...

Отзывы: