Operating The PM295
55
AccS
PASS
1234
To change the user password:
Ä
Press
SELECT
to choose the lower window.
Ä
Adjust the password with the up/down arrow keys. The
password is up to four digits long.
Ä
Press
ENTER
to return to the central window.
Store your password in a safe place. If you will not provide the correct
password, you will need to contact your local distributor for the superuser
password to override password protection.
Enabling/Disabling Password Checking
Ä
From the central window, select the
CtrL
entry with the up/down arrow keys.
AccS
CtrL
OFF
To change the password protection mode:
Ä
Press
SELECT
to choose the lower window.
Ä
With the up/down arrow keys select
OFF
to disable
password protection, and select
On
to enable password
protection.
Ä
Press
ENTER
to return to the central window.
3.4 Self-Test Diagnostics
The
PM295
periodically performs self-test diagnostics. If the instrument fails the
self-test diagnostics, it discards the last measurement results, and an error code is
displayed for one second on all LEDs. Error codes are listed in
Table 3.1
. Frequent
failures may be result of excessive electrical noise in the region of the instrument. If
the instrument resets itself continuously, contact your local distributor.
Table 3-1 Self-Test Diagnostic Codes
Diagnostic Code
Meaning
1
ROM error
2
RAM error
3
Watch dog timer reset
4
Sampling failure
5
Out of control trap
7
Timing failure
8
Power up