36
7. INSTALLATION INSTRUCTIONS
7-1. Installation Site Selection
To prevent abnormal heat
generation and the possibility
of fire, don’t place obstacles,
enclosures and grills in front
of or surrounding the air
conditioner in a way that may
block air flow.
AVOID:
●
direct sunlight.
●
nearby heat sources that may affect performance of
the unit.
●
areas where leakage of flammable gas may be
expected.
●
places where large amounts of oil mist exist.
DO:
●
select an appropriate position from which every
corner of the room can be uniformly air-conditioned.
(High on a wall is best)
●
select a location that will hold the weight of the unit.
●
select a location where tubing and drain pipe have the
shortest run to the outside.
●
allow room for operation and maintenance as well as
unrestricted air flow around the unit. (Fig. 1)
●
install the unit within the maximum elevation
difference (H) above or below the outdoor unit and
within a total tubing length (L) from the outdoor unit as
detailed Table 1 and Fig. 2a.
Indoor Unit
,
5 cm
min.
5 cm
min.
5 cm min.
INDOOR UNIT
Front View
INDOOR
UNIT
Tubing length (L)
OUTDOOR
UNIT
Elevation
difference (H)
Fig. 2
Fig. 2a
Fig.1
WARNING
Table 1
* If total tubing length becomes 7.5 to 15 (max.) or 7.5 to 20 (max.), charge additional refrigerant (R22) by 15 g / m or 25 g / m.
No additional charge of compressor oil is necessary.
Minimum height
from floor level
1.5m
Indoor Unit
Wall
Floor level
For stable operation of
the air conditioner, do
not install wall-mounted
type indoor units under
1.5m from floor level.
CAUTION
Fig. 2b
Model
Max. Allowable Tubing
Length at Shipment (m)
Limit of Tubing
Length (L)
(m)
Limit of Elevation
Difference (H)
(m)
Required Amount of
Additional Refrigerant
(g / m)*
C71, C91
7.5
15
7
15
C121
7.5
20
7
25
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html