background image

TECHNICAL & SERVICE MANUAL

SAP – K71GJA

+

SAP – C71GA

SAP – K91GJA

+

SAP – C91GA

+

SAP – C91JA

SAP – K121GJA

+

SAP – C121GA

+

SAP – C121JA

FILE NO.

REFERENCE NO. 

SM

700455

Indoor Unit

Outdoor Unit

SPLIT SYSTEM AIR CONDITIONER

80%

SAP – K71GJA

SAP – K91GJA

SAP – K121GJA

SAP – C71GA

SAP – C91GA
SAP – C91JA

SAP – C121GA
SAP – C121JA

Indoor Model No.

Product Code No.

Destination

SAP – K71GJA– S

1  852  070  36

General (50/60Hz)

SAP – K91GJA– S

1  852  070  37

SAP – K121GJA– S

1  852  069  63

Outdoor Model No.

Product Code No.

Destination

SAP – C71GA– S

1  852  070  50

General (50Hz)

SAP – C91GA– S

1  852  070  52

General (50Hz)

SAP – C91JA– S

1  852  070  53

General (60Hz)

SAP – C121GA– S

1  852  069  64

General (50Hz)

SAP – C121JA– S

1  852  070  54

General (60Hz)

General (50/60Hz)

General (50/60Hz)

Большая библиотека технической документации

http://splitoff.ru/tehn-doc.html   

каталоги, инструкции, сервисные мануалы, схемы.

Содержание SAP-C121GA

Страница 1: ...uct Code No Destination SAP K71GJA S 1 852 070 36 General 50 60Hz SAP K91GJA S 1 852 070 37 SAP K121GJA S 1 852 069 63 Outdoor Model No Product Code No Destination SAP C71GA S 1 852 070 50 General 50Hz SAP C91GA S 1 852 070 52 General 50Hz SAP C91JA S 1 852 070 53 General 60Hz SAP C121GA S 1 852 069 64 General 50Hz SAP C121JA S 1 852 070 54 General 60Hz General 50 60Hz General 50 60Hz Большая библ...

Страница 2: ...reful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the units weight It may be necessary to construct a strong wood or metal frame to prov...

Страница 3: ...Length and Diameter 39 8 FUNCTION 8 1 Room Temperature Control 40 8 2 Dry Operation 41 8 3 Freeze Prevention 41 8 4 Outdoor Fan Speed Control 42 9 TROUBLESHOOTING 9 1 Check before and after troubleshooting 43 9 2 Air conditioner does not operate 44 9 3 Some part of air conditioner does not operate 48 9 4 Air conditioner operates but abnormalities are observed 50 9 5 If a sensor is defective 51 10 ...

Страница 4: ...TING RANGE Temperature Indoor Air Intake Temp Outdoor Air Intake Temp Cooling Maximum 32 C D B 23 C W B 43 C D B Minimum 19 C D B 14 C W B 19 C D B Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 5: ...Indoor Outdoor 3 and Auto 1 Hi Airflow direction Indoor Horizontal Manual Vertical Auto Air filter Washable Anti Mold Compressor Rotary Hermetic Refrigerant Amount charged at shipment g R22 670 Refrigerant control Capillary tube Operation sound Indoor Hi Me Lo dB A 36 33 31 Outdoor Hi dB A 45 Refrigerant tubing connections Flare type Max allowable tubing length at shipment m 7 5 Refrigerant tube N...

Страница 6: ...Auto 1 Hi Airflow direction Indoor Horizontal Manual Vertical Auto Air filter Washable Anti Mold Compressor Rotary Hermetic Refrigerant Amount charged at shipment g R22 850 Refrigerant control Capillary tube Operation sound Indoor Hi Me Lo dB A 39 37 33 Outdoor Hi dB A 44 Refrigerant tubing connections Flare type Max allowable tubing length at shipment m 7 5 Refrigerant tube Narrow tube mm in 6 35...

Страница 7: ...orizontal Manual Vertical Auto Air filter Washable Anti Mold Compressor Rotary Hermetic Refrigerant Amount charged at shipment g R22 780 Refrigerant control Capillary tube Operation sound Indoor Hi Me Lo dB A 39 37 33 Outdoor Hi dB A 44 Refrigerant tubing connections Flare type Max allowable tubing length at shipment m 7 5 Refrigerant tube Narrow tube mm in 6 35 1 4 diameter Wide tube mm in 9 52 3...

