13
Instruction Manual for BIO-WALL™
1-888-726-8869
www.sanuvox.com
MAINTENANCE
How to Replace Lamp(s)
Lamps should be replaced every 2 years to maintain design specifications.
Replacing the lamps of a BIO-WALL™ is quick and easy. Turn off the power source. Remove and dispose of old lamps as you
would regular fluorescents. Replace new SANUVOX brand UV lamps. Turn the power source back on.
See below for detailed step-by-step instructions.
CAUTION: In order to avoid reduced performance of lamp(s), do not touch lamp glass without gloves.
STEP 2
STEP 3
STEP 4
STEP 5
1. Before doing any maintenance, be sure to turn off the power.
2. Open the duct access door.
3. Carefully pull one of the lamps to remove it from the metal clips holding
it in place. Gently remove the connector from the end of the lamp and
pull the lamp out of the conduit.
NOTE: If the connector is damaged, do not hesitate to replace it.
4. Take a new lamp – with your gloved hands, insert it into the conduit and
plug the connector into it. If you have difficulty inserting the connector,
turn it 90°.
5. Insert the lamp into the extrusion on the metal clamps and gently secure
it in place. It is likely that you will have to tighten the clamps a little
before putting the lamp in.
STEP 6
STEP 8
6. Do the same for the other 4 lamps.
7. When you are finished, close the access door and turn the power back on.
8. All that remains is to reset the hour counter to 17,000 hours.
Step by Step Lamp Replacement