Remove fan with mounting plate attached by

pulling down and forward out of ‘keyhole’ slots.

Unscrew and remove two screws securing heat

exchanger inspection plate to flue hood.

Remove inspection plate by pulling forward and

off flue hood.

Examine heat exchanger for any blockages or build

up of deposits.

Clean heat exchanger with soft brush or vacuum

cleaner.

Reassembly of parts removed for servicing

All parts are replaced in reverse order to removal.

Note:
1)

 When refitting fan, ensure that it is pushed upwards

as far as the locating lugs will allow.

2)

 When refitting the ignition and flame detection

leads, the RED lead goes to the REAR electrode and
the WHITE lead goes to the FRONT electrode.

ROUTINE CLEANING AND INSPECTION

To ensure the continued efficient and safe opera-
tion of the boiler it is recommended that it is checked
and serviced at regular intervals. The frequency of
servicing will depend upon the particular installa-
tion conditions and usage, but in general once a
year should be enough.

It is the law that any servicing is carried out by a
competent person.

Service Check and Preparation.

Operate boiler and check for any faults that need

to be put right.

Isolate boiler from the gas and electrical supplies.

On completion check all gas carrying parts for

soundness with leak detection fluid.

The maximum domestic hot water flow rate is 12

litres/minute.

Remove boiler casing as follows:

Upper front panel

Remove by pulling free from the spring clips at the

top and bottom.

Side panels

Remove the four screws securing each panel to the

boiler,  two at the top, two at the bottom.

Lift off panel.

Combustion chamber

Unclip four toggle clips holding the sealed chamber

cover

.

Unscrew and remove two screws securing sealed

chamber cover to sealed chamber 

see diag. 1

.

Remove four screws securing combustion chamber

cover to combustion chamber, 

see diagram 2

.

Important:

 Note position of baffle secured by upper

two combustion chamber cover screws.

Pull combustion chamber cover down and out of

boiler, taking care not to damage insulating material
on internal faces of combustion chamber.

Burner

Undo main gas supply nut from burner.

Pull main burner forward, pull off the ignition and

flame sense leads from the electrodes and remove
burner from boiler.

Note: 

The washer between main burner and main

burner gas supply must be kept for use on reassembly.

Remove ignition and flame sense electrodes from

burner.

Unscrew and remove four injector bar retaining

screws and separate injector bar from burner.

Examine and clean injectors as necessary.

Note:

 DO NOT use  a wire or sharp instrument on the

holes.

Heat exchanger

Disconnect power supply leads from fan by

separating at electrical connector.

Unscrew, but do not remove, two fan retaining

screws at lower front edge of fan mounting plate.

Diagram. 1

Diagram. 2

Содержание SYLVA FF 24 E

Страница 1: ...Servicing instructions THIS IS A CAT II2H3 APPLIANCE SYLVA 01773 828100 IN WARRANTY TECHNICAL HELPLINE 01773 828400...

Страница 2: ...2...

Страница 3: ...switch 6 Printed circuit board 6 Central heating thermistor 6 Central heating temperature control 6 Pump 6 7 Temperature gauge 7 Pressure gauge 7 3 way valve head 7 3 way valve 7 Loss of water switch...

Страница 4: ...fluid The maximum domestic hot water flow rate is 12 litres minute Remove boiler casing as follows Upper front panel Remove by pulling free from the spring clips at the top and bottom Side panels Rem...

Страница 5: ...only of storage cylinder preferably when cold Isolate electrical supply to boiler Close isolating valve c on cold water inlet pipe see diagram 3 Drain upper section only of storage cylinder by attach...

Страница 6: ...rew and disconnect two incoming mains wi res Unscrew and disconnect two mains warning light wires Remove screws securing PCB to control panel and lift out PCB Fit replacement PCB in reverse order to r...

Страница 7: ...drain down entire heating system to carry out this work Remove 3 way valve head as described previously Unscrew three nuts securing 3 way valve to pipework and lift out 3 way valve making note of the...

Страница 8: ...connection on fixing jig see diagram 3 Refill storage tank and vent cylinder Check for leaks To replace anode To replace anode it is necessary to drain upper sec tion only of storage cylinder preferab...

Страница 9: ...nscrew and remove screws securing expansion vessel to boiler Lift vessel out of boiler Fit replacement vessel to boiler in reverse order to removal ensuring that sealing washer is fitted to pipe conne...

Страница 10: ...Cold water inlet C Heating flow D Domestic hot water flow F Gas supply 1 3 way valve 2 Loss of water switch 3 Pump 4 CVI unit 5 Gas valve 6 Ignition electrode 7 Injector manifold 8 Flame detection ele...

Страница 11: ...81 m3 h 2 10 kg h 2 06 kg h Gas rate minimum 1 32 m3 h 0 98 kg h 0 97 kg h Gas reference 15 1013 mbar Burner pressures burner pressures as listed in the table below must be checked after the boiler ha...

Страница 12: ...tors A7 Clock option connector BR Reset button CTN Thermistor EV1 Modulating valve EV Main gas valve EX Fan E H Summer Winter switch F1 F2 F3 Fuses FA Ignition elctrode FL Flame sense electrode IG Mai...

Страница 13: ...works but the heating doesn t refer to chart No 1 If heating works correctly but the hot water doesn t refer to chart No 2 IMPORTANT Always adopt a logical step by step procedure starting at the begin...

Страница 14: ...tral heat ing potentiometer Replace central heating thermistor Faulty PCB replace Are heating controls calling for heat NO NO NO NO NO YES DHW ok Replace domestic hot water thermostat Replace 3 way va...

Страница 15: ...fitted and free of obstructions Check for correct fit of sealed chamber cover Is pump running at full speed Does burner remain on for less than 5 seconds Is fan running at full speed Refer to chart N...

Страница 16: ...al heating safety valve 56110 12 Expansion valve 6bar 56029 13 T P relief valve 7bar 56108 14 Anode 56000 15 High limit thermostat 56012 16 Ignition flame sense electrode 56002 85890 B 07 97 CHART N 5...

Отзывы: