TOP OUTLET FLUE INSTALLATION

Top outlet flue - kit 86151 see diagram 18

, is 1000 mm long

and comprises:
- Outer pipe .......................................................................

A

- Inner pipe ........................................................................

B

- External rubber sealing collar ........................................

C

- Flue elbow .......................................................................

D

- Internal flange ................................................................

E

- 'O' rings .............................................................................

F

- Screws ............................................................................

G

- Rubber collar ..................................................................

H

- Clamp and seal ...............................................................

I

- Gasket ..............................................................................

J

A - Flue to rear of boiler

• Mark correct position of hole from template.

B - Flue to side of boiler

• Mark horizontal centre line for  hole on rear wall. Extend
horizontal centre line to side wall and mark vertical centre
line of flue hole as shown in 

diag. 12.

Under normal circumstances, it will be possible to gain ac-
cess to the outside of the building to fit the flue terminal
assembly. Where outside access is not possible e.g. high
rise buildings, the flue terminal can be fitted from inside the
building only if required.

Note : 

When cutting flue hole and when extending flue

centre line to a side wall, remember that the flue system
must have a fall of about 35 mm per metre of flue DOWN-
WARD AWAY FROM the boiler. There must NEVER be a down-
ward incline towards the boiler.

Cutting the flue hole

• Making allowance for the slope of the flue, cut hole in
external wall, preferably using a core drill.

For installations with internal and external access

 - Use a

105 mm diameter core drill.

For installations with internal access only

 - Use a 125 mm

diameter core drill.

Important: 

Before cutting hole for flues to rear of boiler, al-

ways cover fixing jig to make sure it is not damaged.

Hab 210b

Diagram 17

A

B

C

J

H

D

F

E

G

I

Diagram 18

Pho 422

e

e

a

a

X

X

Table 2 : Number of extension kits required

Flue option

Dimension 'X'

No. of

extension kits

Side flue

1081 to 1811 mm

1

(left or right)

1812 to 2542 mm

2

                        

Flue Cutting length (mm)

Flue option

outer pipe

inner pipe

Comments

Top outlet

e + a + 125

e + a + 202

maximum

Side flue to

distance 'X' without

(left or right)

extension 1080 mm

Calculation of flue cutting lengths

• Measure wall thickness

 e

 (mm), 

see

 

diagram 17.

• For side flues, measure distance from inside face of side
wall to centre line of flue and subtract 205 mm for both
right and left hand flues to get dimension 

(mm).

• Refer to

 table 1

 for cutting lengths of both inner and outer

flue pipes for each of the various flue options available.

Important:

 All flue cutting lengths must be measured from

the terminal end of the flue pipes, 

see

 

diag. 15

.

When the dimension 

measured on site is greater than that

given in 

table 1,

 a flue extension kit will be required, refer to

table 2

 for details.

Extended flue

The horizontal flue is extended by using one or more of the
1000 mm extension pipes, 

Saunier Duval 

part number 85091.

These are connected together by push fit type joints, clamps
and seals.

Calculation of flue cutting lengths for extended flue

• Using the correct number of extension kits as 

table 3

,

measure dimensions 

and 

e

see diagram 17

.

Important: 

All cutting lengths should be measured from the

push fit end of the extension pipe. Do not leave any burrs or
sharp edges on the cut ends of the  pipes.

Table 3 :

                 

Extended Flue Cutting length (mm)

Flue option

outer pipe

inner pipe

Comments

Top outlet

e + a + 877

e + a + 800

maximum

Side flue to

distance 'X' without

(left or right)

extension 1080 mm

Installation of flue assembly

• Fit rubber sealing collar (

C

) into groove at the outer end

of pipe (

A

), 

see diagram 18.

• Fit outer pipe (

A

) into wall with the groove to the outside.

• Pull pipe inwards to bring rubber sealing collar hard up
against external wall, 

see diagram16.

• Fit internal plastic flange (

E

) onto outer pipe. Push along

the pipe until engaged against internal wall.
• From inside, insert inner pipe (

B

) into outer pipe.

• Fit both 'O' rings 

(F)

 into the flue elbow 

(D)

, one at the

inlet, one at the outlet. By necessity, they are a loose fit,
apply a small amount of silicone grease to each 'O' ring
when fitting.

Important

: If the flue has been cut, ensure that there are no

burrs that could damage the 'O' ring.
• Remove the backing from the self adhesive gasket 

(J)

and carefully fit gasket to base of flue elbow.
• Fit elbow onto boiler and secure with the four screws

(G)

.

• Take hold of inner flue, twist clockwise and push gently
onto the elbow outlet taking care not to tear the 'O' ring.
• Fit clamp and seal (

I

) onto outer pipe ensuring a good

seal.

Table 1 :

Содержание THEMA F 23 E

Страница 1: ...1 Heating and hot water for the professionals 01773 828100 IN WARRANTY TECHNICAL HELPLINE 01773 828400 THIS IS A CAT II2H3 APPLIANCE THEMA F Installation and Servicing Instructions...

Страница 2: ...essure switch 19 Spark generator 19 Main printed circuit board 19 Ignition printed circuit board 20 Pump 20 Temperature Pressure gauge 20 Reversing valve assembly 20 Reversing valve front section 21 L...

Страница 3: ...ec tion Alternatively the boiler is designed to allow the flue system to be connected to the top of the boiler top outlet flue connection Refer to the flue fitting instructions Electrical components h...

