Satec PM130E Скачать руководство пользователя страница 1

 

 

Se

 

Series 

P

M1

3

0

        

 

P

owermeters

 

 

Installation 

 

and Operatio

 

M

an

ual

 

 
 
 

BG0

306

  Rev.

 A1

Содержание PM130E

Страница 1: ...Se Series PM130 Powermeters Installation and Operation Manual BG0306 Rev A1 ...

Страница 2: ...Series PM130 Powermeters Installation and Operation Manual ...

Страница 3: ... taken to manufacture and calibrate your instrument However these instructions do not cover all possible contingencies that may arise during installation operation or maintenance and all details and variations of this equipment are not covered by these instructions For additional information regarding installation operation or maintenance of this instrument contact the manufacturer or your local r...

Страница 4: ...and is secured using an external strain relief to reduce mechanical strain on the screw terminals if necessary Setup procedures must be performed only by qualified personnel familiar with the instrument and its associated electrical equipment DO NOT open the instrument under any circumstances Modbus is a trademark of Modicon Inc Read this manual thoroughly before connecting the meter to the curren...

Страница 5: ... 4 3 Pulsing Output Setup Menu PM130E 22 4 4 Alarm Event Setpoints Setup Menu 23 4 5 Relay Operation Control Menu 27 4 6 Display Setup Menu 28 4 7 User Selectable Options Menu 29 4 8 Access Control Menu 30 4 9 Reset Synchronization Menu 31 Chapter 5 Data Display 32 5 1 Navigating in the Display Mode 32 5 2 Data Display Formats 34 5 3 Self Test Diagnostics Display 39 Chapter 6 Viewing Status Inform...

Страница 6: ...iv Quick Start TYPICAL INSTALLATION see Section 2 2 4 for full instructions Wiring Mode 4LL3 ...

Страница 7: ...current transformer d P Power demand period 1 2 5 10 15 20 30 60 E The length of the period for power demand calculations in minutes E external synchronization n dp Number of power demand periods 1 15 1 The number of demand periods to be averaged for sliding window demands 1 block interval demand calculation A dP Ampere Volt demand period 0 1800 900 The length of the period for volt ampere demand ...

Страница 8: ...information may be useful during installation Technical Specifications for the PM130 are found in the Appendix 1 2 About The PM130 The PM130 is a compact panel mounted 3 phase AC Powermeter specially designed to meet the requirements of users ranging from electrical panel builders to substation operators The PM130 is available in three models the PM130 for basic voltage current and frequency measu...

Страница 9: ...mode P cAL Mode 1 Reactive power calculation rEAc Active power P and reactive power Q are measured directly and apparent power S P2 Q2 Mode 2 Non active power calculation nAct Active power is measured directly and apparent power S V I V I rms voltage and currents and non active power N S 2 P2 Mode 1 is recommended for electrical networks with low harmonic distortion voltage THD 5 current THD 10 Mo...

Страница 10: ...uency setup via PC setup via panel Average RMS Voltage per phase Average RMS Current per phase Average Frequency Average Neutral Current Voltage Current unbalance Amps Volt Demand Parameters Ampere Demand per phase Volt Demand per phase Ampere Maximum Demand per phase Voltage Max Demand per phase Average Power values Average Active Power per phase Average Reactive Power per phase Average Apparent ...

Страница 11: ... Reactive Energy Absolute Total Apparent Energy Min Max Log Min Max Volts Min Max A Neutral current Min Max frequency Min Max kW kvar kVA PF Real time Amps Volts Frequency RT RMS Voltage per phase RT RMS Current per phase RT Frequency RT Neutral Current RT Voltage Current unbalance Real time Power Values RT Active Power per phase RT Reactive Power per phase RT Apparent Power per phase RT Total Act...

Страница 12: ...Chapter 1 Introduction 5 Instrument Dimensions Figure 1 1 PM130 Dimensions ...

Страница 13: ...ter 2 Installation 6 Chapter 2 Installation 2 2 1 Mechanical Installation 1 Position Powermeter in cut out 2 Affix the Powermeter using washers and nuts Figure 2 1 Mounting the PM130 Square or Round Cut out ...

Страница 14: ...Chapter 2 Installation 7 Figure 2 2 The PM130 Terminations ...