Страница 8: ...d Auto Auto Hi Lo Airflow direction Indoor Horizontal Manual Vertical Auto Air filter Washable Anti Mold Compressor Rotary Hermetic Refrigerant Amount charged at shipment g R22 875 Refrigerant control Capillary tube Operation sound Indoor Hi Me Lo dB A 40 37 34 Outdoor Hi dB A 46 Refrigerant tubing connections Flare type Max allowable tubing length at shipment m 7 5 Refrigerant tube Narrow tube mm...

Страница 9: ...oor Horizontal Manual Vertical Auto Air filter Washable Anti Mold Compressor Rotary Hermetic Refrigerant Amount charged at shipment g R22 810 Refrigerant control Capillary tube Operation sound Indoor Hi Me Lo dB A 40 37 34 Outdoor Hi dB A 46 Refrigerant tubing connections Flare type Max allowable tubing length at shipment m 7 5 Refrigerant tube Narrow tube mm in 6 35 1 4 diameter Wide tube mm in 1...

Страница 10: ...2 1 160 Nominal output W 20 Coil resistance Ambient temp 20 C Ω WHT BRN 201 WHT VLT 261 Safety Type Thermal fuse devices Operating temp Open C 130 Close Run capacitor µF 1 5 VAC 440 Type Stepping motor Model MP24GA3 Rating DC 12 V Coil resistance Ambient temp 25 C Ω A pair of each terminal 380 7 Coil Aluminum plate fin Copper tube Rows 2 Fin pitch mm 1 4 Face area m2 0 110 Heat Exch Coil Flap Moto...

Страница 11: ... W 20 Coil resistance Ambient temp 20 C Ω WHT BRN 201 WHT VLT 261 Safety Type Thermal fuse devices Operating temp Open C 130 Close Run capacitor µF 1 5 VAC 440 Type Stepping motor Model MP24GA3 Rating DC 12 V Coil resistance Ambient temp 25 C Ω A pair of each terminal 380 7 Coil Aluminum plate fin Copper tube Rows 2 Fin pitch mm 1 4 Face area m2 0 110 Heat Exch Coil Flap Motor Fan Fan Motor Contro...

Страница 12: ... W 20 Coil resistance Ambient temp 20 C Ω WHT BRN 201 WHT VLT 261 Safety Type Thermal fuse devices Operating temp Open C 130 Close Run capacitor µF 1 5 VAC 440 Type Stepping motor Model MP24GA3 Rating DC 12 V Coil resistance Ambient temp 25 C Ω A pair of each terminal 380 7 Coil Aluminum plate fin Copper tube Rows 2 Fin pitch mm 1 4 Face area m2 0 110 Heat Exch Coil Flap Motor Fan Fan Motor Contro...

Страница 13: ...Run capacitor µF 20 0 VAC 400 Type Propeller Number Dia mm 1 ø 370 Fan motor model Number UE6 21AH5PB S 1 No of poles rpm 230 V High 6 760 Nominal output W 20 Coil resistance Ambient temp 20 C Ω WHT BRN 338 3 WHT PNK 389 7 Safety Type Thermal fuse devices Operating temp Open C 145 2 Close Run capacitor µF 1 5 VAC 440 Coil Aluminum plate fin Copper tube Rows 1 Fin pitch mm 1 3 Face area m2 0 259 Ex...

Страница 14: ...or µF 22 5 VAC 400 Type Propeller Number Dia mm 1 ø 370 Fan motor model Number UE6 21AH5PB S 1 No of poles rpm 230 V High 6 760 Nominal output W 20 Coil resistance Ambient temp 20 C Ω WHT BRN 338 3 WHT PNK 389 7 Safety Type Thermal fuse devices Operating temp Open C 145 2 Close Run capacitor µF 1 5 VAC 440 Coil Aluminum plate fin Copper tube Rows 1 Fin pitch mm 1 3 Face area m2 0 333 External Fini...

Страница 15: ...tor µF 25 0 VAC 400 Type Propeller Number Dia mm 1 ø 370 Fan motor model Number UE6 21AH5PB S 1 No of poles rpm 220 V High 6 720 Nominal output W 20 Coil resistance Ambient temp 20 C Ω WHT BRN 338 3 WHT PNK 389 7 Safety Type Thermal fuse devices Operating temp Open C 145 2 Close Run capacitor µF 1 5 VAC 440 Coil Aluminum plate fin Copper tube Rows 1 Fin pitch mm 1 3 Face area m2 0 333 External Fin...

