Operating The PM295
47
To enter a sub-menu:
Ä
From the upper window, select the sub-menu entry with the up/down arrow
keys.
Ä
Press
SELECT
to enter the selected sub-menu. For instructions on operating
sub-menus, see the paragraphs below.
To quit the secondary menu and return to the primary menu:
Ä
Press
SELECT
to choose the upper window.
Ä
Press
ENTER
to return to the primary menu.
Viewing and Changing a Setpoint Condition
Each condition sub-menu displays the setup parameters for one of four setpoint
triggers. For information on specifying setpoint triggers, refer to
Section 4.17.3
. To
enter a sub-menu, choose one of the entries
Cnd1
to
Cnd4
in the upper window
using the up/down arrow keys, then press
SELECT
. The following illustrations show
the sub-menu windows:
Cnd1
ConJ
Or
Cnd1
GrP
rt.Hi
Cnd1
InP
cur
Cnd1
Cond
GE
Cnd1
On
3000
Cnd1
OFF
2950
Conjunction
operation
(Or/And)
Trigger
parameter
group
Trigger
parameter
name
Operate
condition
(GE/LE
Eq/nE
On/OFF
nEU)
Operate
limit
Release
limit
To view the trigger parameters:
Ä
From the central window, scroll through the list of parameters with the up/down
arrow keys. The lower window will display the current parameter setup.
All trigger parameters that can be used for setpoint operation are organized in
groups that are listed in
Table B-6
(see
Appendix B
) with the corresponding group
label. The trigger parameter is defined by both the parameter group and parameter