5
Instruction Manual for BIO-WALL™
1-888-726-8869
www.sanuvox.com
Step by Step Installation
STEP 1
STEP 2
STEP 3
STEP 4
1. Select where the BIO-WALL™ extrusion will be installed. The
location requires a straight duct of a minimum length without obstruction.
Refer to the table below according to the length of the BIO-WALL™ to be
installed.
Model
Length required
for installation
Distance between
support rods
BIOM18
28" (71 cm)
25.25" (64 cm)
BIOM24
34" (86 cm)
31.25" (80 cm)
BIOM30
40" (102 cm)
37.25" (94.5 cm)
BIOM40
50" (127 cm)
47.25" (120 cm)
BIOM50
60" (152 cm)
57.25" (145.5 cm)
BIOM60
70" (178 cm)
67.25" (171 cm)
NOTE:
The BIO-WALL™ can be installed in the return plenum or in the
supply duct indistinctly. In any case, the extrusion must be positioned
parallel to the airflow and in the center of the ventilation duct.
2. Select the location where the ballast box will be installed.
Often the
ballast box is installed on the conduit or on one of the sides. You can
install it on a nearby wall, but make sure of the distance: you only have 3
m of cable between the box and the extrusion.
NOTE:
Operating information can be provided in 2 ways: via dry contacts
that relay data to a BMS or via a BioSmart touch screen (optional) that
can be installed up to 100 feet (32m) away.
3. Install an access door on the section that will receive the BIO-
WALL™ extrusion. The size of the access door will be determined by
the height of the duct.
NOTE: The access door must be able to uncover the upstream section of
the BIO-WALL™, so that the lamp connectors are directly in front of the
opening. So that when it comes time to change the lamps, this operation
can be done easily.
4. Install a limit switch on the access door. This will automatically cut off
the power supply to the system if someone inadvertently opens the door.
In this way, anyone is protected from being exposed to UV rays.
NOTE: The switch must be approved in the country where the installation
is made and must have the following characteristics: insulation of 600
volts and 500,000 cycles of operation.
In Canada and the USA, the MSCSWC14 switch is available from SANUVOX.