11
GB
4.3.4 - OTHER CONTROL CONNECTIONS
Caution
:
To avoid problems related to electromagnetic disturbances, do not route these cables near power cables.
B
D
C
A
A
A1
A2
CC1
E
F
Control unit
With built-in ambient temperature sensor.
To be installed in zone 1.
Load shedding
(if installed)
Outside air
temperature
Outdoor unit
Installation
water outlet
temperature
Installation
water return
temperature
Control by pilot wire for 2
nd
zone (if any) with electric convectors.
Application: 1 FLOOR ZONE or 1 TERMINAL UNIT ZONE or 1
RADIATORS ZONE
ECO signal to remote controls.
For the terminal unit zone.
Application: 1 TERMINAL UNIT ZONE or 2 MIXED ZONES
BUS connection to 2-zone module ATK-WM2ZF or ATK-WM2ZM.
Applications: 2 FLOOR ZONES or 2 MIXED ZONES
Possible connections to be
made depending on the
applications
A) BUS
- 2-conductor shielded cable, minimum size 1 mm_ with shielding grounded on indoor unit side (*).
-
Total
length of the BUS connection: 40 meters (indoor unit / control box conn indoor unit / 2-zone module
connection, if any).
- To be connected to the (+) and (-) terminals if terminal strip XB.
(*) Refer to the ground shielding principle in paragraph 4.3.3.
B) Outside temperature sensor
- 2-conductor cable, min. size 0.5 mm
2
.
- Maximum length 25 meters.
- To be connected to the heating board
A1.
-
Note
:
This sensor must be located outside in a location that is representative of the temperature to be measured (on a wall facing
North / North-west) and located away from parasitic heat sources (chimney, thermal bridge, etc..) and sheltered from
inclement weather (under a roof overhand, for example).
C) Outdoor unit control connection
- 2-conductor shielded cable with shielding grounded on both the outdoor unit and indoor unit side.
- Minimum cable size: 0.75 mm
2
.
- Maximum length 70 meters.
- Connection as per paragraph 4.3.3.
D) Module additional heating load shedding signal (if installed)
- Two possibilities:
1
) By a "remote info" signal coming from the electrical utility meter: 1 twisted pair (6/10) cable with shielding (shielding
grounded on module side).
2
) By a good quality, potential-free external contact.
- Contact closed = load shedding of the additional electric heating.
- 2-conductor cable, min. size 0.5mm
2
.
- Maximum length 25 meters.
- To be connected to the heating board
A1.
Indoor unit
Содержание SPW-W366HH58
Страница 19: ...19 GB ...
Страница 37: ...19 FR ...
Страница 38: ...SANYO Airconditioners Europe S r l Via Bisceglie No 76 20152 Milano Italy SAN 10 11 525 GB FR 00 ...