Chapter 5 Data Display
34
Fast Reset of Accumulated Data
When changing data via the front panel is not secured by a
password, you can reset the Min/Max registers, maximum
demands and energies from the display mode without entering the
reset menu.
Select the display page of the data you want to reset. To reset:
•
Min/Max log registers: select a Min/Max page from the
Min/Max measurements display (where a Max or Min round
LED is illuminated).
•
Ampere and volt maximum demands: select the ampere or
volt maximum demand page from the Min/Max
measurements display (where a MAX DMD LED is
illuminated, and volts or amps LEDs at the right are lit).
•
Power maximum demands: select the power maximum
demand page from the Min/Max measurements display
(where a MAX DMD LED is illuminated, and kVA/MVA and
kW/MW LEDs at the right are lit).
•
Total and phase energies: select the energy measurements
display.
While holding the key, press and hold for
about 5 seconds. The displayed data is reset to zero.
5.2 Data Display Formats
The display windows are labeled in the table as follows: 1 = upper
window, 2 = middle window, 3 = lower window.
Table 5-1 Displayed Parameters for the
PM130
Page Window Indicator
LED
Parameter
Digits Unit
Common Measurements
1 1
V1/V1-2
Voltage L12
4
V/kV
1 2
V2/V2-3
Voltage L23
4
V/kV
1 3
V3/V3-1 L.
Voltage L31
4 V/kV
2 1
V1/V1-2
Voltage L1 4
V/kV
2 2
V2/V2-3
Voltage L2 4
V/kV
2 3
V3/V3-1 P.
Voltage L3
4 V/kV
3 1
A1
Current L1
4
A/kA
3 2
A2
Current L2
4
A/kA
3 3
A3
Current L3
4
A/kA
4 1
A Neut
Neutral current
4
A/kA
4 2
Hz
Frequency
4
Hz
4 3
Phase
Rot.
Phase rotation sequence
(POS/NEG/ERR)
4
SELECT
ENTER
Содержание PM130E
Страница 1: ...Se Series PM130 Powermeters Installation and Operation Manual BG0306 Rev A1 ...
Страница 2: ...Series PM130 Powermeters Installation and Operation Manual ...
Страница 6: ...iv Quick Start TYPICAL INSTALLATION see Section 2 2 4 for full instructions Wiring Mode 4LL3 ...
Страница 12: ...Chapter 1 Introduction 5 Instrument Dimensions Figure 1 1 PM130 Dimensions ...
Страница 14: ...Chapter 2 Installation 7 Figure 2 2 The PM130 Terminations ...
Страница 17: ...Chapter 2 Installation 10 Figure 2 4 Current Input Connection ...