SPW-W units are designed to be supplied with either single-phase 230V or three-phase 400V.
In a three-phase configuration, the jumper between terminals L1, L2, and L3 on terminal strip XA.
Note
:
The unit is designed to be connected to a power supply having a TT neutral regime (neutral to ground) or TN.S regime
(to neutral) as per NF C 15-100.
POWER SUPPLY CABLE
-
Section
: see amperage table.
- The sections are given as an indication only. They have to be verified and adapted, if necessary, according to the
installation conditions and the standards in force.
CURRENTS AND CROSS-SECTIONS
(*) With 6 kW electric heating module only.
SELECTION OF ELECTRIC HEATING MODULE POWERS
- To obtain the maximum electric heating module power ratings, the jumper must be installed between 22 and 23 on
terminal strip XA (jumper included).
4.3.3 - CONNECTION WITH THE OUTDOOR UNIT
- The control connection between the indoor unit and the outdoor unit is made by a shielded 0.75 mm
2
cable
(AWG #18), with the shielding grounded at both the indoor unit and outdoor unit side.
- Maximum length 70 meters.
- The cable's shielding must be grounded at both ends by means of a metal clamp (not supplied) screwed onto the
terminal strip support plate.
- To avoid problems related to electromagnetic disturbances, do not route this cable near power cables.
SPW-W366 / SPW-W486 / SPW-W606
N
L1
L2
L3
1
2
U1
U2
Three-phase power supply
400V / 3+N+T / 50Hz
PE N Ph1 Ph2 Ph3
Terminal
strip XA
SPW-W366 / SPW-W486 / SPW-W606
N
L1
L2
L3
Single-phase power supply
230V / 1+T / 50Hz
PE N
Ph
Jumper
Terminal
strip XA
Model
SPW-W366
230/1/50
SPW-W366
400/3N/50
SPW-W486
230/1/50
SPW-W486
400/3N/50
SPW-W606
230/1/50 (*)
SPW-W606
400/3N/50
Rated input amperage
A
27
9.5
27
9.5
27
14
Protection rating
A
32
12
32
12
32
16
Power supply cable size
3G6mm
2
5G2.5mm
2
3G6mm
2
5G2.5mm
2
3G6mm
2
5G2.5mm
2
Model
SPW-W366
single
SPW-W366
three
SPW-W486
single
SPW-W486
three
SPW-W606
single
SPW-W606
three
Jumper between 22 and 23 of
terminal strip XA
no
yes
no
yes
no
yes
no
yes
no
no
yes
Electric heating
kW
module powers
4
(2+2)
6
(4+2)
4
(2+2)
6
(4+2)
4
(2+2)
6
(4+2)
4
(2+2)
6
(4+2)
6 only
(3+3)
6
(3+3)
9
(6+3)
Outdoor Unit
Indoor Unit
Interconnect cable
between the indoor
unit and the outdoor
unit
Shielding
Screws (not supplied)
Metal clamp (not supplied) screwed to
the terminal strip's support plate
Grounding of the
cable shielding:
Содержание SPW-W366HH58
Страница 19: ...19 GB ...
Страница 37: ...19 FR ...
Страница 38: ...SANYO Airconditioners Europe S r l Via Bisceglie No 76 20152 Milano Italy SAN 10 11 525 GB FR 00 ...