SAFETY

DISCONNECT FROM THE MAINS SUPPLY BEFORE 

REMOVING ANY COVERS.

Never  attempt  to  replace  the  immersion  heater(s) 

other  than  with  the  recommended  PremierPlus 

immersion heater(s).

DO  NOT  BYPASS  THE  THERMAL  CUT-OUT(S)  IN 

ANY CIRCUMSTANCES

. Ensure the two male spade 

terminations  on  the  underside  of  the  combined 

thermostat  and  thermal  cut-out  are  pushed  firmly 

onto the corresponding terminations on the element 

plate assembly. 

In case of difficulty contact service support; contact 

details available at the back of this booklet.

INSTALLATION - INDIRECT UNITS

PLUMBING CONNECTIONS

PremierPlus indirect cylinders require the following 

pipework connections.

Cold water supply to and from inlet controls.

• 

Outlet to hot water draw off points. 

• 

Discharge  pipework  from  valve  outlets  to 

• 

tundish

Connection to the primary circuit.

• 

All  connections  are  22mm  compression.  However, 

3/4”BSP parallel threaded fittings can be fitted to the 

primary coil connections if required.

ELECTRICAL SUPPLY

1 2 3

B

A

1

1

2

2 3

Green/

yellow

Indirect thermal 

cut-out

Indirect 

thermostat

Terminal 

block

Green/

yellow

To indirect system 

controls junction 

box - see Figs . 8/9

13 amps mains 

supply. 1.5mm² 

min cable size

Brown

Blue

Direct 

thermostat

Fig. 8: Indirect electrical connections (schematic)

All units are fitted with a 3kW immersion heater and a 

combined thermostat and thermal cut-out to control 

the indirect heating source. The PremierPlus cylinder 

MUST be earthed. 

All wiring to the unit must be installed in  accordance 

with the latest IEE Wiring Regulations and the supply 

circuits  must  be  protected  by  a  suitable  fuse  and 

double pole isolating switch with a contact separation 

of at least 3mm in both poles. All connections are 

made to the terminal block located under the terminal 

cover mounted on the side of the unit. The supply 

cable(s) must be routed through the cable grip(s) in 

the terminal housing.

DISCONNECT FROM MAIN SUPPLY BEFORE REMOVING 

ANY COVERS. DO NOT BYPASS THE THERMAL CUT-

OUT(S)  IN  ANY  CIRCUMSTANCES.  Ensure  the 

thermostat  and  thermal  cut-out  sensing  bulbs  are 

pushed fully into the pockets on the element plate 

assembly. 

BOILER SELECTION

The boiler should have a control thermostat and non 

self-resetting thermal cut-out and be compatible with 

unvented storage water heaters.

Where use of a boiler without a thermal cut-out is 

unavoidable  a  “low  head”  open  vented  primary 

circuit  should  be  used.  The  feed  and  expansion 

cistern head above the PremierPlus cylinder should 

not exceed 2.5m.

PRIMARY CIRCUIT CONTROL

The  2  port  motorised  valve  supplied  with  the 

PremierPlus cylinder MUST be fitted on the primary 

flow  to  the  PremierPlus  cylinder  heat  exchanger 

and wired in series with the indirect thermostat and 

thermal cut-out fitted to the unit.

Primary circulation to the PremierPlus cylinder heat 

exchanger must be pumped;  gravity circulation WILL 

NOT WORK.

SPACE AND HEATING SYSTEMS CONTROLS

The controls provided with the PremierPlus cylinder 

will  ensure  the  safe  operation  of  the  unit  within 

the  central  heating  system.  Other  controls  will  be 

necessary to control the space heating requirements 

and times that the system is required to function. (See 

Fig. 7, page 10)

The  PremierPlus  cylinder  is  compatible  with  most 

heating  controls,  examples  of  electrical  circuits 

are  shown  in  Figs.  9  and  10  (page  12).  However, 

other systems may be suitable, refer to the controls 

manufacturers’  instructions,  supplied  with  the 

controls  selected,  for  alternative  system  wiring 

schemes.

Содержание PremierPlus 100

Страница 1: ...r s and thermal controls l Factory fitted temperature pressure relief valve l Cold water combination valve assembly l Expansion vessel and mounting bracket l Tundish l Motorised valve indirect models...

