background image

3

009-1593-02

 

– Pencil

 

– #2 Phillips screwdriver

 

– Small slotted screwdriver

 

– Drill with 

5/32

 inch drill bit

 

– Wire stripper

 

– Needle-nose pliers

 

– Hammer (if wall anchors are used)

Welcome

Getting Started

Location and Mounting Overview

The following is needed for a trouble free installation:

This document describes how to:

1.  Remove the old thermostat.

2.  Mount your new CLI-W200 thermostat.

3.  Wire your new CLI-W200 thermostat.

 

CAUTION!

 When replacing an older thermostat that 

contains Mercury in a sealed tube, do not discard into trash. 

Refer to the thermostat-recycle.org website for information 

on how to properly dispose.

For new installations or when relocating the thermostat, 

follow the guidelines below:

 

– Locate thermostat on an inside wall.

 

– Do not locate where air circulation is poor such as in a 

corner or behind a door.

 

– Do not locate near windows or doors to reduce the expo-

sure to drafts.

 

– Install away from any heating conditions such as direct 

sunlight, near a radiator register or vent, or near a fireplace.

 

– To adhere to ADA requirements, install thermostat 48 - 54 

inches (1.22 - 1.37 meters) above the floor. 

 

– Height requirements can be adjusted upward to 60 inches 

(1.5 meters) if ADA requirements are not mandatory.

 

– The thermostat does not need to be level to operate cor-

rectly. Leveling the thermostat is for aesthetics only.

 

– Thermostat can be oriented in either a portrait or land-

scape layout.

Содержание CLI-W200

Страница 1: ...1 009 1593 02 SMART THERMOSTAT QUICK START GUIDE CLI W200 ...

Страница 2: ...Flush Mount CLI PLEN1R C Plenum Sensor CLI SLAB1 Slab Sensor Environmental Temperature 32 to 104 F 0 TO 40 C Humidity 10 to 90 non condensing Power Input 24V AC Current Draw 70 mA typical 250 mA maximum Max Power 6 watts Cable Requirements Power 18 AWG HVAC 18 AWG Thermostat Wire solid Remote Sensors 24 AWG 500 feet 152 m max Regulatory Safety Emissions FCC Part 15 FCC ID ASU CLIW200 IC 10052A CLI...

Страница 3: ...o properly dispose For new installations or when relocating the thermostat follow the guidelines below Locate thermostat on an inside wall Do not locate where air circulation is poor such as in a corner or behind a door Do not locate near windows or doors to reduce the expo sure to drafts Install away from any heating conditions such as direct sunlight near a radiator register or vent or near a fi...

Страница 4: ... Color of Wire R C RC 5 Remove each of the wires recorded above and attach a label that matches the terminal designation from the old thermostat Label wires according to the terminal desig nation and NOT the wire color 6 Again using the chart below add a check and record the wire color for each signal wire Terminal Color of Wire O G Y2 Y1 W2 W1 NOTE Additional information on terminal designa tions...

Страница 5: ...n mounting using a landscape layout remove bubble level by pushing it out through the rear of the mounting plate and reinstall it into the bubble level slot on the right side of center cutout See diagram above 4 Drill a 5 32 inch hole on each mark made and tap the wall anchor into wall until flush In some installations that have a sub wall to fasten to wall anchors may not be required 5 Pull the e...

Страница 6: ...are slots 1 8 inch bare wire exposed 2 Strip back insulation on each wire to 1 4 inch and insert the stripped wire into the proper connection 3 Turn screws clockwise CW until the crimps tighten around each wire Tug on each wire a bit to verify they are secure When connecting wires to the CLI W200 follow the guide lines set below to ensure a safe and secure connection o G Y2 Y1 W2 W1 RC RH TX TX 24...

Страница 7: ... system uses separate power sources to run the heating and cooling you should have three wires labeled for power R C and RC In this scenario remove the jumper shunt from JP1 The next section describes this Jumper JP1 on the thermostat board connects the RH and RC terminals The thermostat is shipped from the factory with a jumper shunt installed For systems with more than one power source remove th...

Страница 8: ...his sensor is shipped already pre installed between terminals RS1 and GND RS2 A remote temperature sensor can be added between terminals RS2 and GND No polarity is observed on either sensor TIP Refer to the Making Connections section above to ensure a safe and secure connection is made O Relay to control changeover valve on a Heat Pump G Fan Relay Y2 Relay for control of 2nd stage cooling Y1 Relay...

Страница 9: ...i ty to finish installation of the thermostat To ensure the IP Address will not change due to a power outage Savant recommends DHCP reservation be configured Using this method static IP Addresses for all devices can be managed from a single User Interface avoiding the need to access devices individually Setting DHCP reservation varies from router to router Refer to the documentation for the router...

Страница 10: ... functions such as schedules and OTA updates can not occur Are both Fahrenheit and Celsius supported Yes Does the thermostat support setting both a heating and cooling set point No The CLI W200 thermostat is a single set point thermo stat However the thermostat does support adding a range to the set point For example adjusting the set point to 70 with a range of 3 will manage the temperature so it...

Страница 11: ...his equipment has been tested and found to comply with the limits for CLASS B digital device pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the ins...

Страница 12: ...is equipment complies with IC radiation exposure limits set forth for an uncontrolled environment This equipment should be installed and operate with minimum distance 20cm between the radiator and your body Le présent appareil est conforme aux CNR d Industrie Canada applicables aux appareils radio exempts de licence L exploitation est autorisée aux deux conditions suivantes 1 L appareil ne doit pa...