Страница 16: ...Propeller Number Dia mm 1 ø 370 Fan motor model Number UE6S 21AC5P S 1 No of poles rpm 230 V High 6 750 Nominal output W 20 Coil resistance Ambient temp 20 C Ω BRN WHT 341 2 WHT YEL 212 7 YEL PNK 190 0 Safety Type Thermal fuse devices Operating temp Open C 145 2 Close Run capacitor µF 1 5 VAC 440 Coil Aluminum plate fin Copper tube Rows 2 Fin pitch mm 1 2 Face area m2 0 315 External Finish Acrylic...

Страница 17: ...22 5 VAC 400 Type Propeller Number Dia mm 1 ø 370 Fan motor model Number UE6S 21AC5P S 1 No of poles rpm 220 V High 6 780 Nominal output W 20 Coil resistance Ambient temp 20 C Ω BRN WHT 341 2 WHT YEL 212 7 YEL PNK 190 0 Safety Type Thermal fuse devices Operating temp Open C 145 2 Close Run capacitor µF 1 5 VAC 440 Coil Aluminum plate fin Copper tube Rows 2 Fin pitch mm 1 2 Face area m2 0 315 Exter...

Страница 18: ...220V 25A Outdoor Unit SAP C71GA SAP C91GA SAP C91JA SAP C121GA SAP C121JA Thermistor Room sensor DTN TKS128B Resistance kΩ 25 C 5 0 3 Thermistor Coil sensor DTN TKS131B Resistance kΩ 0 C 15 0 2 Transformer TR ATR J105 Rating Primary AC 230V 50 60Hz Secondary 19V 0 526A Capacity 10VA Coil resistance Ω at 21 C Primary WHT WHT 205 10 Secondary BRN BRN 2 0 10 Thermal cut off temp 150 C Indoor Unit SAP...

Страница 19: ...K121GJA 790 250 174 3 Narrow tube ø6 35 1 4 Drain hose ø18 58 5 132 41 0 41 0 Center of tubing hole 2 places Remote control unit 172 61 23 Wide tube ø9 52 3 8 Wide tube ø12 7 1 2 K71 K91 K121 Unit mm Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 20: ...AP C91JA 680 58 530 15 225 Narrow tube service valve ø6 35 1 4 Wide tube service valve ø9 52 3 8 150 103 55 538 C91 only 2 ø12 holes 71 286 260 Air intake Air discharge Unit mm Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 21: ...P C121JA 680 71 530 15 225 Narrow tube service valve ø6 35 1 4 Wide tube service valve ø12 7 1 2 150 103 55 538 2 ø12 holes 71 286 260 Air intake Air discharge Unit mm Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 22: ...as been insulated never try to bend it into a narrow curve because it can cause the tube to break or crack IMPORTANT CAUTION Wide tube Thickness Min 8 mm Insulation Narrow tube Thickness Min 8 mm Compressor Accumulator Wide tube service valve Wide tube O D ø9 52 mm 3 8 O D ø12 7 mm 1 2 Narrow tube service valve Narrow tube O D ø6 35 mm 1 4 Condenser Capillary tube Indoor Unit Outdoor Unit Evaporat...

Страница 23: ...0 45 50 Outdoor inlet air D B temp C Operating current A 10 Low pressure at wide tube service valve kg cm 2 G 32 27 21 32 27 21 Points of Rating condition Black dots in above charts indicate the following rating conditions Cooling Indoor air temperature 27 C D B 19 C W B Outdoor air temperature 35 C D B 24 C W B NOTE Indoor Unit SAP K71GJA Outdoor Unit SAP C71GA Все каталоги и инструкции здесь htt...

Страница 24: ...lowing rating conditions Cooling Indoor air temperature 27 C D B 19 C W B Outdoor air temperature 35 C D B 24 C W B NOTE Indoor Unit SAP K91GJA Outdoor Unit SAP C91GA Indoor Unit SAP K91GJA Outdoor Unit SAP C91JA 13 12 11 10 9 8 7 6 25 30 35 40 45 50 Outdoor inlet air D B temp C 5 4 3 Indoor inlet air D B temp C Cooling Characteristics Indoor inlet air D B temp C 10 9 8 7 6 5 4 3 2 25 30 35 40 45 ...

Страница 25: ...wing rating conditions Cooling Indoor air temperature 27 C D B 19 C W B Outdoor air temperature 35 C D B 24 C W B NOTE Indoor Unit SAP K121GJA Outdoor Unit SAP C121GA Indoor Unit SAP K121GJA Outdoor Unit SAP C121JA Indoor inlet air D B temp C Outdoor fan speed High Low 13 12 11 10 9 8 7 6 25 30 35 40 45 50 Low pressure at wide tube serveice valve kg cm 2 G 5 4 3 Cooling Characteristics 12 11 10 9 ...