Страница 15: ...power supply communication and optional relay output and CT cores located on the rear of the instrument as shown in Figure 2 3 Note If your PM130 was not ordered with the optional relay it will not have the relay connector Figure 2 3 PM130 Connections Rear View 2 2 1 Power Supply Connection The power supply can be dedicated fused or from a monitored voltage if it is within the instrument s power s...

Страница 16: ...ure 2 4 In the case of a retrofit where each external CT ends with two wires pass one wire through the core and connect it to one of the instrument termination screws connect the second wire from the termination screw to the external CT to close the loop One wire must pass through the core observe the arrow which indicates the current direction see Figure 2 4 2 2 3 Ground Connect the ground PM130 ...

Страница 17: ...Chapter 2 Installation 10 Figure 2 4 Current Input Connection ...

Страница 18: ...rations Wiring Mode Definition See parameter setup instructions in Section 4 1 3 wire direct connection using 2 CTs 2 element 3dir2 Figure 2 5 4 wire WYE direct connection using 3 CTs 3 element 4Ln3 or 4LL3 Figure 2 6 4 wire WYE connection using 3 PTs 3 CTs 3 element 4Ln3 or 4LL3 Figure 2 7 3 wire open delta connection using 2 PTs 2 CTs 2 element 3OP2 Figure 2 8 3 wire open delta connection using ...

Страница 19: ...Chapter 2 Installation 12 Figure 2 6 Four Wire WYE Direct Connection Using 3 CTs 3 element Wiring Mode 4LL3 or 4Ln3 Figure 2 5 Three Wire Direct Connection Using 2 CTs 2 element Wiring Mode 3dir2 ...

Страница 20: ...hapter 2 Installation 13 Figure 2 7 Four Wire WYE Connection Using 3 PTs 3 CTs 3 element Wiring Mode 4LL3 or 4Ln3 Figure 2 8 Three Wire Open Delta Connection Using 2 PTs 2 CTs 2 element Wiring Mode 3OP2 ...

Страница 21: ... Connection Using 2 PTs 3 CTs 2 element Wiring Mode 3LL3 or 3Ln3 Note This configuration will provide accurate power measurements only if the voltages are balanced Figure 2 9 Three Wire Open Delta Connection Using 2 PTs 3 CTs 2 element Wiring Mode 3OP3 ...

Страница 22: ...1 Four Wire Delta Direct Connection Using 3 CTs 3 element Wiring Mode 4LL3 or 4Ln3 2 2 5 Relay One relay optional is provided for energy pulsing alarms or remote control Figure 2 12 Relay Connection c99 07014 RELAY N 120V AC LOAD 10A FUSE ...

Страница 23: ...ultidrop Computer Connection NOTE Where an RS 232 RS 485 converter is used on a computer connection R1 is not applicable since it is built in to the converter Activity on the communications port lines is indicated via the Status Information menu see Chapter 6 A full description of the communication protocols may be found in the PM130 ASCII Modbus or DNP3 0 Communications Manuals provided with your...

Страница 24: ...epending on the model of your instrument some menus may not appear Password The Setup Change Menu can be secured by a user defined password comprised of 4 digits The instrument is shipped with password protection disabled To enable password protection go to the Access Control Menu see Section 4 13 The Password Menu appears if password protection is enabled To enter a password Set the first digit u...

Страница 25: ... Display Setup Reset Functions Selectable Options Access Control ENTER ENTER PHAS rEL Cnt 1 Cnt 2 Cnt 3 Cnt 4 Port Phase Rotation Relay Status Counter 1 Counter 2 Counter 3 Counter 4 Port status E available in the PM130E E SELECT Selects an active window Enters menu sub menu Quits menu sub menu Scrolls options forward Scrolls options backward ENTER ESC E P available in the PM130P P E P rELo Relay ...

Страница 26: ...e middle window to scroll through the list of available options and then activate the lower window to set the option value To select and view a setup option Press to activate the middle window Use the up down arrow keys to scroll to the desired option The current value for this option appears in the lower window To change the value of the selected option Press to make the lower window active Press...

