System Design
2. Refrigerant piping design
D-9
(6) Calculation of amount of additional refrigerant charge
1) Table 2 shows the refrigerant charge at factory shipping time. Additional refrigerant must be added
according to the size and length of the piping (calculated from the size and diameter of the liquid piping
using the values in Table 1).
Table 1. Quantity of additional refrigerant charge
Table 2.
Liquid pipe
diameter (mm)
Additional charge quantity per
meter (g/m)
φ
9.52
56
φ
12.7 128
φ
15.88 185
φ
19.05 259
φ
22.22 366
Required additional refrigerant charge (g)
= 366
×
(A) + 259
×
(B) + 185
×
(C) + 128
×
(D) + 56
×
(E) +
Unit additional charge amount(F)
(A) = total length in meters of 22.22 mm diameter liquid piping
(B) = total length in meters of 19.05 mm diameter liquid piping
(C)= total length in meters of 15.88 mm diameter liquid piping
(D) = total length in meters of 12.70 mm diameter liquid piping
(E) = total length in meters of 9.52 mm diameter liquid piping
(F) = Unit additional charge amount (Table 3)
2) Be careful to charge accurately according to refrigerant weight.
3) Charging procedure
Evacuate the system, close the gauge manifold at the gas pipe side to ensure that no refrigerant enters
the gas pipe side, then charge the system with liquid refrigerant at the liquid pipe side. While charging,
keep all valves fully closed.
The compressor can be damaged if liquid refrigerant is added at the gas pipe side.
4) If the system does not accept the predetermined quantity of refrigerant, fully open all valves and run the
system (either heating or cooling). While the system is running, gradually add refrigerant at the low
pressure side by slightly opening the valve on the cylinder just enough so that the liquid refrigerant is
gasified as it is sucked into the system. (This step is normally only needed when commissioning the
system.
)
All outdoor unit valves should be fully open.
5) When charging is completed, fully open all valves.
6) Avoid liquid back-flow when charging with R410A refrigerant by adding small amounts at a time.
Notes
When charging with additional refrigerant, use liquid only.
R410A cylinders are colored gray with a pink top.
Check whether a siphon pipe is present (indicated on the label at the top of the cylinder).
)
Depending on refrigerant and system pressure, conventional refrigerant (R22, R407A) equipment may
or may not be compatible with R410A equipment, so care is needed.
In particular, the gauge manifold used must be specifically designed for R410A.
Be sure to check the limiting density.
Refer to the section “Opening the closed valves” when the instructions call for fully opening all valves.
Model Type
No.
Quantity of refrigerant
charge when shipped (kg)
Type190
16
Table 3.
Model Type No.
Unit additional charge
amount (kg)
Type190
4.5
Содержание ECO G SGP-EGW190M2G2W
Страница 3: ...A 1 System Configuration Contents 1 Type Configuration 1 Outdoor unit A 2 ...
Страница 9: ...Outdoor Unit 3 External Dimensions B 5 ...
Страница 10: ...Outdoor Unit 4 Wiring Diagram B 9 ...
Страница 13: ...Outdoor Unit 6 Operating Sound Level Characteristics B 9 1 Standard Mode ...
Страница 14: ...Outdoor Unit 6 Operating Sound Level Characteristics B 10 2 Quiet Mode ...
Страница 17: ...Control 1 System Block Diagram C 2C 2 ...
Страница 18: ...Control Related 2 Remote Control Warning List C 3 ...
Страница 19: ...Control Related 2 Remote Control Warning List C 4 ...
Страница 20: ...Control Related 2 Remote Control Warning List C 5 ...
Страница 23: ...System Design 1 Operating temperature ranges for heating and cooling D 3 temperature is below 10ºC ...
Страница 25: ...System Design 2 Refrigerant piping design D 4 2 Selecting system header and branch piping sizes ...
Страница 40: ...Installation Work 1 Points regarding refrigerant pipe work E 2 1 Points regarding branch pipe work APR P160BG ...
Страница 41: ...Installation Work 1 Points regarding refrigerant pipe work E 3 APR P680BG ...
Страница 42: ...Installation Work 1 Points regarding refrigerant pipe work E 4 APR P1350BG ...
Страница 43: ...Installation Work 1 Points regarding refrigerant pipe work E 5 APR CHP680BG APR CHP1350BG ...
Страница 48: ...Installation Work 2 Points regarding electrical work outdoor unit E 10 1 Wiring thickness and device capacity ...
Страница 50: ...Installation Work 2 Points regarding electrical work outdoor unit E 12 3 Precautions regarding electrical work ...
Страница 51: ...Installation Work 2 Points regarding electrical work outdoor unit E 13 ...
Страница 52: ...Installation Work 3 Outdoor unit installation work E 14 ...
Страница 53: ...Installation Work 3 Outdoor unit installation work E 15 ...
Страница 54: ...Installation Work 3 Outdoor unit installation work E 16 ...
Страница 55: ...Installation Work 3 Outdoor unit installation work E 17 ...
Страница 56: ...Installation Work 3 Outdoor unit installation work E 18 ...
Страница 57: ...Installation Work 3 Outdoor unit installation work E 19 ...
Страница 58: ...Installation Work 3 Outdoor unit installation work E 20 ...
Страница 59: ...Installation Work 3 Outdoor unit installation work E 21 ...
Страница 60: ...Installation Work 3 Outdoor unit installation work E 22 ...
Страница 61: ...Installation Work 3 Outdoor unit installation work E 23 ...
Страница 62: ...Installation Work 3 Outdoor unit installation work E 24 ...
Страница 63: ...Installation Work 3 Outdoor unit installation work E 25 ...
Страница 64: ...Installation Work 3 Outdoor unit installation work E 26 ...
Страница 65: ...Installation Work 3 Outdoor unit installation work E 27 ...
Страница 66: ...Installation Work 3 Outdoor unit installation work E 28 ...
Страница 67: ...Installation Work 3 Outdoor unit installation work E 29 ...
Страница 68: ...Installation Work 3 Outdoor unit installation work E 30 ...
Страница 69: ...Installation Work 3 Outdoor unit installation work E 31 ...
Страница 70: ...Installation Work 3 Outdoor unit installation work E 32 ...
Страница 71: ...Installation Work 3 Outdoor unit installation work E 33 ...
Страница 72: ...F 1 Separately Sold Parts Contents 1 Outdoor unit related parts 1 Exhaust extension kit SGP PEX560K F 2 ...