
A S S E M B LY
9
Fresh air intake
In a well-insulated house, the air used up by the burning process has
to be replaced. This particularly applies to houses with mechanical
ventilation. There are different ways of making sure that an air
exchange takes place. The most important thing is to ensure that
there is a supply of air to the room where the wood stove is located.
The external wall vent must be located as close to the wood stove
as possible, and you must be able to close it when you are not using
the wood stove.
National and local building regulations must be followed with
regard to the connection of fresh-air intake.
Closed combustion system
If you have decided to use the stove’s closed combustion system,
connect the external combustion air using a ventilation pipe pas-
sing through the wall or floor.
It must not be possible to shut off the ventilation pipe with a valve
Minimum Ø100 mm ventilation pipe, maximum length: 6 m
with a maximum of one bend
•
The Scan
58
with pedestal plinth
External combustion air can be connected via the pedestal or plinth
base by fitting the connection piece supplied to the pedestal plinth
and connecting outdoor air.
External combus-
tion air via wall
External combus-
tion air via floor
D
D
5. Fit the blanking plate in the smoke outlet.
Place the top plate on the stove.
Bracket
Allen screw