Страница 27: ...suring peak current buF Averaging buffer size 8 16 32 The number of measurements for RMS sliding averaging rSt Reset enable disable diS En Protects all reset functions both via the front panel or communications Freq Nominal frequency 50 60 Hz The nominal power utility frequency Synchronization of the power demand interval can be made through communications see the PM130 Communications Reference Gu...

Страница 28: ...indow To change the selected option Press to activate the lower window Press the up down arrow keys to scroll to the desired value Press to store the selected value or press to quit the setup menu Table 4 2 Communications Options default setting Code Parameter Options Description Prot Communications protocol ASCII rtu dnP3 ASCII protocol Modbus RTU protocol DNP3 0 protocol rS Interface standard 48...

Страница 29: ...ode Parameter Units nonE Output disabled Ac Ei Active energy import kWh import positive Ac EE Active energy export kWh export negative rE Ei Reactive energy import kvarh import inductive rE EE Reactive energy export kvarh export capacitive rE Et Reactive energy total kvarh total absolute AP Et Apparent energy total kVAh total NOTES 1 If your instrument is not equipped with the optional relay then ...

Страница 30: ... setpoint setup parameters available triggers and setpoint actions Example Trigger parameter Setpoint 1 is set to monitor the real time high current on phase 1 the trigger parameter Operate limit Release limit The operate On and release OFF limits which determine setpoint operation are defined as 1200A and 1100A respectively Operate delay Release delay The delays before operation On d and release ...

Страница 31: ...ach time you select a new trigger parameter the operate and release limits are set by default to zero 4 You will not be able to store your setpoint setup to the instrument if a setpoint action is directed to a relay allocated for pulsing 5 The setpoint action directed to a relay output can be overridden using commands sent via communications A relay can be manually operated or released When the re...

Страница 32: ...ax A Lo C3 Low current L3 A 0 to Imax Average Values on any Phase A Hi U High voltage V 0 to Vmax A Lo U Low voltage V 0 to Vmax A Hi C High current A 0 to Imax A Lo C Low current A 0 to Imax Average Total Values A Hi P i High total kW import positive kW 0 to Pmax A Hi P E High total kW export negative kW 0 to Pmax A Hi q i High total kvar import positive kvar 0 to Pmax A Hi q E High total kvar ex...

Страница 33: ...eutral for any other wiring mode they will be line to line Table 4 6 Setpoint Actions lower window when middle window is Act Code Action nonE No action rEL Operate relay In Cn 1 Increment counter 1 In Cn 2 Increment counter 2 In Cn 3 Increment counter 3 In Cn 4 Increment counter 4 ti Cn 1 Count operating time using counter 1 ti Cn 1 Count operating time using counter 2 ti Cn 1 Count operating time...

Страница 34: ...ration A failsafe relay is closed only if it is under setpoint control and no alarm conditions exist or if it is manually operated via communications To change the relay operation mode Press to activate the lower window Use the up down arrow keys to set the desired option Select nor for normal non failsafe relay operation or select FSAFE for failsafe relay operation Press to store your new setting...

Страница 35: ...inal load current for LED bar graph 0 50000A 0 defines the nominal load 100 level for the bar graph display 0 CT primary current Ph P Phase powers display mode diS En disables enables display of phase powers in common measurements To select a display option Press to activate the middle window and then use the up down arrow keys to scroll to the desired option To change the display option Press to ...

Страница 36: ...set the desired value Press to store your new setting or to leave the previous setting unchanged To quit the display setup menu From the middle window press or Table 4 8 User Selectable Options default setting Code Parameter Options Description P cAL Power calculation mode rEAc nAct Using reactive power Using non active power roLL Energy roll value 10 E4 10 E5 10 E6 10 E7 10 E8 10 000 100 000 1 00...

Страница 37: ...e the password unchanged To enable disable password checking Press to activate the middle window and then use the up down arrow keys to move to the CtrL entry Press to activate the lower window Use the up down arrow keys to change the password checking status select OFF to disable password protection or select On to enable password protection Press to store your new option or to leave the option u...

Страница 38: ...own arrow keys to scroll to the desired data location entry Press to activate the lower window Press and hold for about 5 seconds until the do label is replaced with done release the key You will return to the middle window Press to quit the menu NOTES If you select the d Snc entry take into consideration the following 1 If the power demand period is specified in minutes see Section 4 1 Basic Setu...