Страница 26: ...ocity m s Vertical distance m Room air temp 27 C Fan speed High 0 1 2 3 4 0 1 2 3 4 5 6 7 8 9 Flap angle 0 Axis air velocity 0 Flap angle 30 Axis air velocity 30 0 1 2 3 4 0 1 2 3 4 5 6 7 8 9 Flap angle 0 Axis air velocity 0 Flap angle 30 Axis air velocity 30 23 Indoor Unit SAP K71GJA Indoor Unit SAP K91GJA Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 27: ... High Heating Horizontal distance m Axis air verocity m s Vertical distance m Room air temp 27 C Fan speed High 0 1 2 3 4 0 1 2 3 4 5 6 7 8 9 Flap angle 0 Axis air velocity 0 Flap angle 30 Axis air velocity 30 Indoor Unit SAP K121GJA Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 28: ...2 36 2 26 2 15 2 05 1 93 1 77 CM 0 47 0 51 0 55 0 59 0 65 0 70 21 SHC 1 04 0 99 0 95 0 91 0 85 0 79 19 23 SHC 1 22 1 18 1 13 1 09 1 04 0 98 25 SHC 1 41 1 36 1 32 1 28 1 23 1 16 27 SHC 1 59 1 55 1 51 1 46 1 41 1 35 29 SHC 1 78 1 74 1 69 1 65 1 60 1 53 31 SHC 1 97 1 92 1 88 1 83 1 78 1 72 TC 2 50 2 39 2 28 2 17 2 04 1 88 CM 0 49 0 53 0 56 0 61 0 66 0 72 23 SHC 1 02 0 98 0 93 0 89 0 84 0 78 21 25 SHC...

Страница 29: ... 68 2 55 2 40 2 21 CM 0 64 0 69 0 74 0 79 0 87 0 94 21 SHC 1 29 1 23 1 18 1 12 1 05 0 97 19 23 SHC 1 50 1 44 1 39 1 33 1 26 1 18 25 SHC 1 71 1 65 1 60 1 54 1 47 1 39 27 SHC 1 92 1 86 1 81 1 75 1 68 1 60 29 SHC 2 13 2 07 2 01 1 96 1 89 1 81 31 SHC 2 34 2 28 2 22 2 17 2 10 2 02 TC 3 11 2 97 2 84 2 70 2 54 2 34 CM 0 65 0 71 0 76 0 81 0 89 0 97 23 SHC 1 27 1 21 1 16 1 10 1 04 0 96 21 25 SHC 1 48 1 42 ...

Страница 30: ... 68 2 55 2 40 2 21 CM 0 64 0 69 0 74 0 79 0 87 0 94 21 SHC 1 29 1 23 1 18 1 12 1 05 0 97 19 23 SHC 1 50 1 44 1 39 1 33 1 26 1 18 25 SHC 1 71 1 65 1 60 1 54 1 47 1 39 27 SHC 1 92 1 86 1 81 1 75 1 68 1 60 29 SHC 2 13 2 07 2 01 1 96 1 89 1 81 31 SHC 2 34 2 28 2 22 2 17 2 10 2 02 TC 3 11 2 97 2 84 2 70 2 54 2 34 CM 0 65 0 71 0 76 0 81 0 89 0 97 23 SHC 1 27 1 21 1 16 1 10 1 04 0 96 21 25 SHC 1 48 1 42 ...

Страница 31: ...2 82 2 70 TC 3 57 3 40 3 20 2 94 CM 1 11 1 19 1 24 1 43 21 SHC 1 58 1 50 1 41 1 29 19 23 SHC 1 81 1 73 1 64 1 53 25 SHC 2 05 1 97 1 87 1 76 27 SHC 2 28 2 20 2 10 1 99 29 SHC 2 51 2 43 2 33 2 22 31 SHC 2 74 2 66 2 57 2 45 TC 3 78 3 60 3 39 3 12 CM 1 14 1 23 1 28 1 47 23 SHC 1 56 1 48 1 39 1 27 21 25 SHC 1 79 1 71 1 62 1 50 27 SHC 2 02 1 94 1 85 1 74 29 SHC 2 25 2 17 2 08 1 97 31 SHC 2 48 2 40 2 31 ...

