Configuration
Diagnostic
2-17
2
file: <file_name>
Error 7003: Secondary device does not reference Redundant device’s sym
-
bol file: <file_path>
Error 7004: Redundant device does not reference Primary device’s symbol
file: <file_path>
Error 7004: Redundant device does not reference Secondary device’s sym
-
bol file: <file_path>
The symbol file references should be as shown in the Project Tree picture above.
The primary and secondary devices should reference the redundant device’s
symbols (e.g. FromRedSymbols.sy5), the redundant device should reference
the primary and secondary devices symbol files (ToRedSymbolsPrimary.sy5 and
ToRedSymbolsSecondary.sy5)
Error 7005: Invalid or missing Primary IP address for Redundant device
Error 7005: Invalid or missing Secondary IP address for Redundant device
Error 7005: Invalid or missing Subnet Mask for Redundant device
Error 7005: Invalid or missing Default Gateway for Redundant device
The IP address is not valid. open the Redundancy Configuration dialog box and
correct it.
Error 7006: Primary and Secondary IP addresses for Redundant device are
the same
Different IP addresses must be used. Open the Redundancy Configuration
dialog box and correct it.
Error 7007: Invalid ‘Online Settings’ for Redundant device (needs Sta
-
tion=253, Auto Station=No): <device_name>
This is possible because the ‘Online Settings’ does not know what the device
type is, and cannot stop the user changing the settings. Open the ‘Online Set-
tings’ for the redundant device and correct them.
Error 7008: Primary device symbol file has wrong extension: <file_name>
Error 7008: Secondary device symbol file has wrong extension: <file_name>
Error 7008: Redundant device symbol file has wrong extension: <file_name>
A file with the correct name exists, but the existing file does not have the ‘.sy5’
file extension. Manually create a new Global Symbol File (.sy5) and change the
file name in the Redundancy Configuration, or use OK to create a new file for
you.
Error 7009: Primary device symbol file is not a ‘Symbols file’, see Properties:
<file_name>
Error 7009: Secondary device symbol file is not a ‘Symbols file’, see Proper
-
ties: <file_name>
Error 7009: Redundant device symbol file is not a ‘Symbols file’, see Proper
-
ties: <file_name>
The file exists, but it has not been flagged as being a ‘Symbols file”. Open the file’s
‘Properties’ and check the ‘Symbols file’ checkbox.
Error 7011: Redundant device’s S-Bus station number must be 253
The S-Bus station number for the Redundant device (CPU1) must be 253. This