Страница 39: ...backward Returns to the first page within current measurement group For each display page up to three parameters can be displayed The Load bar graph displays the amount in percent of the current load with respect to user defined nominal load current The highest current measured by the PM130 is divided by the nominal load current as defined in the Display Setup Menu see Section 4 6 and expressed as...

Страница 40: ...e last page that was displayed prior to loss of power Selecting a Display Page Press the up down arrow keys to scroll through display pages Selecting Common Measurements Press the key pointed to by the illuminated round LED below the front panel display If no LED is lit up this means that the front panel displays the common measurements parameters When Display Auto Scroll is in effect see Section ...

Страница 41: ...he Min Max measurements display where a MAX DMD LED is illuminated and kVA MVA and kW MW LEDs at the right are lit Total and phase energies select the energy measurements display While holding the key press and hold for about 5 seconds The displayed data is reset to zero 5 2 Data Display Formats The display windows are labeled in the table as follows 1 upper window 2 middle window 3 lower window T...

Страница 42: ... ampere demand L2 4 A kA 3 3 A3 Max ampere demand L3 4 A kA Displayed readings for all electrical quantities except Min Max log are sliding average values Voltage and current readings with a decimal point are displayed in kV and kA When the value width exceeds the window resolution the right most digits are truncated When the 4LN3 or 3LN3 wiring mode is selected the voltages will be line to neutra...

Страница 43: ...VA MVA 4 2 PF Total power factor 4 4 3 kW Total kW 4 kW MW 5 1 A NEUT Neutral current 4 A kA 5 2 Hz Frequency 4 Hz 5 3 kvar Total kvar 4 kvar Mvar 6 1 Ph L1 Label 6 2 PF Power factor L1 4 6 3 kW kW L1 4 kW MW 7 1 kVA kVA L1 4 kVA MVA 7 2 Ph L1 Label 7 3 kvar kvar L1 4 kvar Mvar 8 1 Ph L2 Label 8 2 PF Power factor L2 4 8 3 kW kW L2 4 kW MW 9 1 kVA kVA L2 4 kVA MVA 9 2 Ph L2 Label 9 3 kvar kvar L2 4...

Страница 44: ...4 A kA 4 2 Hz Min real time frequency 4 Hz 4 3 kvar Min real time total kvar 4 kvar Mvar MAX 5 1 V1 V1 2 Max real time voltage L1 L12 4 V kV 5 2 V2 V2 3 Max real time voltage L2 L23 4 V kV 5 3 V3 V3 1 Max real time voltage L3 L31 4 V kV 6 1 A1 Max real time current L1 4 A kA 6 2 A2 Max real time current L2 4 A kA 6 3 A3 Max real time current L3 4 A kA 7 1 kVA Max real time total kVA 4 kVA MVA 7 2 ...

Страница 45: ...l 1 3 MWh import 5 MWh 2 1 Mvarh rE En Label 2 2 IP Label 2 3 Mvarh import 5 Mvarh 3 1 MVAh AP En Label 3 3 MVAh 5 MVAh 4 1 MWh Ac En Label 4 2 EP Label 4 3 MWh export 5 MWh 5 1 Mvarh rE En Label 5 2 EP Label 5 3 Mvarh export 5 Mvarh Phase Energies 6 1 MWh Ac En Label 6 2 IP L1 Label 6 3 MWh import L1 5 MWh 7 1 Mvarh rE En Label 7 2 IP L1 Label 7 3 Mvarh import L1 5 Mvarh 8 1 MVAh AP En Label 8 2 ...

Страница 46: ...runcated To avoid truncation you can change the energy roll value to lower limit via the User Selectable Options menu see Section 4 7 Negative exported energy readings are displayed without a sign Per phase power and power factor readings are displayed only in 4LN3 4LL3 and 3LN3 3LL3 wiring modes see Section 4 1 if the phase powers display is enabled in the Display Setup menu see Section 4 6 Phase...

Страница 47: ... provides a self check alarm register accessible through communications that indicates possible problems with instrument hardware or setup configuration The hardware problems are indicated by the appropriate bits which are set whenever the instrument fails self test diagnostics or in the event of loss of power The setup problems are indicated by the dedicated bit which is set when either configura...

