Electronic heating controller 

en Quick reference

SAUTER equitherm

®

EQJW245

General

Congratulations! You have chosen a Sauter controller – a quality 
product from one of the leading manufacturers of control products 
for the HVAC industry. Your heating controller combines simplicity of 
operation with ultra-modern microprocessor technology. Follow these 
operating instructions so that you can adapt the device to your needs.

Key

1.1 

Factory setting 

sek.

Secondary side

BW

Domestic water

T

A

Outside temperature 

CP

Communication parameters

T

B

Boiler temperature

HK

Heating circuit

T

F

Flow temperature

Imp

Impulse

T

R

 Room 

temperature 

KW

Chilled water

T

RF

Return temperature 

LP

Charge pump

T

W

Temperature of 
domestic water

prim.

Primary side

SP

SERVice parameters

UP

Heating pump

Flashing value in display denotes:

special/unusual status

• 

value that can be changed

• 

Indicators and operating controls

Front view of EQJW245

2.1 

2

1

1

°C

sec

h

equitherm

®

EQJW245

1

2

PROG

PROG

1

2

LOG

PROG

PROG

1x

ESC

OK

STOP

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

2

1

3

4

B1

1423

1

Rotary switch

2

Display

3

Input knob

4

ESC key

LCD

2.2 

0  1  2  3  4  5  6  7  8..........21 22 23 24

Times for normal mode on the current day

Time, date, setpoints, actual values etc.

Automatic mode according to weekly and calendar 
switching programme. Flashing: limited/unlimited 
temperature change

Controller operating in normal mode

Controller operating in reduced mode

Controller operating in standby mode. 
Flashing: frost protection is active

Sensor is faulty

Heating pump for HC1, HC2 is switched on

Control unit 1, 2 is opened (

c

) or closed (

d

)

Setpoint temperature. 
Flashing: actual temperature is displayed

Flow temperature

Outside temperature

Room temperature

Return temperature 

Charge temperature of domestic water

Domestic-water temperature 1

Domestic-water temperature 2

    , 

Display refers to HC1 (–) or HC2 (=)

Controller is in summer mode

Calendar switching programme is currently active

Domestic water. 
Flashing: increased temperature

Charge pump is switched on

An error has occurred

Rotary switch for heating circuit 1 (top)

2.3 

Operating modes

Inputs

Automatic mode as per 
switching programme

Setpoint adjustment, 
normal mode

Controller is continuously in 
normal mode

Setpoint adjustment, 
reduced mode

Controller is continuously in 
reduced mode

Enter weekly and calendar 
programme for heating

Controller is continuously in 
standby mode

(Un)limited temperature 
change

Access to manual mode for 
heating

Access to SERVice, 
commissioning and 
communication level

Rotary switch for heating circuit 2 (middle)

2.4 

Operating modes

Inputs

Automatic mode as per 
switching programme

Setpoint adjustment, normal 
mode

Controller is continuously in 
normal mode 

1

Setpoint adjustment, 
reduced mode

Controller is continuously in 
reduced mode

Enter weekly and calendar 
programme for heating

Controller is continuously in 
standby mode 

2

(Un)limited temperature 
change

Access to manual mode for 
heating

Access to logbook

1

 Normal mode corresponds to nominal mode as per EN12098-1

2

 Standby mode means that the heating is switched off and the anti-

  frost function is active.

Contents: 
1. General
2. Indicators and operating controls
3. Putting into service (by a technician)
4. How to operate (user)

Содержание equitherm EQJW245

Страница 1: ... is active Sensor is faulty Heating pump for HC1 HC2 is switched on Control unit 1 2 is opened c or closed d Setpoint temperature Flashing actual temperature is displayed Flow temperature Outside temperature Room temperature Return temperature Charge temperature of domestic water Domestic water temperature 1 Domestic water temperature 2 Display refers to HC1 or HC2 Controller is in summer mode Cal...

Страница 2: ...r will alternate 3 Press input knob year number flashes 4 Turn input knob to change year 5 Press input knob to confirm year and view day month 6 Turn input knob to set date 7 Press input knob to confirm new date 1 The middle and bottom rotary switches should be set at one of the positions for an operating mode Manual mode 3 3 First enable manual mode in SERVice mode cf 3 6 by setting SP 05 to 1 Th...

Страница 3: ...room sensor 4 second flow sensor for domestic water SP09 0 Transmit room temperature for HC1 0 not active 1 active if TRi TRs 2 active if TRi TRs 3 active if TRi TRs SP10 20 Sampling time in minutes for TR1 when transmitted SP11 0 Adjust room temperature TR1 SP12 0 Adjust outside temperature TA SP13 0 RMeasure return temperature TRF1 0 not active 1 max limitation of TRF 2 maintain TRF SP14 0 Adjus...

Страница 4: ...via modem telephone number of the control station CP07 SMS via modem telephone number of the provider No Explanation CP08 SMS via modem telephone number of the mobile phone CP09 0 Device bus time synchronisation 0 not active 1 active CP10 0 Device bus send outside temperature 0 not active 1 active CP11 0 Device bus receive outside temperature 0 not active 1 active CP12 0 Device bus send heat requi...

Страница 5: ...mmand 4 6 4 Show the switching command as described in the section entitled View switching commands e g 1 Press input knob the switching command is called up 2 Turn the input knob select whether to delete Clr or change SEt the switching command 3 Press input knob the selection is confirmed If the switching command was deleted the next switching command will be shown 4 To make a change proceed as d...

Страница 6: ...temperature START daily 0 00 hours Call up weekly switching programme 4 11 1 domestic water 1 1x Set lower rotary knob to 2 Turn input knob select day of week 1 Monday 2 Tuesday 1 7 daily 3 Press the input knob the first switching command is shown View switching commands 4 11 2 Turn the input knob each switching command is shown An empty switching command is shown as _ _ _ _ Enter switching comman...

Отзывы: