Appendix: Technical Specifications
66
Appendix: Technical Specifications
8. ions
Input and Output Ratings
690 V:
(standard)
DIRECT INPUT (690V + 15% line-to-line voltage and
400V +15% line-to-neutral) Burden: <0.5 VA
INPUT USING PT Burden: <0.15 VA
3 galvanically
isolated voltage
inputs
120 V:
(optional)
INPUT USING PT (120V +20% line-to-line voltage)
Burden: <0.1 VA
5 A:
(standard)
Maximum 6A RMS Burden: <0.1 VA
Overload withstand: 10A RMS continuous, 250A RMS for
1 second
3 galvanically
isolated current
inputs
1 A:
(optional)
Maximum 1.2 A RMS Burden: <0.02 VA
Overload withstand: 2A RMS continuous, 50A RMS for 1
second
Voltage and current input
terminals
UL recognized Screws: Brass, M4
Maximum wire section: 2.5 mm
2
(12 AWG)
Optically isolated
communication port
EIA RS-485 or RS-232 standard (factory set)
RS-232: point-to-point, up to 15 meters
RS-485: multidrop, up to 32 loads, up to 1200 meters
(4000 ft.)
Maximum wire section: 1.5 mm
2
(14 AWG)
Relay outputs
5 relays rated at 5A, 250 V AC / 5A, 30 V DC / 0.5A, 110
V DC 2 contacts (SPST Form A)
1 relay rated at 5A, 250 V AC / 5A, 30 V DC / 0.5A, 110
V DC
3 contacts (SPDT Form C)
2 relays rated at 3A, 250 V AC / 3A, 30 V DC / 0.5A, 110
V DC 2 contacts (SPST Form A)
Maximum wire section: 1.5 mm
2
(16 AWG)
Analog output (optional)
4-20 mA
0-20 mA
Accuracy 0.5%, Non-linearity 0.2%
Load up to 510 Ohm
24V DC external power supply required
Status input
Dry contact for external synchronization or monitoring
Maximum impedance on: 300 ohm
Display
3 windows, high-brightness seven-segment digit LEDs
Color relay status LED
Galvanically isolated power
supply (factory set)
120&230V AC / 120&220 V DC
12 V DC
24 V DC
48 V DC
85-265V AC 50/60 Hz and 88-290V DC 10 W
9.6 - 19 V DC
19 - 37 V DC
37 - 72 V DC