Страница 48: ...approximately four times per second and shows you a wide variety of status information that you can review by scrolling through display pages The status parameters are designated by the abbreviated labels in the upper and or middle window The upper window flashes indicating that you are in the menu display Viewing and Clearing Alarms Whenever a setpoint signals an alarm it is latched to non volati...

Страница 49: ...sts all the displays available from the Status Information Menu The display windows are labeled in the table as follows 1 upper window 2 middle window 3 lower window Table 6 1 Status Information Page Window Parameter Digits Unit 1 1 PHAS Label 1 2 rOt Label 1 3 Phase rotation sequence POS NEG ERR 4 2 1 rEL Label 2 3 Relay status 1 3 1 Cnt 1 Label 3 3 Counter 1 5 4 1 Cnt 2 Label 4 3 Counter 2 5 5 1...

Страница 50: ...utput Burden 2 5 to 4 mm 2 13 11 AWG wire from CT Overload withstand 3A RMS continuous 50A RMS for 1 second Voltage input terminals UL recognized E129258 Maximum wire section 4 mm 2 10 AWG Optically isolated communication port EIA RS 485 standard Maximum wire section 2 5 mm2 12 AWG Relay output Relay rated at 3A 250 V AC 3A 30 V DC 0 5A 110 V DC Maximum wire section 1 5 mm 2 14 AWG 2 contacts SPST...

Страница 51: ...ity is declared EN55011 1991 EN50082 1 1992 EN61010 1 1993 A2 1995 EN50081 2 1994 EMC Generic Emission Standard Industrial Environment EN50082 2 1995 EMC Generic Immunity Standard Industrial Environment EN55022 1994 Class A EN61000 4 2 1995 Electrostatic Discharge EN61000 4 4 1995 Electrical Fast Transient EN61000 4 8 1993 Power Frequency Magnetic Field ENV50140 1993 Radio Frequency Electromagneti...

Страница 52: ... 0 75 FS Active power 0 36 PT CT 120V input 1 2 PT CT 690V input 0 5 PF 0 5 2 000 000 to 2 000 000 kW 1 kW 1kW to 9 999 kW 0 1 10 MW to 2 000 MW Reactive power 0 36 PT CT 120V input 1 2 PT CT 690V input 0 5 PF 0 9 2 000 000 to 2 000 000 kvar 1 kvar 1kvar to 9 999 kvar 0 1 10 Mvar to 2 000 Mvar Apparent power 0 36 PT CT 120V input 1 2 PT CT 690V input 0 5 PF 0 5 0 to 2 000 000 kVA 1 kVA 1kVA to 9 9...

Страница 53: ... kVA Active energy Import Export according to power accuracy 0 to 99 999 MWh 1 kWh 1 to 99 999 kWh 10 kWh 100 00 to 999 99 MWh 100 kWh 1000 0 to 9999 9 MWh 1MWh 10 0 to 99 99 GWh Reactive energy Import Export according to power accuracy 0 to 99 999 Mvarh 1 kvarh 1 to 99 999 kvarh 10 kvarh 100 00 to 999 99 Mvarh 100 kvarh 1000 0 to 9999 9 Mvarh 1Mvarh 10 000 to 99 999 Gvarh Apparent energy accordin...

Страница 54: ...e the current is 10 FS the energy accuracy is better than 1 5 Rdg Additional Notes 1 Accuracy is expressed as percentage of reading percentage of full scale 1 digit This does not include inaccuracies introduced by the user s potential and current transformers 2 Specifications assume a reference temperature of 20 26 C 3 Specifications for kvar kVA and PF assume voltage and current waveforms with TH...

Страница 55: ...5 inputs 43 Load bar graph 32 measurement 47 menu 17 19 21 22 23 24 27 28 29 30 31 39 41 Modbus ii v 16 21 mounting 1 6 open delta v 11 19 20 overload withstand 43 password 17 30 31 34 42 PComTest v 19 power i v 1 8 20 27 29 33 34 36 37 38 39 40 45 46 power demand v 20 power factor 45 power source i 8 power supply 43 PT v 11 20 43 45 47 PT RATIO 20 pulsing 22 24 27 reactive energy 46 reactive powe...