27
5-3. Cooling Capacity
Indoor Unit
SAP – K161GJA
Outdoor Unit
SAP – C161GA
240V Single Phase 50Hz
RATING CAPACITY
4.70 kW
AIR FLOW RATE
760 m
3
/h
EVAPORATOR
CONDENSER
ENT. TEMP. °C
OUTDOOR AMBIENT TEMP. °C
W.B.
D.B.
30
35
40
43
TC
4.32
4.12
3.87
3.56
CM
1.25
1.34
1.45
1.60
21
SHC
2.92
2.81
2.68
2.53
15
23
SHC
3.27
3.16
3.04
2.89
25
SHC
3.63
3.52
3.39
3.24
27
SHC
3.98
3.87
3.75
3.56
29
SHC
4.32
4.12
3.87
3.56
31
SHC
4.32
4.12
3.87
3.56
TC
4.64
4.42
4.15
3.82
CM
1.28
1.38
1.49
1.64
21
SHC
2.55
2.45
2.32
2.17
17
23
SHC
2.91
2.80
2.67
2.52
25
SHC
3.26
3.16
3.03
2.88
27
SHC
3.62
3.51
3.38
3.23
29
SHC
3.97
3.87
3.74
3.59
31
SHC
4.33
4.22
4.09
3.82
TC
4.94
# 4.70
4.42
4.07
CM
1.32
1.42
1.54
1.69
21
SHC
2.17
2.06
1.94
1.79
19
23
SHC
2.52
2.42
2.29
2.14
25
SHC
2.88
2.77
2.65
2.50
27
SHC
3.23
3.13
3.00
2.85
29
SHC
3.59
3.48
3.36
3.21
31
SHC
3.94
3.84
3.71
3.56
TC
5.23
4.98
4.68
4.31
CM
1.36
1.46
1.58
1.73
23
SHC
2.13
2.03
1.91
1.76
21
25
SHC
2.49
2.38
2.26
2.11
27
SHC
2.84
2.74
2.62
2.47
29
SHC
3.20
3.09
2.97
2.82
31
SHC
3.55
3.45
3.33
3.18
TC
5.54
5.23
4.90
4.55
CM
1.39
1.50
1.62
1.78
23
25
SHC
2.07
1.95
1.83
1.70
27
SHC
2.43
2.31
2.18
2.06
29
SHC
2.78
2.66
2.54
2.41
31
SHC
3.14
3.02
2.89
2.77
TC :
Total Cooling Capacity (kW)
SHC : Sensible Heat Capacity (kW)
CM :
Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35°C D.B.
Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.