Страница 2: ...istance The outer casing is a combination of resilient thermoplastic mouldings and plastic coated corrosion proofed steel sheet All products are insulated with CFC free polyurethane foam to give good...

Страница 3: ...55 Indirect 100 125 25 120 147 27 150 184 31 170 203 33 210 251 41 250 300 50 300 360 60 Table1 unit weights WATER SUPPLY Bear in mind that the water supply to the property will be supplying both the...

Страница 4: ...unit The fittings are threaded 3 4 BSP male parallel should threaded pipe connections be required COLD FEED A 22mm cold water supply is recommended however if a 15mm 1 2 supply exists which provides...

Страница 5: ...old feed to the unit A swept tee joint is available as an accessory order code no 94 970 033 The secondary return pipe should be in 15mm pipe and incorporate a check valve to prevent backflow A suitab...

Страница 6: ...00 1090 16 4 27 21 170 306 925 1216 173 170 315 354 925 1216 16 0 30 24 210 306 1184 1474 215 210 315 354 1184 1474 18 3 34 26 250 306 1394 1726 257 250 315 354 1391 1726 20 38 27 300 306 1715 2040 31...

Страница 7: ...that is used by the safety devices the manifold should be factory fitted as part of the hot water storage system unit or package Tundish 3 54 The tundish should be vertical located in the same space a...

Страница 8: ...prevent contact whilst maintaining visibility and d discharges at high level e g into a metal hopper and metal downpipe with the end of the discharge pipe clearly visible or onto a roof capable of wi...

Страница 9: ...outlet sizes NOTE The above table is based on copper tube Plastic pipes may be of different bore and resistance Sizes and maximum lengths of plastic should be calculated using data prepared for the t...

Страница 10: ...suitable controller to BSEN 60730 The PremierPlus MUST be earthed All wiring to the unit must be installed in accordance with the latest IEE Wiring Regulations and the circuit must be protected by a s...

Страница 11: ...with a contact separation of at least 3mm in both poles All connections are made to the terminal block located under the terminal cover mounted on the side of the unit The supply cable s must be rout...

Страница 12: ...1 N 2 3 HTG ON DHW ON L N 2 3 1 L 2 N 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Supply 1 2 3 G W Bl 2 0 GY 3 G 1 Br Bl 2 0 L N Programmer Boiler Pump Zone valve HTG Premier Plus terminal block 1 3 2 2 Ro...

Страница 13: ...he temperature can be adjusted by inserting a flat bladed screwdriver in the adjustment knob on top of the immersion heater thermostat and rotating The adjustment range 1 to 5 represents a temperature...

Страница 14: ...r time the immersion heater gasket may become stuck to the mating surface To break the seal insert a round bladed screwdriver into one of the pockets on the immersion heater and gently lever up and do...

Страница 15: ...LY BEFORE OPENING THE COVER S Temperature adjustment is made by inserting a flat bladed screwdriver in the slot on the adjustment disc on top of the thermostat and rotating The adjustment range 1 to 5...

Страница 16: ...pply off 2 Check and open stock cock 2 Strainer blocked 2 Turn off water supply Remove strainer and clean see maintanance section 3 Cold Water Combination Valve incorrectly fitted 3 Check and refit as...

Страница 17: ...ion body 95 605 900 10 Pressure reducing valve cartridge 3 5bar 95 605 898 11 Temperature Pressure Relief Valve 95 605 810 12 Expansion vessel 12 litre 100 120 and 150 litre models 95 607 863 13 Expan...

Страница 18: ...losses based on an ambient air temperature of 20 C and a stored water temperature of 65 C ENVIROMENTAL Products are manufactured from many recyclable materials At the end of their useful life they sho...

Страница 19: ...d to frost nor has it been tampered with or been subjected to misuse or neglect No factory fitted parts have been removed for unauthorised repair or replacement The BenchmarkTM Commissioning Checklist...

Страница 20: ...20 notes...

Страница 21: ...21 notes...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...Business Centre Springfield Road Hayes Middlesex UB40 0TY Tel 0208 5730574 Parts Center Network 65 Business Park Bentley Wood Way Burnley Lancashire BB11 5ST Tel 01282 834403 www partscenter co uk Ne...

Отзывы: