Smoke extraction damper ERK-SO
TECHNICAL DOCUMENTATION
Installation details |
Construction subject to change
No
return
possible
Version:
2017-11-28
|
Page
18
Suspended/vertical installation in solid ceilings
For the correct number and positioning of the mounting brack-
ets, the installation situation ((suspended/vertical) must be
specified when ordering.
suspended
vertical in
Wet installation
Mortar gap
≥
10
≤
60 mm
Wet installation
Mortar gap
≥
10
≤
60 mm
Mortar of category M2.5 to M15 in ac-
cordance with EN 998-2 (previously: MG
II to III according to DIN 1053) or fire
protection mortar of suitable grades.
Mortar of category M2.5 to M15 in accord-
ance with EN 998-2 (previously: MG II to III
according to DIN 1053) or fire protection
mortar of suitable grades.
Figure 11 - Installation in solid ceilings
Remarks:
When installed suspended in solid ceilings, the mount-
ing brackets WE-S must usually be positioned and
mounted on site. Otherwise, if installed ex works, the
ERK-SO could not be inserted into the ceiling recess.