Страница 4: ...eating output automatically variable from kW 8 9 8 9 8 9 BTU H 30 000 30 000 30 000 to kW 23 3 18 5 23 3 BTU H 80 000 63 000 80 000 Efficiency 91 5 90 5 91 5 Heating adjustment 38 C to 90 C Expansion...

Страница 5: ...799 51214 54628 58042 61456 64871 68285 71699 75113 79552 Heat input kW 11 9 13 2 14 4 15 7 16 9 18 1 19 2 20 4 21 5 22 7 23 8 24 9 26 0 26 9 28 3 Btu h 40678 45130 49332 53481 57579 61627 65626 69575...

Страница 6: ...ressure switch 24 Gas cock A Heating return B Cold water inlet C Heating flow D Domestic hot water flow E Gas supply THEMA F 23 E 22 23 A C E 4 16 17 19 6 8 9 10 11 13 12 21 3 14 24 3 Ignition module...

Страница 7: ...to right the fixing jig comprises A Heating return with isolating valve m C Heating flow with isolating valve q drain screw r and safety valve s E Gas service cock 1 2 5 7 r p q 25 23 113 23 s A C E m...

Страница 8: ...made for filling the system at low level The use of a WRC approved filling loop is strongly recommended connected as shown in diagram 6 Safety valve discharge WARNING It must not discharge above an en...

Страница 9: ...talled immediately protect the various couplings to prevent any ingress of foreign materials e g plaster paint etc Terminal position The minimum acceptable spacings from the ter minal to obstructions...

Страница 10: ...age boiler upper part onto the hook see dia gram 9 Allow the boiler to seat down onto support plate see diagram 10 Fit filter and washers strictly adhering to the se quential order and directions show...

Страница 11: ...aged Calculation of flue cutting lengths Measure wall thickness e mm For side flues measure distance from inside face of side wall to centre line of flue and subtract 176 mm for right hand flue or sub...

Страница 12: ...e outer end of pipe A see diagram 16 Fit outer pipe A into wall with groove to the outside Pull pipe inwards to bring rubber sealing collar hard up against external wall see diagram16 Fit internal pla...

Страница 13: ...ue and subtract 205 mm for both right and left hand flues to get dimension a mm Refer to table 1 for cutting lengths of both inner and outer flue pipes for each of the various flue options available I...

Страница 14: ...arning This appliance must be wired in accord ance with these instructions Any fault arising from incorrect wiring cannot be put right under the terms of the Saunier Duval guarantee Time clock A mecha...

Страница 15: ...wing the instructions given in the User Instruc tions set boiler to run in central heating mode Set boiler thermostat for maximum temperature and check that any external controls if fitted are calling...

Страница 16: ...inue to run The boiler will be ready to operate when the fault has been cleared In case of power supply failure The boiler no longer operates As soon as power supply is restored the boiler will be aut...

Страница 17: ...ss The THEMA F 23 E has a built in bypass This must be adjusted according to the requirements of the sys tem refer to the flow rate pressure curve diagram 3 The boiler is supplied with the built in by...

Страница 18: ...e insulation material on inside faces of combustion chamber Cleaning the burner Pull off leads to ignition electrode Pull off lead to flame sense electrode Unscrew and remove screw holding earth lead...

Страница 19: ...rnal controls connector from mount ing bracket Undo two screws securing microswitch assembly to reversing valve assembly see diagram 29 Remove microswitch assembly from reversing valve Fit replacement...

Страница 20: ...onto inlet connection on replacement pump Fit replacement pump in reverse order to re moval Note Apply silicone grease to pump outlet con nection O ring before assembly Refit pump electrical connecti...

Страница 21: ...it U shaped retaining clip Note Use bypass valve fitted to original front sec tion for guidance Fit replacement front section with gasket to rear section Locate front plate and replace six fixing scre...

Страница 22: ...f water valve When clip is fitted check con nection by pushing pipe back away from water valve Refit telescopic connecting pipe to inlet of wa ter valve after applying silicone grease to O ring Fit re...

Страница 23: ...mini mum clearance of 400mm on one side of the boiler and that no vertical pipework passes between boiler and wall on that side Drain down the heating circuit of the boiler only as described in To rep...

Страница 24: ...and Inspection Pull off lead from flame sense electrode Unscrew and remove screw holding earth lead to flame sense electrode Unscrew and remove screw holding flame sense electrode onto burner Fit rep...

Страница 25: ...14 8 14 9 6 8 6 6 6 4 6 2 6 3 2 2 2 1 9 1 9 2 8 4 8 3 8 2 8 1 12 1 12 2 P THEMA F 23 E PCB N L P Ex EV1 EV TRA 6 14 6 15 6 11 CTN TH V3V TA K5 K4 Pr FL Ra FA Al 6 12 6 9 13 2 13 3 13 1 13 4 14 1 14 2...

Страница 26: ...a logical step by step pro cedure starting at the beginning of the appropriate fault finding chart WARNING Always isolate the boiler from the electri cal supply before carrying out any electrical rep...

Страница 27: ...NOT RUNNING FAN NOT RUNNING Replace main PCB YES CHART 4 NO NO Is pump jammed Replace pump motor NO Free pump Replace main PCB Is fan jammed Replace fan NO SPARE PARTS When ordering spare parts quote...