Chapter 4 Setup Menus
35
4.9 User Selectable Options Menu
This menu allows you to change options which relate to the instrument features
and functionality. Table 4-10 lists all available options with their code names and
applicable ranges.
To select an option:
Press to activate the middle window, and then use the
up/down arrow keys to scroll to the desired option.
To change the selected option:
Press to activate the lower window.
Use the up/down arrow keys to set the desired value.
Press to store your new setting or to leave the
previous setting unchanged.
To quit the display setup menu:
From the middle window, press or .
Table 4-10 User Selectable Options (
∗
default setting)
Code
Parameter
Options
Description
P.cAL
Power calculation
mode
rEAc
*
nAct
Using reactive power
Using non-active power
roLL
Energy roll value
10.E4
10.E5
10.E6
10.E7
10.E8
*
10,000 kWh
100,000 kWh
1,000,000 kWh
10,000,000 kWh
100,000,000 kWh
Ph.En
Phase energy
measurements
diS
*
, En
Enables/disables measurements of
energies per phase
Power calculation mode (
P.cAL
):
Mode 1: Reactive power calculation (rEAc)
Active power P and reactive power Q are measured directly and apparent power
S =
√
P
2
+ Q
2
Mode 2: Non-active power calculation (nAct)
Active power is measured directly, apparent power S = V
×
I (where V, I - rms
voltage and currents) and non-active power N =
√
S
2
-
P
2
Mode 1 is recommended for electrical networks with low harmonic distortion (voltage
THD
<
5%, current THD
<
10%); Mode 2 is recommended for all other cases.
SELECT
SELECT
OPtS
rEAc
P.cAL
ENTER
ESC
ESC
ENTER
SELECT
CHG
OPtS
ENTER
ENTER