Configuration
Diagnostic
2-18
2
is hard-wired in the firmware. Communications will not work unless the station
number is 253.
Error 7012: Primary and Secondary devices have the same S-Bus station
number
The Primary and Secondary devices must have different S-Bus station num
-
bers. You will see this error if a new project has been created and the station
numbers have not yet been assigned (both are 0).
Warning Messages
Warning 7101: Invalid ‘Channel Type’ in Online Settings, use S-Bus, S-Bus
USB or SOCKET
Only these channels can be used to communicate with a standby controller.
Warning 7102: Invalid ‘S-Bus Station Number’ in Online Settings (is n, should
be n)
The S-Bus station number on the Online Settings does not match the S-Bus
station number on the device configuration.
Warning 7103: Invalid ‘IP Address’ in Online Settings (is xxx.xxx.xxx.xxx,
should be xxx.xxx.xxx.
xxx)
The IP address in the Online Settings does not match the IP address in the
device configuration.
Warning 7104: Invalid Online Settings, ‘PGU Mode’ should be ‘No’
PGU mode cannot be used to communicate with a standby controller. It may
cause connection to the wrong device or CPU. Open the Online Settings and
ensure ‘PGU’ mode is ‘No’.
Warning 7105: Invalid Online Settings, ‘Auto Station’ should be ‘No’
Automatic station number detection mode cannot be used to communicate
with a standby controller. It may cause connection to the wrong device or CPU.
Open the Online Settings and ensure ‘Auto Station’ is ‘No’.