Fire damper BSK-RPR-EU
Technical
documentation
Specification
texts
Construction subject to change
No return possible
Version: 2015-02-01 | Document: 09/48 | Page 16
Finishing protective grating type ASG-RF
(flange connec-
tion); for installation with ventilation duct connection on on-
ly one side, galvanised sheet steel, mesh width
≤
20 mm, mi-
nimum distance a
min
= 50 mm from the open damper blade
must be taken into account, if necessary, use extension piece
type VT-RF or duct piece.
Product: SCHAKO
type ASG-RF
Dimensions
:
Diameter: ....................
mm
Extra charge for anticorrosive paint - inside and
outside -
- DD coating (two-component top coat based on
polyurethane varnish - RAL 7035 / light-grey)
Extra charge for powder coating (RAL 9010 / pure
white) -inside and outside-
Extra charge for model:
- Material no. 1.4301 (V2A)
- Material no. 1.4571 (V4A)
Finishing protective grating type ASG-RS
(plug-in connec-
tion), for installation with ventilation duct connection on on-
ly one side, wire or punch grille, galvanised sheet steel, mesh
size
≤
20 mm, minimum distance a
min
= 50 mm from the o-
pen damper blade must be taken into account, if necessary,
use extension piece (on site, e.g. duct piece).
Product: SCHAKO
type ASG-RS
Dimensions
:
Diameter: ....................
mm
Extra charge for anticorrosive paint - inside and
outside -
- DD coating (two-component top coat based on
polyurethane varnish - RAL 7035 / light-grey)
Extra charge for powder coating (RAL 9010 / pure
white) -inside and outside-
Extra charge for model:
- Material no. 1.4301 (V2A)
- Material no. 1.4571 (V4A)
Position indicator type MSZ,
consisting of a steel cable
- galvanised - with clamping nipple and position indicator
made of plastic material.
The mechanical position indicator for false ceilings is usable
for each mechanically operated BSK-RPR-EU with hand lever.
Product: SCHAKO
type MSZ
CE marking
12
0761
SCHAKO Klima-Luft
Ferdinand Schad KG
Weidenäcker 9
88605 Meßkirch, Germany
2013
09-48-DoP-BSK-RPR-EU-2013-07-01
EN 15650:2010
Fire Damper
type/version:
BSK-RPR-EU
Nominal conditions of
activation / sensitivity:
- Load bearing capacity of the
temperature-sensitive measuring sensor
- Response temperature of the
temperature-sensitive measuring sensor
passed
Response delay
(Response time):
- Closing time
passed
Operational safety:
- Cyclic testing (50 cycles)
passed
Fire resistance:
- Cross-section maintained
- Integrity E
- Heat insulation I
- Smoke leakage S
- Mechanical strength (under E)
- Cross-section (under E)
EI120
(v
e
i
↔
o) S
Durability of the
response delay:
- temperature-sensitive measuring sensor
Response temperature and load bearing capacity
Durability of the operational safety:
- Test of the opening and closing cycle
passed
passed