![Satec PM130E Скачать руководство пользователя страница 29](http://html.mh-extra.com/html/satec/pm130e/pm130e_installation-and-operation-manual_1200370029.webp)
Chapter 4 Setup Menus
22
4.3 Pulsing Output Setup Menu
(PM130E)
This menu allows you to program a relay (optional) provided by
your
PM130E
instrument to output energy pulses. Available
pulsing parameters are listed in Table 4-3.
To change the pulse relay setup:
Press to activate the middle window.
Use the up/down arrow keys to scroll to the desired
output parameter. Selecting
nonE
disables pulsing
through this relay.
Press to activate the lower window.
Use the up/down arrow keys to set the amount of
unit-hours per pulse. The available range is 1-9999.
Press to store the new setup, or press
to quit the setup without changes.
To quit the pulsing setup menu:
From the upper window, press or .
Table 4-3 Pulsing Output Parameters
Code
Parameter
Units
nonE Output
disabled
Ac.Ei
Active energy import
kWh import (positive)
Ac.EE
Active energy export
kWh export (negative)
rE.Ei
Reactive energy import kvarh import (inductive)
rE.EE
Reactive energy export kvarh export (capacitive)
rE.Et
Reactive energy total
kvarh total (absolute)
AP.Et
Apparent energy total
kVAh total
NOTES
1.
If your instrument is not equipped with the optional relay, then this
setup parameter will not appear on the display.
2.
You will not be able to store your setup in the instrument if you
assigned a parameter to relay output with a zero number of unit-
hours per pulse.
3.
If a relay you allocated for pulsing has been manually operated or
released, it reverts automatically to normal operation.
4.
If a relay you allocated for pulsing has been engaged by an
alarm/event setpoint, the setpoint is automatically disabled.
SELECT
SELECT
ENTER
ESC
ESC
ENTER
rEL
1
Ac.Ei
SELECT
CHG
PulS
ENTER
ENTER
Содержание PM130E
Страница 1: ...Se Series PM130 Powermeters Installation and Operation Manual BG0306 Rev A1 ...
Страница 2: ...Series PM130 Powermeters Installation and Operation Manual ...
Страница 6: ...iv Quick Start TYPICAL INSTALLATION see Section 2 2 4 for full instructions Wiring Mode 4LL3 ...
Страница 12: ...Chapter 1 Introduction 5 Instrument Dimensions Figure 1 1 PM130 Dimensions ...
Страница 14: ...Chapter 2 Installation 7 Figure 2 2 The PM130 Terminations ...
Страница 17: ...Chapter 2 Installation 10 Figure 2 4 Current Input Connection ...