Страница 32: ...2 82 2 71 TC 3 57 3 40 3 20 2 94 CM 1 07 1 15 1 20 1 38 21 SHC 1 59 1 51 1 41 1 30 19 23 SHC 1 82 1 74 1 64 1 53 25 SHC 2 05 1 97 1 88 1 76 27 SHC 2 28 2 20 2 11 1 99 29 SHC 2 51 2 43 2 34 2 22 31 SHC 2 74 2 66 2 57 2 46 TC 3 78 3 60 3 39 3 12 CM 1 10 1 18 1 23 1 42 23 SHC 1 56 1 48 1 39 1 28 21 25 SHC 1 79 1 71 1 62 1 51 27 SHC 2 03 1 95 1 85 1 74 29 SHC 2 26 2 18 2 09 1 97 31 SHC 2 49 2 41 2 32 ...

Страница 33: ...Conditions Running Amps A 0 17 0 18 0 24 0 25 4 49 4 27 4 9 4 7 Power Input kW 0 034 0 040 0 052 0 060 0 964 0 990 1 05 1 09 Rating Conditions Indoor Air Temperature 27 C D B 19 C W B Outdoor Air Temperature 35 C D B Full Load Conditions Indoor Air Temperature 32 C D B 23 C W B Outdoor Air Temperature 43 C D B Indoor Unit SAP K91GJA Outdoor Unit SAP C91GA Indoor Unit Outdoor Unit Complete Unit Fan...

Страница 34: ...JA Outdoor Unit SAP C121JA Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 220 240V Single phase 50Hz Rating Conditions Running Amps A 0 17 0 18 0 23 0 24 5 40 5 48 5 8 5 9 Power Input kW 0 034 0 040 0 050 0 058 1 156 1 192 1 24 1 29 Full Load Conditions Running Amps A 0 17 0 18 0 23 0 24 6 80 6 78 7 2 7 2 Power Input kW 0 034 0 040 0 050 0 058 1 476 1 502 1 56...

Страница 35: ...avoid electrical shock hazard be sure to disconnect power before checking servicing and or cleaning any electrical parts WARNING Indoor Unit SAP K71GJA SAP K91GJA SAP K121GJA Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 36: ...cal shock hazard be sure to disconnect power before checking servicing and or cleaning any electrical parts WARNING Outdoor Unit SAP C71GA SAP C91GA SAP C91JA Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 37: ...d electrical shock hazard be sure to disconnect power before checking servicing and or cleaning any electrical parts WARNING Outdoor Unit SAP C121GA Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 38: ...d electrical shock hazard be sure to disconnect power before checking servicing and or cleaning any electrical parts WARNING Outdoor Unit SAP C121JA Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 39: ... the unit Fig 1 install the unit within the maximum elevation difference H above or below the outdoor unit and within a total tubing length L from the outdoor unit as detailed Table 1 and Fig 2a Indoor Unit 5 cm min 5 cm min 5 cm min INDOOR UNIT Front View INDOOR UNIT Tubing length L OUTDOOR UNIT Elevation difference H Fig 2 Fig 2a Fig 1 WARNING Table 1 If total tubing length becomes 7 5 to 15 max...

Страница 40: ...inst possible water damage and decreased service life Fig 5 use lug bolts or equal to bolt down unit reducing vibration and noise Outdoor Unit Outdoor unit Hot air Heat source Exhaust fan Fig 3 NO Fig 3 Air intake Min 10 cm Air discharge Min 5 cm Min 40 cm Valve side Min 25 cm Top View Side air intake C91 only Rear air intake Concrete or equal About 10 cm Min 10 cm Anchor bolts 4 pcs About 40 cm 2...

Страница 41: ...en using the remote control unit Point the transmission portion of the remote control unit at the receiver area of the indoor unit when operating the remote control unit and during operation of the air conditioner Do not place objects which may block the transmitted signals between the receiver and the remote control unit When mounting the remote control unit to prevent theft Fig 6b 1 Attach the h...

Страница 42: ... refrigerant tubing the compressor or any moving part To avoid the risk of electric shock each air conditioner unit must be grounded Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram The indoor unit draws its power from the outdoor unit WARNING WARNING CAUTION WIRING SYSTEM DIAGRAM INDOOR UNIT OUTDOOR UNIT Terminal Terminal Power line Control line Power su...

Страница 43: ...as a built in automatic time delay to allow the internal pressure to equalize As a protective measure the control circuit switches the compressor OFF after 5 minutes or more of compressor operation Thermo ON When the room temperature is above T 1 C T C is set temperature Compressor ON Thermo OFF When the room temperature is equal to or below set temperature T C Compressor OFF 3 minutes 3 minutes 3...

