FAULT FINDING

CHART N

°

 1

NO CENTRAL

HEATING

CHART N

°

 2

NO DOMESTIC

HOT WATER

NO

NO

NO

NO

NO

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

YES

YES

Does burner fire?

Refer to chart No.3.

Set controls to call for heat.

Are external controls wired?

Rectify wiring.

Is burner pressure correct? -

Refer to technical data.

Heating ok.

Is the range rating potentiometer

correctly adjusted?

Adjust potentiometer to required

setting - does potentiometer

adjust burner pressure?

Faulty potentiometer - replace

PCB.

YES

YES

Does burner fire when a hot tap

is opened for approximately 3 

minutes ?

Is plug to the external controls 
connected to the boiler ?

Connect external controls plug.

Remove leads from central 
heating thermistor. Check its 
resistance in accordance with 
diagram 17 - is central heating 
thermistor OK ?

Remove potentiometer connec-
tor from A5 on PCB. Check resis-
tance of heating potentiometer 
between white and black leads
- does it adjust between 0-1 k

 ?

Replace central heat-
ing potentiometer

Replace central 
heating thermistor

Faulty PCB - replace

Are heating controls calling for heat ? 

NO

NO

NO

NO

NO

YES

DHW ok.

Replace domestic hot water

thermostat

Replace 3 - way

valve  head

Refer to 

chart N

°

5

NO

NO

NO

YES

YES

YES

YES

YES

YES

With the "Summer/winter" switch in the 
winter, hot water and central heating 
position - does the burne fire for central 
heating ?

Refer to chart No.3.

Remove domestic hot water thermostat 
connector from A3 on PCB. Turn thermos-
tat up maximum - Is there continuity bet-
ween the two thermostat leads ?

Check PCB - replace if necessary

Replace domestic hot water thermostat

Is the hot water hot enough ?

Adjust domestic hot water

thermostat

Is the domestic hot water 
thermostat set to the desired 
position ?

Check operation of 3 - way valve 
- is there flow of hot water to 
storage cylinder flow pipe ?

Is domestic hot water thermostat 
working correctly, that is, by 
turning to maximum does burner 
fire, by turning to minimum does 
burner go out ?

Operate 3 - way valve 
manually - is there flow 
of hot water to storage 
cylinder flow pipe ?

Does the burner fire when a hot tap is 
opened for aproximately 3 minutes ?

Содержание SYLVA FF 24 E

Страница 1: ...Servicing instructions THIS IS A CAT II2H3 APPLIANCE SYLVA 01773 828100 IN WARRANTY TECHNICAL HELPLINE 01773 828400...

Страница 2: ...2...

Страница 3: ...switch 6 Printed circuit board 6 Central heating thermistor 6 Central heating temperature control 6 Pump 6 7 Temperature gauge 7 Pressure gauge 7 3 way valve head 7 3 way valve 7 Loss of water switch...

Страница 4: ...fluid The maximum domestic hot water flow rate is 12 litres minute Remove boiler casing as follows Upper front panel Remove by pulling free from the spring clips at the top and bottom Side panels Rem...

Страница 5: ...only of storage cylinder preferably when cold Isolate electrical supply to boiler Close isolating valve c on cold water inlet pipe see diagram 3 Drain upper section only of storage cylinder by attach...

Страница 6: ...rew and disconnect two incoming mains wi res Unscrew and disconnect two mains warning light wires Remove screws securing PCB to control panel and lift out PCB Fit replacement PCB in reverse order to r...

Страница 7: ...drain down entire heating system to carry out this work Remove 3 way valve head as described previously Unscrew three nuts securing 3 way valve to pipework and lift out 3 way valve making note of the...

Страница 8: ...connection on fixing jig see diagram 3 Refill storage tank and vent cylinder Check for leaks To replace anode To replace anode it is necessary to drain upper sec tion only of storage cylinder preferab...

Страница 9: ...nscrew and remove screws securing expansion vessel to boiler Lift vessel out of boiler Fit replacement vessel to boiler in reverse order to removal ensuring that sealing washer is fitted to pipe conne...

Страница 10: ...Cold water inlet C Heating flow D Domestic hot water flow F Gas supply 1 3 way valve 2 Loss of water switch 3 Pump 4 CVI unit 5 Gas valve 6 Ignition electrode 7 Injector manifold 8 Flame detection ele...

Страница 11: ...81 m3 h 2 10 kg h 2 06 kg h Gas rate minimum 1 32 m3 h 0 98 kg h 0 97 kg h Gas reference 15 1013 mbar Burner pressures burner pressures as listed in the table below must be checked after the boiler ha...

Страница 12: ...tors A7 Clock option connector BR Reset button CTN Thermistor EV1 Modulating valve EV Main gas valve EX Fan E H Summer Winter switch F1 F2 F3 Fuses FA Ignition elctrode FL Flame sense electrode IG Mai...

Страница 13: ...works but the heating doesn t refer to chart No 1 If heating works correctly but the hot water doesn t refer to chart No 2 IMPORTANT Always adopt a logical step by step procedure starting at the begin...

Страница 14: ...tral heat ing potentiometer Replace central heating thermistor Faulty PCB replace Are heating controls calling for heat NO NO NO NO NO YES DHW ok Replace domestic hot water thermostat Replace 3 way va...

Страница 15: ...fitted and free of obstructions Check for correct fit of sealed chamber cover Is pump running at full speed Does burner remain on for less than 5 seconds Is fan running at full speed Refer to chart N...

Страница 16: ...al heating safety valve 56110 12 Expansion valve 6bar 56029 13 T P relief valve 7bar 56108 14 Anode 56000 15 High limit thermostat 56012 16 Ignition flame sense electrode 56002 85890 B 07 97 CHART N 5...