Chapter 4 Setup Menus
26
Vmax
(690 V input option) = 828.0 V
Vmax
(120 V input option) = 144.0 V
Pmax
= (Imax
×
Vmax
×
3) [kW x 0.001] @ wiring modes 4Ln3, 3Ln3
Pmax
= (Imax
×
Vmax
×
2) [kW x 0.001] @ wiring modes 4LL3, 3OP2, 3dir2, 3OP3, 3LL3
NOTE: Pmax
is rounded to nearest whole kW units.
If
Pmax
is more than
9999.000 kW, it is truncated to 9999.000 kW
Wiring via PTs (PT Ratio > 1):
Vmax
(690 V input option) = 144
×
PT Ratio [V]
Vmax
(120 V input option) = 144
×
PT Ratio [V]
Pmax
= (Imax
×
Vmax
×
3)/1000 [MW x 0.001] @ wiring modes 4Ln3, 3Ln3
Pmax
= (Imax
×
Vmax
×
2)/1000 [MW x 0.001] @ wiring modes 4LL3, 3OP2, 3dir2, 3OP3, 3LL3
NOTE: Pmax
is rounded to nearest whole kW units.
The actual frequency range is 45.00 - 65.00 Hz
4.5 Pulsing Output Setup Menu
This menu allows you to program any of the eight relays provided by your
C192PF8-RPR
instrument to output energy pulses. Relays #7 and #8 are
especially recommended for use as pulsing relays because of their high
endurance. Available pulsing parameters are listed in Table 4-5.
To select a pulse relay:
Use the up/down arrow keys to scroll to the desired relay. The
pulsing parameter assigned to the relay is displayed in the
middle window, and the amount of unit-hours per pulse is
displayed in the lower window.
To change the pulse relay setup:
Press to activate the middle window.
Use the up/down arrow keys to scroll to the desired output
parameter. Selecting
nonE
disables pulsing through this relay.
Press to activate the lower window.
Use the up/down arrow keys to set the amount of unit-hours
per pulse. The available range is 1-9999.
Press to store the new setup, or press to quit the
setup without changes.
To quit the pulsing setup menu:
From the upper window, press or .
Table 4-5 Pulsing Output Parameters
Code
Parameter
Units
nonE
Output disabled
Ac.Ei
Active energy import
kWh import (positive)
Ac.EE
Active energy export
kWh export (negative)
rE.Ei
Reactive energy import
kvarh import (inductive)
SELECT
SELECT
ENTER
ESC
ESC
ENTER
rEL.1
1
Ac.Ei
SELEC
CHG
PulS
ENTER
ENTER