Страница 44: ...he indoor heat exchange coil falls below 1 C the control circuit stops the compressor for at least 6 minutes The compressor does not start again until the temperature rises above 8 C or 6 minutes has elapsed ON ON ON ON OFF OFF Set speed More than 10 minutes 6 minutes T 1 C Indoor heat exch coil temp 1 C Compressor Indoor fan Room temp Thermo OFF Thermo ON Set temp T C More than 10 minutes More th...

Страница 45: ...he outdoor temperature If the outdoor air temperature falls below 28 5 C the fan speed switches to LOW If the outdoor air temperature rises above 31 5 C the fan speed switches to HIGH This function does not become active in heating operation H H L 31 5 28 5 Outdoor air temperature C Outdoor fan speed Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 46: ...10 of the rating Check that power is being supplied 9 1 4 Check lead wires and connectors in indoor and outdoor units Check that coating of lead wires is not damaged Check that lead wires and connectors are firmly connected Check that wiring is correct Outdoor unit Indoor unit Ground Inter unit power wiring 1 2 4 5 6 Power supply CxxGA 50Hz 1 phase 220 240V CxxJA 60Hz 1 phase 220V Ground 1 2 4 43 ...

Страница 47: ...to OFF Measure insulation resistance of electrical parts in indoor unit 1 Remove both power supply wires and inter unit wires from terminal plate in outdoor unit Measure insulation resistance of outdoor unit 2 Remove inter unit wires from terminal plate in indoor unit Measure insulation resistance of indoor unit Insulation of outdoor unit is defective Insulation of indoor unit is defective WARNING...

Страница 48: ...idue buildup on transmitter of remote control unit Check for residue buildup on remote control receiver on front of indoor unit Clean receiver Does not run NO Check power supply Power is being supplied to the outdoor unit Circuit breaker is tripped Power failure Reset breaker Wait for recovery or contact power company Replace with suitable one larger capacity NO Check capacity of circuit breaker C...

Страница 49: ...F Measure resistance of primary and secondary winding of transformer TR Indoor PCB Ass y or switch Ass y is defective OK OK Measure resistance of indoor and or fan motor winding FM Measure resistance of compressor motor winding CM OK Measure coil resistance of power relay PR Replace the fuse If fuse has been blown Measure resistance of primary and secondary winding TR YES NO OPERATION selector swi...

Страница 50: ...ance of power relay Check indoor PCB Ass y PR OK NO Is room temperature too low Try to lower setting temperature by temperature setting button button Outdoor unit still does not run Remote control unit is defective Try to run using another remote control unit 47 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 51: ...nding Check fan motor capacitor Fan cannot be turned OK Check fan rotation Turn fan gently once or twice by hand Check fan casing foreign matter on inside Fan motor burnout or foreign matter in bearings Remove foreign matter or repair Repair or replace Measure resistance of indoor fan motor winding Check fan motor capacitor OK Measure resistance of indoor fan motor winding Check fan motor capacito...

Страница 52: ...door unit 23S Measure resistance of flap motor winding Check compressor motor capacitor Measure resistance of compressor motor winding NO YES YES Overload relay is working YES Temperature of compressor is abnormally high Refrigerant gas shortage Charge refrigerant gas R22 Rotor may be locked up Measure Power supply voltage The voltage is too low No 49 Все каталоги и инструкции здесь http splitoff ...

Страница 53: ...ity of gas shortage YES Check position of remote control unit Cool air from air conditioner reaches position directly Change position of remote control unit Wide and narrow tubes between indoor unit and outdoor unit are insulated Insulate both wide and narrow tubes separately and then tape together Measure temperature of suction and discharge air of air conditioner Charge refrigerant gas R22 Check...

Страница 54: ...conditions as the controller tries to detect extremely high room temperature In Cooling mode The air conditioner continues to operate Thermo ON Both the outdoor fan and compressor do not stop As a result the room becomes too cold Definition of Open or Short Circuit of Sensor Thermistor Open A lead wire is broken or disconnected or the circuit inside the temperature sensor is open Short The protect...

Страница 55: ...with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw where power supply lines are connected on the terminal plate Fig 2 10 1 4 Measurement of Insulation Resistance for Electrical Parts Disconnect the lead wires of the desired electric part from terminal plate capacitor etc Similarly disconnect the connector Then measure the ins...

