Option 50 - Entering Diagnostic Mode
Press the bottom button to scroll between “E - d”. Setting the option
to “E” will enable the option and will enter diagnostic mode. Setting
the option to “d” will disable the option and upon depressing the top
button, the clock will return to the time.
Option 51 - Sends Diagnostic to Slave Clock
Pressing the bottom button will scroll from “1-5 and 9”.
01 - Protocol Verification
02 - Comprehensive Test
03 - Manufacturer’s Default
04 - Combination of 02 & 03 (button must be pressed on SAM)
05 - Combination of 02 & 03 (no need to press button on SAM)
09 - Overrides the Previous Diagnostic and Goes Back to the Time
Option 52 - Set Duration (in minutes) that the Results of the Diagnostic
will be Viewable on the Clock
Pressing the bottom button will scroll from “00-60”. Pressing the top
button will go back to the displayed time.
Sync-Wire Communication – Protocol Definitions
1 - 58th minute (1)
The hourly correction for 55 seconds every hour from XX:58:05 to XX:59:00. The daily correction (5 a.m. & 5 p.m.) is
ten correction cycles sent to the relay (each for 95 seconds) beginning at 5:05:00, 5:07:00, 5:09:00, 5:11:00, 5:13:00,
5:15:00, 5:17:00, 5:19:00, 5:21:00, and 5:23:00.
2 - 58th minute (2)
The hourly correction for 60 seconds every hour from XX:58:00 to XX:59:00. The daily correction (5 a.m. & 5 p.m.) is
twelve correction cycles sent to the relay (each for 65 seconds on and 25 seconds off) beginning at 5:05:00 to 5:22:35.
3 - 58th minute (3)
The hourly correction for 60 seconds every hour from XX:58:00 to XX:59:00. The daily correction (5 a.m. & 5 p.m.) is twelve
correction cycles sent to the relay (each for one minute on and two minutes off) beginning at 5:06:00.
4 - 58th minute (4)
The hourly correction for 55 seconds every hour from xx:58:05 to XX:59:00. The daily correction (5 a.m. & 5 p.m.) is 12
correction cycles for 55 seconds. The timings will be 05:03:05, 05:07:05, 05:11:05, 05:15:05, 05:19:05, 05:23:05, 05:27:05,
05:31:05, 05:35:05, 05:39:05, 05:43:05 and 05:47:05.
5 - 59th minute
The hourly correction for 8 seconds every hour from XX:57:54 to XX:58:02. The daily correction (5 a.m. & 5 p.m.) is a 14
second pulse from 5:57:54 to 5:58:08.
6 - National Time & Rauland (1)
The hourly correction is for 25 seconds every hour from XX:00:00 to XX:00:25. The daily correction (6 a.m. & 6
p.m.) is 25 seconds on, 35 seconds off every minute for 24 minutes.
7 - National Time & Rauland (2)
The hourly correction is for 25 seconds every hour from XX:00:00 to XX:00:25. The daily correction is a 24
minute pulse from 6:00:25 to 6:24:25 AM and PM.
8 - Once a Day Pulse
The Once a Day Pulse allows the user to manually configure when the relay will close and for how long it needs to close.
9 - Rauland Digital
The Rauland Digital will reset the clock to 12:00:00AM and advance the clock one minute for every 0.5 seconds that the
Dig line is shorted to ground.