12
September 2006
The AEP-700 Inverter will indicate high and low DC voltage conditions as follows:
Model
Dc Input over
voltage
shut-down
Dc Input over
voltage alarm
Dc Input
under voltage
alarm
Dc Input
under voltage
shut-down
AEP-700-121
AEP-700-122
16.0VDC
15.5VDC
10.5VDC
10.0VDC
AEP-700-241
AEP-700-242
32.0VDC
31VDC
21.0VDC
20.0VDC
AEP-700-481
AEP-700-482
62.0VDC
61VDC
43.0VDC
42.0VDC
2-7-2 Output Voltage Indicator:
VAC LED illuminated. Display indicates output voltage value.
2-7-3 Output Current Indicator:
AMP LED illuminated. Display indicates output current value.
2-7-4 Output Watts Indicator:
Watts LED illuminated. Display indicates Watts value.
2-7-5 Input DC Voltage Indicator:
VDC LED illuminated. Display indicates input DC voltage value
2-7-6 Temperature Indicator:
TEMP LED illuminated. Display indicates internal operating temperature value.
2-7-7 Output Frequency DC Indicator:
Hz LED illuminated. Display indicates output frequency value