
2 - 34
Description of parameters
7000928003 R4
Sauter Components
bXi. , bXi.
Range Xi for free unit of measurement and active transducer
Access:
Service level
Indicates the associated value ranges for the selected unit of measurement.
Cod
Code number
Access:
Service level
To gain access to the service level, a password (code) has to be entered. It is 6-7-8-9, and it cannot be changed. Access to
the service level can also be prevented by sealing the mode switch.
cXi.
config Xi
Access:
Service level
Settings for the type of sensor connected. In addition, the jumpers should be inserted at the rear of the unit.
Possibilities:
cXs.
Calculated setpoint
Access:
manual, automatic
Calculated setpoint, e.g. for summer compensation. The setpoint cXs is calculated from setpoint Xs, shifted by amount
WS.
It has an adding or subtracting effect, depending on the configuration.
Type
Sensor
Type
Sensor
1
Ni1000
4
Current 0...20 mA
2
Voltage 0...10 V
5
Current 4...20 mA
3
Voltage 2...10 V
6
Voltage 0...1 V
7
Active dewpoint input, only Xi4
Содержание RDT 300 F001
Страница 2: ...7000928003 R4 Sauter Components...
Страница 4: ...7000928003 R4 Sauter Components...
Страница 8: ...2 4 Service 7000928003 R4 Sauter Components...
Страница 18: ...2 14 Service 7000928003 R4 Sauter Components...
Страница 19: ...Overview of models 2 15 7000928003 R4 Sauter Components Overview of models...
Страница 34: ...2 30 Overview of models 7000928003 R4 Sauter Components...
Страница 35: ...Description of parameters 2 31 7000928003 R4 Sauter Components Description of parameters...
Страница 36: ...2 32 Description of parameters 7000928003 R4 Sauter Components...
Страница 48: ...2 44 Description of parameters 7000928003 R4 Sauter Components...
Страница 49: ...List of parameters 2 45 7000928003 R4 Sauter Components List of parameters...
Страница 50: ...2 46 List of parameters 7000928003 R4 Sauter Components...