background image

 

Fire damper BSK-RPR-EU 

  

Technical 

documentation 

 Technical

 data 

Construction subject to change 

 

No return possible 

Version: 2015-02-01 | Document: 09/48 | Page 9 

Pressure loss and radiated noise 

 
Nominal size 100 to 

 250 

 

Nominal sizes > 250 to 500 

 

 

Diagram 3: Pressure loss and radiated noise 

Application limits: 
max. operating pressure of 1000 Pa at v

stirn

 

 10 m/s. 

Free cross-section [m²] 

 

Nominal si-

ze 

D [mm] 

Free cross-section [m²] 

100 98 

0.0046 

125 123 

0.0081 

140 138 

0.0107 

160 158 

0.0147 

180 178 

0.0193 

200 198 

0.0246 

224 222 

0.0317 

250 248 

0.0404 

280 278 

0.0492 

315 313 

0.0641 

355 353 

0.0836 

400 398 

0.1086 

450 448 

0.1401 

500 498 

0.1755 

Table 6: Free cross-section [m²]

 

Weight table [kg] 

No-

minal 

size 

[mm] 

Manual triggering 

BSK-RPR-EU-S BSK-RPR-EU-F 

L=455 L=580 L=375 L=500 

100 98  2.44  2.74  2.49  2.80 
125 123  2.83  3.21  2.89  3.29 
140 138  3.06  3.49  3.13  3.57 
160 158  3.35  3.84  3.43  3.93 
180 178  3.65  4.20  3.74  4.31 
200 198  3.97  4.59  4.07  4.70 
224 222  4.37  5.07  4.48  5.19 
250 248  4.80  5.58  4.93  5.71 
280 278  6.31  7.17  6.45  7.33 
315 313  7.14  8.13  7.30  8.29 
355 353  8.08  9.19  8.26  9.37 
400 398  9.09  10.34  9.29  10.55 
450 448 10.50 11.91 10.73 12.14 
500 498 11.85 13.42 12.10 13.67 

 

No-

minal 

size 

[mm] 

Spring return actuator 

BSK-RPR-EU-S BSK-RPR-EU-F 

L=455 L=580 L=375 L=500 

100 98  3.89  4.19  3.94  4.25 
125 123  4.28  4.66  4.34  4.74 
140 138  4.51  4.94  4.58  5.02 
160 158  4.80  5.29  4.88  5.38 
180 178  5.10  5.65  5.19  5.76 
200 198  5.42  6.04  5.52  6.15 
224 222  5.82  6.52  5.93  6.64 
250 248  6.25  7.03  6.38  7.16 
280 278  7.79  8.65  7.93  8.81 
315 313  8.62  9.61  8.78  9.77 
355 353  9.56  10.67  9.74  10.85 
400 398 10.57 11.82 10.77 12.03 
450 448 11.98 13.39 12.21 13.62 
500 498 13.33 14.90 13.58 15.15 

 

Table 7: Weight table [kg] 

All data given are approximate 

Содержание BSK-RPR-EU Series

Страница 1: ...ances or p data es ch urn actuators rts on texts ranch offices ures tables di chad KG 10 drive s n projecting end agrams ds 1 1 1 1 1 1 2 2 Te Fa ww 1 3 6 7 7 8 10 10 11 13 15 17 21 23 Install elephon...

Страница 2: ...tumescent seals Horizontal position of the damper blade axle The installation position is independent of the air flow direction Thermal trigger via fusible link 72 C optionally at an extra charge with...

Страница 3: ...urn possible Version 2015 02 01 Document 09 48 Page 3 MODELS AND DIMENSIONS BSK RPR EU S plug in connection Figure 1 Dimensions BSK RPR EU S BSK RPR EU F flanged connection Figure 2 Dimensions BSK RPR...

Страница 4: ...PR EU S is delivered by default with a rubber lip seal Figure 3 Rubber lip seal Trigger device thermomechanical Figure 4 Trigger device BSK RPR EU Flange bores BSK RPR EU F Figure 5 Flange bores Table...

Страница 5: ...de and the finishing protective grating ASG RF RS Use The fire damper type BSK RPR EU can be installed as shown in the following table Table 4 Usability BSK RPR EU F Figure 7 Damper blade projecting e...

