Description of parameters
2 - 33
7000928003 R4
Sauter Components
Description of parameters
1W
1st shift (W), input
Access:
Service level
Source for the first shift module. The source denotes the Xi input that is used for the shift. This Xi input determines the unit of
measurement for parameters "Start of shift" and "End of shift". Every Xi input can be used for a shift. Enter OFF to deactivate
the shift module. On activation, the shift acts on controller PI 2 (cooling).
2W
2nd shift (W), input
Access:
Service level
Source for the second shift module. The source denotes the Xi input that is used for the shift. This Xi input determines the unit
of measurement for parameters "Start of shift" and "End of shift". Every Xi input can be used for a shift. Enter OFF to deacti-
vate the shift module. On activation, the shift acts on controller PI 1 (heating), or the heating curve can also be assigned as an
alternative.
3H
Heating curve - input
Access:
Service level
Source for the heating curve. The source denotes the Xi input that is used to calculate the heating curve. Every Xi input can be
used. Enter OFF to deactivate the heating curve. On activation, the heating curve acts on controller PI 1 (heating), or shift 2
can also be assigned as an alternative.
5r
Input -
controller 5
Access:
Service level
Assignment of Xi input for controller PI 5. This controller can be used freely, e.g. to control a dehumidifier or a refrigeration
machine.
ALErt
Forwarding an
alarm
Access:
Service level
Parameter for issuing an alarm. If a short circuit is detected at input Xi6, e.g. due to a closed relay, then the output relay -
which is selected using the ALErt parameter - will be closed. This makes it possible to forward an alarm.
Содержание RDT 300 F001
Страница 2: ...7000928003 R4 Sauter Components...
Страница 4: ...7000928003 R4 Sauter Components...
Страница 8: ...2 4 Service 7000928003 R4 Sauter Components...
Страница 18: ...2 14 Service 7000928003 R4 Sauter Components...
Страница 19: ...Overview of models 2 15 7000928003 R4 Sauter Components Overview of models...
Страница 34: ...2 30 Overview of models 7000928003 R4 Sauter Components...
Страница 35: ...Description of parameters 2 31 7000928003 R4 Sauter Components Description of parameters...
Страница 36: ...2 32 Description of parameters 7000928003 R4 Sauter Components...
Страница 48: ...2 44 Description of parameters 7000928003 R4 Sauter Components...
Страница 49: ...List of parameters 2 45 7000928003 R4 Sauter Components List of parameters...
Страница 50: ...2 46 List of parameters 7000928003 R4 Sauter Components...