background image

Fire damper BSK-RPR-EU 

 

Technical documentation

Description

 

Construction subject to change 
No return possible 

Version: 2015-02-01 | Document: 09/48 | Page 2 

D

ESCR

IPTION 

Fire dampers built into ventilation ducts (air-conditioning 
systems) are used for the automatic locking of fire lobbies.  
The fire damper BSK-RPR-EU corresponds to EN 15650, EN 
13501-3 and EN 1366-2.  
BSK-RPR-EU has been tested according to EN 1366-2 in com-
pliance with Declaration of performance no. 09-48-DoP-BSK-
RPR-EU-2013-07-01. It has the EC certificate of conformity 
0761 - CPD - 0247. Its category according to EN 13501-3 is EI 
120 (v

e

 i

o) S. The national standards and guidelines must 

be observed along with this technical documentation, instal-
lation, mounting and operating instructions. 
For maintenance, servicing, retrofitting, etc., it may be ne-
cessary to provide on-site inspection openings in suspended 
ceilings, shaft walls, downstream ventilation ducts, etc. They 
must be built in in sufficient numbers and size and must not 
impair the functioning of the fire dampers.  
The fire dampers must be connected to the ventilation ducts 
of the ventilation system either on one or both sides. When 
connected on one side, finishing protective gratings made of 
non-flammable building materials (EN13501-1) must be pro-
vided on the opposite side. The fire dampers can be connec-
ted to non-flammable or to flammable ventilation ducts. 

 

Housing made of galvanised sheet steel;  
optionally (at an extra charge): 

 

Housing made of stainless steel material no. 
1.4301 or 1.4571 

 

Housing with DD coating (two-component  

top coat based on polyurethane varnish) inside 

and/or outside 

 

Extra charge for powder coating (RAL 9010 / pure 
white), inside and outside 

 

Model with plug-in connection (-S) or flanged connection 
(-F) according to EN 12220 and DIN 24154-1, respec-
tively. 

 

Shut-off damper made of silicate board 

 

Cold and hot leakage requirements according to EN 
1366-2 are complied with using circumferential rubber 
and intumescent seals. 

 

Horizontal position of the damper blade axle 

 

The installation position is independent of the air flow 
direction. 

 

Thermal trigger via fusible link 72°C; 
optionally (at an extra charge): 

 

with electrothermal trigger devices (for spring re-
turn actuators) 

 

Use: max. operating pressure of 1000 Pa  at v

stirn

 

 10 

m/s 

 

Housing leakage class C according to EN 1751 

 

Use or connection of a smoke trigger device with general 
building supervisory approval (Germany) (e.g. SCHAKO 
smoke detection system RMS, see technical documenta-
tion smoke detection system RMS) in connection with 
suitable electric trigger devices of the fire damper is pos-
sible; only trigger devices working according to the "cur-
rentless closed" principle may be connected to the RMS 
system; the propagation of fire and smoke is effectively 
prevented and the requirements of the Model Building 
Regulation (MBO) are fulfilled.

Optimal integration into the building control system by 
means of the SCHAKO EasyBus signalling and switching 
bus system (see technical documentation EasyBus) or 
the fire damper mini-controller BKSYS (see technical 
documentation BKSYS). 

MAINTENANCE INFORMATION

We point out that only suitable cleaning materials may be 
used for cleaning fire dampers in stainless steel design! 

ATTENTION 

Building installations must be erected, modified and main-
tained in a way to prevent the fire outbreak and propagation 
of fire and smoke (propagation of fire) and to allow rescue of 
persons and animals and effective fire extinguishing. Smoke 
propagation through the ventilation and air-conditioning sys-
tems can be effectively prevented only by means of suitable 
electric trigger devices in connection with a smoke detection 
system. 

We, therefore, recommend fitting the fire dampers, for 
example, with electric spring return actuators that can be 
triggered by the smoke detector. 

GENERAL 

Data and requirements according to German standards (DIN) 
must be checked on site for compatibility with current stan-
dards and directives in the respective states/countries and 
adapted, if necessary. Whether the installation of flexible 
connection pieces is required, must be determined on site. 

Содержание BSK-RPR-EU Series

Страница 1: ...ances or p data es ch urn actuators rts on texts ranch offices ures tables di chad KG 10 drive s n projecting end agrams ds 1 1 1 1 1 1 2 2 Te Fa ww 1 3 6 7 7 8 10 10 11 13 15 17 21 23 Install elephon...

Страница 2: ...tumescent seals Horizontal position of the damper blade axle The installation position is independent of the air flow direction Thermal trigger via fusible link 72 C optionally at an extra charge with...

