Fixed ON time – OFF if door closed

 [ON, close

off] – the relay output will be turned on 

until the door is closed (door status input is reconnected to common ground), however 
not longer than for the “Relay ON time”. 

Relay ON time 

– the time during which the relay output can be turned on after the access is 

granted. You can program from 1 to 255 seconds. 

 

 

Fig. 4. DLOADX program: parameters and options of code lock. 

 

Relay

 [Relay type] – status of the deactivated relay: 

NO

 [Normal.open NO] – the relay contacts are open (they close on activating the relay). 

NC

 [Normal.closed NC] – the relay contacts are closed (they open on activating the relay). 

Authorization

 

control 

[Unauth. event] –  if this option is enabled, unauthorized opening of 

the door will save the event to the control panel memory. 

Alarm on unauth. access 

[Unauth. alarm] – if this option is enabled, unauthorized opening 

of the door when the partition is armed will trigger an alarm. The option is available if the 
“Authorization control”

 

option is enabled. 

Max. door open time

 [Max. door open] – the maximum period of time during which the door 

can be open (the door status input can be disconnected from common ground). If the door 
is open longer, audible alarm will be triggered in the code lock, and the event will be saved 
to the control panel memory. You can enter from the 0 to 255 seconds. If you enter 0, the 
door can be open for any long period of time. 

Содержание INT-SZ

Страница 1: ...INT SZ Code lock Firmware version 2 02 int sz_en 08 20 SATEL sp z o o ul Budowlanych 66 80 298 Gda sk POLAND tel 48 58 320 94 00 www satel eu...

Страница 2: ...rights under the warranty SATEL aims to continually improve the quality of its products which may result in changes in their technical specifications and software Current information about the change...

Страница 3: ...ng 4 3 1 Description of parameters and options 4 4 Using 7 4 1 LED indicators 7 4 2 Sound signaling 7 4 2 1 Beeps generated when operating 7 4 2 2 Signaling events 7 4 3 Code 8 4 4 Available functions...

Страница 4: ...n flap cover 1 Features Single door control relay output for control of electric strike electromagnetic lock or another door actuator door status input NC Capability of triggering alarm from the keypa...

Страница 5: ...twisted pair cable The wires must be run in one cable 8 Connect the wires for control of electric strike electromagnetic lock or another door actuator to the NO terminals see Fig 2 It is not recommend...

Страница 6: ...dules branch code lock name LCD keypad Service mode Structure Hardware Expanders Settings code lock name 3 1 Description of parameters and options Names of parameters and options from the DLOADX progr...

Страница 7: ...sed they open on activating the relay Authorization control Unauth event if this option is enabled unauthorized opening of the door will save the event to the control panel memory Alarm on unauth acce...

Страница 8: ...bled entering a wrong code three times will trigger an alarm Control BI output BI outs ctrl if this option is enabled the Bi output operating type of users can use the code lock to control outputs Con...

Страница 9: ...he event of fire alarm in the partition to which the code lock belongs Object fire alarm on object fire the door will be unlocked in the event of fire alarm in the object to which the code lock belong...

Страница 10: ...e outputs turn on the 24 MONO switch type outputs confirm the guard round temporary block the partition 4 4 2 Triggering the alarm from keypad The installer can permit triggering alarms from the keypa...

Страница 11: ...SATEL INT SZ 9 Relay output resistive load 1 A 30 VDC Environmental class according to EN50130 5 II Operating temperature range 10 C 55 C Maximum humidity 93 3 Dimensions 80 x 127 x 24 mm Weight 110 g...

Отзывы: