I - 7
p
Forced Rotational Speed Setting Operation
This setting is used to forcibly fix the revolution of en
-
gine when doing test runs.
1) Press the HOME (S004) key for one second or more.
The menu item number “
” will be dis
-
played.
2) Next press the UP (S005) and DOWN (S006) keys to
display menu item number “
”
3) Press the SET (S007) key while “
” is dis-
played. The forced engine revolution setting display
“
” will appear (Figure 9).
4) When the SET (S007) key is pressed in this mode, the
following displays will cycle in sequence at 1-second
intervals.
Display
Function
Forced engine revolutions (example: 1400 min
-
)
Engine revolutions (example: 1400 min
-
)
Compressor inlet pressure (example: 0.56 Mpa)
Compressor outlet pressure (example: 0.56 Mpa)
Compressor outlet temperature (example: 85.0ºC)
5) Setting and Canceling Forced Rotational Speed
Select forced engine revolutions using the UP (S005) and DOWN (S006) keys.
The speed can be set within the range from the minimum speed to the maximum speed of the engine, in units of
100 revolutions. With the speed selected, press the SET (S007) key for 1 second or more. The selected speed will
be fixed as the forced engine revolutions. During this time, the forced setting in progress display will appear (the
TEST/WARNING LED (D052) will light).
To cancel the forced engine revolution setting, press the SET (S007) key for 1 second or more. The forced setting
in progress display will be cleared (the TEST/WARNING LED (D052) will go out) and the display will return to
the forced setting selection operation.
q
Test Run Procedure
This setting is used to perform a test run from the outdoor unit.
1) Set all remote controller switches to “Stop”.
2) Select “
“ (forced cooling test run) or “
“ (forced heating test run). For details see steps 1) to 4)
on page I-7.
3) Setting and Canceling a Forced Test Run
When “
“ (forced cooling test run) or “
“ (forced heating test run) is selected, holding down
the SET (S007) key 1 second or longer causes the forced setting to appear (TEST/WARNING LED (D052) before
a test run starts. To cancel forced test run operation, hold down the SET (S007) key for 1 second or longer. This
clears the forced setting (TEST/WARNING LED (D052) goes off) and the forced setting selection reappears.
Figure 9