Страница 56: ... capacitor terminals as shown in Fig 7 Observe the deflection of the pointer setting the resistance measuring range of the multimeter to the maximum value The capacitor is good if the pointer bounces to a great extent and then gradually returns to its original position The range of deflection and deflection time differ according to the capacity of the capacitor Fuse PCB Ass y Fuse Compressor motor...

Страница 57: ...ed you cannot restore the original address setting of the remote control unit To Change Address on PCB 1 Cut jumper wire JP02 on the indoor unit PCB Use cutting pliers to cut and disconnect the Jumper wire 2 Switch the address switch on the remote control unit to B position 3 After inserting the batteries press reset button To Change Address on Remote Control Unit Remove the batteries before chang...

Страница 58: ...INSTRUCTION MANUAL SAP K71GJA SAP C71GA SAP K91GJA SAP C91GA SAP C91JA SAP K121GJA SAP C121GA SAP C121JA APPENDIX 55 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 59: ...be set to automatically turn off the unit at any time after one hour Night Setback Pressing this button changes the setting of the room temperature thermostat allowing you to set the temperature at whatever level that you find comfortable Automatic and 3 step Fan Speed Auto High Medium Low Air Sweep Control This function moves a flap up and down in the air outlet directing air in a sweeping motion...

Страница 60: ...Product Information If you have problems or questions concerning your Air Conditioner you will need the following information Model and serial numbers are on the nameplate of the cabinet Model No Serial No Date of purchase Dealer s address Phone number Alert Symbols The following symbols used in this manual alert you to potentially dangerous conditions to users service personnel or the appliance T...

Страница 61: ... a qualified electrician Safety Instructions Read this Instruction Manual carefully before using this air conditioner If you still have any difficulties or problems consult your dealer for help This air conditioner is designed to give you comfortable room conditions Use this only for its intended purpose as described in this Instruction Manual Never use or store gasoline or other flammable vapor o...

Страница 62: ...sture in the room condenses and drains off through this hose Outdoor Condensing Unit The outdoor unit contains the compressor fan motor heat exchanger coil and other electrical components Air outlet Drain hose Refrigerant tubes Air outlet Air intakes INDOOR UNIT OUTDOOR UNIT Remote control unit This illustration is based on the external appearance of a standard model Consequently the shape may dif...

Страница 63: ... is used only when servicing the air conditioner Do not set at the TEST position for normal operation OPERATION lamp This lamp lights when the system is in the continuous DRY or COOL mode TIMER lamp This lamp lights when the system is being controlled by the timer OI 378 06EG 6 Unit Display and Operation Selector Remote control receiver Operation selector TIMER lamp OPERATION lamp INDOOR UNIT IMPO...

Страница 64: ...tting timer Displayed when setting temperature 1 Operation mode COOL MILD DRY 2 Fan speed Automatic operation HIGH MEDIUM LOW 3 Set temperature 16 30 C When set to 28 C 4 Timer 12 hour ON Timer 12 hour OFF Timer 1 hour OFF Timer 5 NIGHT SETBACK 6 Confirmation of transmission 7 Flap angle indication 8 Sweep indication SAP K121GJA oi 3 4 00 16 49pm Page 7 Все каталоги и инструкции здесь http splitof...

Страница 65: ...s in the display and the remote control unit will automatically adjust the set temperature to save energy TEMP setting buttons Press the button to increase the set temperature Press the button to reduce the set temperature ON OFF operation button This button is for turning the air conditioner on and off OI 378 08EG 8 Remote Control Unit Display TEMP setting buttons NIGHT SETBACK button TIMER OFF b...

Страница 66: ...r The air conditioner automatically decides the fan speeds button High fan speed Medium fan speed Low fan speed 1 HR TIMER button When you press this button regardless of whether the unit is 1 HOUR OFF TIMER operating or stopping the unit operates for one hour and then shuts down ACL button Puts the remote control unit into pre operation status Always press this ALL CLEAR button after replacing th...

Страница 67: ...osition from a wall mounted position To ensure that the air conditioner operates correctly DO NOT install the remote control unit in the following places DO NOT In direct sunlight Behind a curtain or other places where it is covered More than 8 m away from the air conditioner In the path of the air conditioner s airstream Where it may become extremely hot or cold Where it may be subject to electri...

Страница 68: ...ch may block the transmitted signals between the receiver and the remote control unit When Mounting the Remote Control Unit to Prevent Theft 1 Attach the holder to the wall with one of the screws using only the hole in the top of the holder 2 Remove the cover of the remote control unit and take out the batteries Next place the remote control unit in the holder 3 Fasten both the remote control unit...

Страница 69: ...F operation button STEP 3 Press the TEMP setting buttons to change the temperature setting to the desired temperature Adjustable temperature range 30 C max 16 C min STEP 4 Set the FAN SPEED selector button to the setting you want If the fan speed is set to Automatic the fan speed switches automatically according to the difference between the actual room temperature and the temperature setting STEP...

Страница 70: ...r in the air conditioner automatically controls the fan speed when the mode is selected When the air conditioner starts operating the difference between the room temperature and the set temperature is detected by the microcomputer which then automatically switches the fan speed to the most suitable level Cooling and DRY mode B Manual If you want to adjust fan speed manually during operation just s...

Страница 71: ...d the air conditioner automatically raises the temperature setting 1 C when 30 minutes have passed after the selection was made and then another 1 C after another 30 minutes have passed regardless of the indoor temperature when night setback was selected This enables you to save energy without sacrificing comfort This function is convenient when gentle cooling is needed Setting temperature Press t...

Страница 72: ...t will stop When the power is resumed the unit will restart automatically after three minutes In cooling operation any plastic parts may expand or shrink due to a sudden temperature change In this event a clicking sound may occur This is normal and the sound will soon disappear The remote control unit sends the setting condition to the air conditioner regularly at three minute intervals Remote Con...

Страница 73: ...ut the indication remains To check the status of the timer while it is counting down press the TIMER SET button Cancellation procedure Press the TIMER OFF button once again 2 TIMER OFF mode Example 2 TIMER ON mode Example OI 378 16EG 16 STEP 1 Press the MODE button and set the desired operation mode and press the ON OFF operation button See Operation with the Remote Control Unit page 12 STEP 2 Pre...

Страница 74: ...ur first is the one with the shorter time setting Cancellation procedure Press the TIMER ON button and TIMER OFF buttons once again Set the ON and OFF Timers simultaneously Unless you set the 12 Hour ON and OFF Timers at the same time they may not operate at the specified time NOTE 3 ON OFF Parogram Timer OI 378 17EG 17 TIMER ON display during counting TIMER OFF display during counting after 3 hou...

Страница 75: ...e TIMER OFF function operates the OFF Timer is canceled and the unit will stop operating one hour later By combining the 1 Hour OFF Timer and 12 Hour ON Timer it is possible to have the unit operate for just one hour from the present time and then have it switch on again later at a time specified by you Example Having the unit operate for just one hour from the present time and then switch on agai...

Страница 76: ...ically closes when the unit is off Use the FLAP button on the remote control to adjust the position of the flap If you move the flap by hand the flap position according to the remote control and the actual flap position may no longer match If this should happen shut off the unit wait for the flap to close and then turn on the unit again the flap position will now be normal again Do not have the fl...

Страница 77: ...ditioner off and also to disconnect the power before cleaning 2 Do not pour water on the unit to clean it This will damage the internal components and cause an electric shock hazard Clean the casing and grille of the indoor unit with a vacuum cleaner brush or wipe them with a clean soft cloth If these parts are stained use a clean cloth moistened with a mild liquid detergent When cleaning the gril...

Страница 78: ...st on the filter wash the filter in lukewarm soapy water rinse it in clean water and dry it How to replace the 1 With the FRONT mark anti mold filter facing you slide the anti mold filter up into the unit and then lower the handle into the groove on the unit 2 After installing the anti mold filter press the locations marked by the arrows and close the air intake grille OI 378 21EG 21 Air intake gr...

Страница 79: ... the symbols meaning FRONT facing the front 3 Reinstall the anti mold filter Cleaning the main unit and Wipe clean using a soft dry cloth remote controle unit To remove stubborn dirt moisten a cloth in warm water no hotter than 40 C wring thoroughly and then wipe The air intake grille can be removed in order to wash it with water Removing and remounting With the air intake grille open all the air ...

Страница 80: ... Power failure 2 Leakage circuit breaker tripped 3 Line voltage is too low 4 Operation button is OFF 5 Batteries in remote control unit have run down Trouble in wiring system Obstruction in front of condenser coil 1 Dirty or clogged air filter 2 Heat source or many people in room 3 Doors and or windows are open 4 Obstacle near air intake or air discharge port 5 Thermostat is set too high for cooli...

Страница 81: ...SANYO Electric Co Ltd Osaka Japan SM700455 10 00 200 Printed in Japan Большая библиотека технической документации http splitoff ru tehn doc html каталоги инструкции сервисные мануалы схемы ...