Страница 3: ...urn possible Version 2015 02 01 Document 09 48 Page 3 MODELS AND DIMENSIONS BSK RPR EU S plug in connection Figure 1 Dimensions BSK RPR EU S BSK RPR EU F flanged connection Figure 2 Dimensions BSK RPR...

Страница 4: ...PR EU S is delivered by default with a rubber lip seal Figure 3 Rubber lip seal Trigger device thermomechanical Figure 4 Trigger device BSK RPR EU Flange bores BSK RPR EU F Figure 5 Flange bores Table...

Страница 5: ...de and the finishing protective grating ASG RF RS Use The fire damper type BSK RPR EU can be installed as shown in the following table Table 4 Usability BSK RPR EU F Figure 7 Damper blade projecting e...

Страница 6: ...e dampers before and after mounting and ensure ready access Electrical installations or work on electrical components may only be carried out by skilled electricians The supp ly voltage must be switch...

Страница 7: ...des with ventila tion ducts BK Fire damper BSK RPR EU ASG Finishing protective grating type ASG 1 VT Extension piece type VT LL Ventilation duct SW Shaft wall SR Closing direction LR Air flow directio...

Страница 8: ...to 250 Nominal sizes 250 to 500 Diagram 1 Pressure loss and flow generated noise without finishing protective grating Application limits max operating pressure of 1000 Pa at vstirn 10 m s Pressure los...

Страница 9: ...00 98 2 44 2 74 2 49 2 80 125 123 2 83 3 21 2 89 3 29 140 138 3 06 3 49 3 13 3 57 160 158 3 35 3 84 3 43 3 93 180 178 3 65 4 20 3 74 4 31 200 198 3 97 4 59 4 07 4 70 224 222 4 37 5 07 4 48 5 19 250 24...

Страница 10: ...ignalling and switching bus system type EasyBus Fire damper mini controller BKSYS Extension piece type VT RF 1 Assembly part type REBT 2 required for installation of the smoke detection system type RM...

Страница 11: ...upply voltage in accordance with regula tions and unlocked mechanically Display of the damper end positions is possible by me ans of integrated micro switches via potential free changeover contacts co...

Страница 12: ...position W 0 8 1 1 Power consumption dimensioning 4 VA Imax 8 3 A 5 ms 6 5 VA Imax 4 A 5 ms Auxiliary switch 2 x EPU Switching capacity of auxiliary switch 1 mA 3 0 5 inductive A AC 250 V Connection...

Страница 13: ...2 on page 4 Nominal size D mm L mm The dimension L depends on the nominal size 100 98 160 125 123 140 138 160 158 180 178 200 198 224 222 250 248 280 278 315 313 355 353 400 398 450 448 500 498 190 T...

Страница 14: ...248 280 278 315 313 355 353 400 398 450 448 500 498 Table 10 Dimensions REBT Figure 18 Round duct assembly type REBT side view front view and top view Position indicator type MSZ Figure 19 Position in...

Страница 15: ...1 V2A Housing with DD coating solvent containing two component top coat based on polyurethane var nish RAL 7035 light grey inside outside Housing with powder coating RAL 9010 pure white inside and out...

Страница 16: ...charge for anticorrosive paint inside and outside DD coating two component top coat based on polyurethane varnish RAL 7035 light grey Extra charge for powder coating RAL 9010 pure white inside and out...

Страница 17: ...e of the damper blade and of the manual lever There is a risk of in jury The fire damper must close and lock automatically locking of the damper blade in the closed positi on 1 3 Opening the fire damp...

Страница 18: ...pply Fire damper must close automatically locking is performed by blocking the spring return actuator 2 3 Replacement of the thermoelectric release device if necessary Exchange takes place by unscrewi...

Страница 19: ...no Series Release device The following function steps have been carried out according to the documents installation mounting and operating instructions Prior to com missioning Next functional test in...

Страница 20: ...chako de Web www schako de Sample Functional test protocol for fire dampers Cons No ____________________ Defects found during the test on ________________________________________ Sluggishness due to s...

Страница 21: ...02 51620946 Fax 385 51 701 470 info europersis gr insupco netvision net il info schako it ri intel trade hr www europersis gr www insupco com www schako it www intel trade hr Luxembourg Niederlande st...

Страница 22: ...00 Praha 10 Zabehlice San ve Tic Ltd Sti Tel 421 337 741 843 Calle B nave 3 Tel 42 02 727 680 43 Pursaklar Sanayi Sitesi Fax 421 337 741 843 E 50840 San Mateo de G llego Fax 42 02 727 693 93 Karaca re...

Страница 23: ...ng return actuator 11 Figure 15 Connecting diagram B10 B11 11 Figure 16 Extension piece type VT RF 13 Figure 17 Finishing protective grating type ASG RS RF 13 Figure 18 Round duct assembly type REBT s...

Отзывы: