background image

SATEL 

INT-SZ 

The code lock is designed for indoor installation. The place of installation should be readily 
accessible to the system users. 

1.  Open the code lock enclosure. 

2.  Set the code lock address (see “Address setting” p. 3). 

3.  Place the enclosure base on the wall and mark the location of mounting holes.  

4.  Drill the holes for wall plugs (anchors). 

5.  Run the wires through the opening in the enclosure base. 

6.  Using wall plugs (anchors) and screws, fasten the enclosure base to the wall. Select wall 

plugs specifically intended for the mounting surface (different for concrete or brick wall, 
different for drywall, etc.). 

7.  Connect the CLK, DTA and COM terminals to the  appropriate terminals of the control 

panel expander bus (see  the control panel installer manual). It is recommended that an 
unshielded non-twisted cable be used for making the connection. If you use the twisted-
pair type of cable, remember that CLK (clock) and DTA (data) signals must not be sent 
through one twisted-pair cable. The wires must be run in one cable. 

8.  Connect the wires for control of electric strike, electromagnetic lock or another door 

actuator to the NO terminals (see Fig. 2). It is not recommended that the door actuator be 
powered from the same source as the code lock. 

 

 

Fig. 2. Connecting the actuator to the code lock. 

 
9.  If the code lock is to supervise the door status, connect the detector supervising the door 

status to the IN and COM terminals. If the code lock is not to supervise the door status, 
connect the IN terminal to the COM terminal or, when configuring the code lock, set value 
0 for the “Max. door open time” parameter. 

10. Connect the power wires to the 12V and COM terminals. The code lock may be powered 

directly  from the control panel, from an expander with power supply or from a power 
supply unit. 

11. Close the enclosure. 

12. Power on the alarm system. 

13. Start the identification function in the control panel (see the control panel installer 

manual). The code lock will be identified as “INT-SZ/SZK”. 

2.1  Address setting 

An individual address (different from that in the other devices connected to the control panel 
bus) must be set in the code lock. 

Содержание INT-SZ

Страница 1: ...INT SZ Code lock Firmware version 2 02 int sz_en 08 20 SATEL sp z o o ul Budowlanych 66 80 298 Gda sk POLAND tel 48 58 320 94 00 www satel eu...

Страница 2: ...rights under the warranty SATEL aims to continually improve the quality of its products which may result in changes in their technical specifications and software Current information about the change...

Страница 3: ...ng 4 3 1 Description of parameters and options 4 4 Using 7 4 1 LED indicators 7 4 2 Sound signaling 7 4 2 1 Beeps generated when operating 7 4 2 2 Signaling events 7 4 3 Code 8 4 4 Available functions...

Страница 4: ...n flap cover 1 Features Single door control relay output for control of electric strike electromagnetic lock or another door actuator door status input NC Capability of triggering alarm from the keypa...

Страница 5: ...twisted pair cable The wires must be run in one cable 8 Connect the wires for control of electric strike electromagnetic lock or another door actuator to the NO terminals see Fig 2 It is not recommend...

Страница 6: ...dules branch code lock name LCD keypad Service mode Structure Hardware Expanders Settings code lock name 3 1 Description of parameters and options Names of parameters and options from the DLOADX progr...

Страница 7: ...sed they open on activating the relay Authorization control Unauth event if this option is enabled unauthorized opening of the door will save the event to the control panel memory Alarm on unauth acce...

Страница 8: ...bled entering a wrong code three times will trigger an alarm Control BI output BI outs ctrl if this option is enabled the Bi output operating type of users can use the code lock to control outputs Con...

Страница 9: ...he event of fire alarm in the partition to which the code lock belongs Object fire alarm on object fire the door will be unlocked in the event of fire alarm in the object to which the code lock belong...

Страница 10: ...e outputs turn on the 24 MONO switch type outputs confirm the guard round temporary block the partition 4 4 2 Triggering the alarm from keypad The installer can permit triggering alarms from the keypa...

Страница 11: ...SATEL INT SZ 9 Relay output resistive load 1 A 30 VDC Environmental class according to EN50130 5 II Operating temperature range 10 C 55 C Maximum humidity 93 3 Dimensions 80 x 127 x 24 mm Weight 110 g...

Отзывы: