25
MAINTENANCE
Cleaning of condenser filter
This unit is provided with the filter check lamp. This lamp
lights when the condenser filter is clogged. Clean the
filter according to the following procedure. As a clogged
filter may cause poor cooling and compressor trouble,
clean it once a month.
1.
Remove the mounting screw securing the grille and pull
out the grille. (Fig. 1)
2.
Remove the filter installed inside the grille (Fig. 2), wash
it with water and dry it naturally.
3.
Replace the clean filter as before.
4.
Replace the grille and tighten the screws.
5.
Check that the filter check lamp is off.
CAUTION
Never touch the condenser directly when the filter is removed for cleaning.
It may cause injury by
heat.
This unit is provided with the filter check lamp. This lamp lights when the condenser filter is clogged.
Clean the filter according to the following procedure. As a clogged filter may cause poor cooling and
compressor trouble, clean it once a year.
1.
Turn the power switch OFF.
2.
Take off the 4 screws from the left side cover and
remove it. Pull the condenser filter toward you.
3.
For cleaning dust and other foreign substances
accumulated on the condenser filter surface, wash it
with clean water, and dry naturally.
4.
After finishing the cleaning, insert the condenser
filter to the rail.
5.
Fix the cover in its former place and operate the
freezer again.
Fig. 1