Страница 6: ...e dampers before and after mounting and ensure ready access Electrical installations or work on electrical components may only be carried out by skilled electricians The supp ly voltage must be switch...

Страница 7: ...des with ventila tion ducts BK Fire damper BSK RPR EU ASG Finishing protective grating type ASG 1 VT Extension piece type VT LL Ventilation duct SW Shaft wall SR Closing direction LR Air flow directio...

Страница 8: ...to 250 Nominal sizes 250 to 500 Diagram 1 Pressure loss and flow generated noise without finishing protective grating Application limits max operating pressure of 1000 Pa at vstirn 10 m s Pressure los...

Страница 9: ...00 98 2 44 2 74 2 49 2 80 125 123 2 83 3 21 2 89 3 29 140 138 3 06 3 49 3 13 3 57 160 158 3 35 3 84 3 43 3 93 180 178 3 65 4 20 3 74 4 31 200 198 3 97 4 59 4 07 4 70 224 222 4 37 5 07 4 48 5 19 250 24...

Страница 10: ...ignalling and switching bus system type EasyBus Fire damper mini controller BKSYS Extension piece type VT RF 1 Assembly part type REBT 2 required for installation of the smoke detection system type RM...

Страница 11: ...upply voltage in accordance with regula tions and unlocked mechanically Display of the damper end positions is possible by me ans of integrated micro switches via potential free changeover contacts co...

Страница 12: ...position W 0 8 1 1 Power consumption dimensioning 4 VA Imax 8 3 A 5 ms 6 5 VA Imax 4 A 5 ms Auxiliary switch 2 x EPU Switching capacity of auxiliary switch 1 mA 3 0 5 inductive A AC 250 V Connection...

Страница 13: ...2 on page 4 Nominal size D mm L mm The dimension L depends on the nominal size 100 98 160 125 123 140 138 160 158 180 178 200 198 224 222 250 248 280 278 315 313 355 353 400 398 450 448 500 498 190 T...

Страница 14: ...248 280 278 315 313 355 353 400 398 450 448 500 498 Table 10 Dimensions REBT Figure 18 Round duct assembly type REBT side view front view and top view Position indicator type MSZ Figure 19 Position in...

Страница 15: ...1 V2A Housing with DD coating solvent containing two component top coat based on polyurethane var nish RAL 7035 light grey inside outside Housing with powder coating RAL 9010 pure white inside and out...

Страница 16: ...charge for anticorrosive paint inside and outside DD coating two component top coat based on polyurethane varnish RAL 7035 light grey Extra charge for powder coating RAL 9010 pure white inside and out...

Страница 17: ...e of the damper blade and of the manual lever There is a risk of in jury The fire damper must close and lock automatically locking of the damper blade in the closed positi on 1 3 Opening the fire damp...

Страница 18: ...pply Fire damper must close automatically locking is performed by blocking the spring return actuator 2 3 Replacement of the thermoelectric release device if necessary Exchange takes place by unscrewi...

Страница 19: ...no Series Release device The following function steps have been carried out according to the documents installation mounting and operating instructions Prior to com missioning Next functional test in...

Страница 20: ...chako de Web www schako de Sample Functional test protocol for fire dampers Cons No ____________________ Defects found during the test on ________________________________________ Sluggishness due to s...

Страница 21: ...02 51620946 Fax 385 51 701 470 info europersis gr insupco netvision net il info schako it ri intel trade hr www europersis gr www insupco com www schako it www intel trade hr Luxembourg Niederlande st...

Страница 22: ...00 Praha 10 Zabehlice San ve Tic Ltd Sti Tel 421 337 741 843 Calle B nave 3 Tel 42 02 727 680 43 Pursaklar Sanayi Sitesi Fax 421 337 741 843 E 50840 San Mateo de G llego Fax 42 02 727 693 93 Karaca re...

Страница 23: ...ng return actuator 11 Figure 15 Connecting diagram B10 B11 11 Figure 16 Extension piece type VT RF 13 Figure 17 Finishing protective grating type ASG RS RF 13 Figure 18 Round duct assembly type REBT s...

Отзывы: