26
8. INSTALLATION INSTRUCTIONS
8-1. Installation Site Selection
AVOID:
●
direct sunlight.
●
nearby heat sources that may affect performance of
the unit.
●
areas where leakage of flammable gas may be
expected.
●
places where large amounts of oil mist exist.
DO:
●
select an appropriate position from which every cor-
ner of the room can be uniformly cooled. (High on a
wall is best.)
●
select a location that will hold the weight of the unit.
●
select a location where tubing and drain hose have
the shortest run to the outside.
●
allow room for operation and maintenance as well as
unrestricted air flow around the unit. (Fig. 1)
●
install the unit within the maximum elevation differ-
ence (H1, H2, H3, H4) above or below the outdoor
unit and within a total tubing length (L1+L2+L3+L4)
from the outdoor unit as detailed in Table 1 and Fig. 2.
Table 1
WARNING
To prevent abnormal heat
generation and the possibility
of fire, do not place obsta-
cles, enclosures and grilles in
front of or surrounding the air
conditioner in a way that may
block air flow.
Indoor Unit
Front view
5 cm (15 cm) min.
5 cm (15 cm) min.
5 cm (15 cm) min.
Fig. 1
INDOOR
UNIT (1)
INDOOR
UNIT (4)
INDOOR
UNIT (3)
INDOOR
UNIT (2)
Tubing length (L1)
L2
L3
L4
Elevation
difference (H1)
H2
H3
H4
OUTDOOR
UNIT
Fig. 2
Indoor unit
Floor level
Wall
Minimum height
from floor level
1.5 m
Fig. 3
For stable operation of
the air conditioner, do not
install wall-mounted type
indoor units under 1.5 m
from floor level.
CAUTION
Measurements in parentheses are for SAP-KMV181G.
Number of
Limit of Tubing
Limit of Elevation
Length (L1, L2, L3, L4)
Difference (H1, H2, H3, H4)
Indoor Units
(m)
(m)
1
20
10
2 to 4
40
*
10
*
The total tubing length must be less than 40 meters. Also, additional charging
is not necessary when tubing length for each unit is less than 20 meters and
total tubing length is less than 40 meters.
No additional compressor oil is necessary.