background image

 

4

2. Place a pallet truck or similar 

support under the motor brack-
et. See fig. 8. Attach a bench 
screw to the front support to pre-
vent the motor bracket and rotor 
from falling backwards when 
they are retracted from the fan 
housing. See fig. 9.
Support the rear, if necessary, to 
keep the motor bracket horizon-
tal.

3. Pull rotor and motor bracket out 

of the fan housing. It may be nec-
essary to use a crowbar to loosen 
the sealing plate from the hous-
ing. See fig. 10 and 11.
Check that the pallet truck is set 
to the correct height.
When retracting the rotor, it is 
recommended to stop 100 mm 
before the motor bracket slides 

off the guide rails. See fig. 12.

4. Clean the rotor carefully as dirt 

and coatings causes imbalance.
Also check that the sealing plate 
rubber seal is intact. If the seal is 
damaged, it must be replaced.

The impeller is dismantled and reas-
sembled as described in section “5.6 
Shaft seal” under “Dismounting” 
and “Mounting” respectively.

5.5 Mounting of motor with 

impeller from motor side

1. Push the palletizer with motor 

bracket towards the fan housing. 
Correct the nuts so that they may 
slide in the rails. See fig. 13.
When the motor bracket is ap-
prox. 20 mm from the fan hous-
ing, align it so that the bolts are 
opposite the holes. Use, for ex-
ample, a conical arbor. See fig. 
14.
Then push the parts completely 
together. 

2. Mount the bolts from the fan 

housing supports for the motor 
bracket. See fig. 15. Then insert 
all sealing plate nuts.
 Tighten the sealing plate nuts to 
a torque of 25 Nm. See fig. 16.
Finally, fasten the bolts in the 
bottom of the motor bracket to 
the guide rails. See fig. 7.

Fig. 7

Fig. 8

Fig. 9

Fig. 10

Fig. 11

Fig. 12

100 mm

Fig. 13

Fig. 14

Fig. 15

Содержание NOVENCO CAL Series

Страница 1: ...CAL INSTALLATION AND MAINTENANCE 919043 0 English CAL...

Страница 2: ...tact If the fans are stored indoors under well ventilated conditions with no risk of condensation the storage pe riod may be extended to six months The storage place must not be ex posed to vibrations...

Страница 3: ...t it cannot be exceeded 4 5 Start up procedure Start fan Check that there are no abnor mal mechanical noises or pulsa tions Check the vibration level It must not exceed 7 mm s RMS measured on bearing...

Страница 4: ...sc pos 10 holding the impeller Detach the im peller using a puller secured in the two threaded puller holes in the im peller hub 5 3 Mounting of impeller from the inlet side Fig 4 Place the impeller p...

Страница 5: ...that the sealing plate rubber seal is intact If the seal is damaged it must be replaced The impeller is dismantled and reas sembled as described in section 5 6 Shaft seal under Dismounting and Mounti...

Страница 6: ...t be centred around the shaft pos 1 Press the oil thrower pos 6 and seals pos 13 over the shaft pos 1 and mount the impeller and fasten it by means of the washers pos 14 and the screw pos 8 Tighten th...

Страница 7: ...type CAL have been manufactured in accordance to and comply with the European Council s directives 2006 42 EU regarding mutual ap proximation of the machinery laws the Machinery Directive of the membe...

Страница 8: ...WWW NOVENCO BUILDING COM CAL...