DANGER 

MAKE SURE THAT STRING POLARITY IS CORRECT BEFORE 
CONNECTING THE STRINGS. 

ALWAYS PROVIDE FUNCTIONAL EARTH BONDING. 

 

 

CAUTION 

Properly tighten cable-glands and cable tubing to prevent water and small 
animals from entering the string box and lead to fire risks.  Plug unused cable 
glands.  

 

CAUTION 

Avoid transferring mechanical stress from the cables to  the string boxes. 
Provide special anchoring for the output cable.  Cable anchoring is particularly 
required for cable cross-sections over 240 mm

2

 and when the free cable length 

exceeds 100 cm. 

 

CAUTION 

The SMART STRING BOX LT must be installed with the cable in-out side turned 
down and the front cover in upright position.  Make sure that air circulation is 
effective around the string boxes. 

 

REPLACING AND INSERTING THE STRING FUSES 

  Open the inverter DC-side switch. 

  Open the cover of the SMART STRING BOX LT. 

  Open the disconnector in the SMART STRING BOX LT. 

 

Check with a current probe that no current is flowing. 

  Check string polarity by measuring voltage between the positive and negative pole of each string on the 

connection screws of each fuse-holder. Voltage must be positive, unless strings are in the shadow. 

  Extract or insert the fuse into the fuse-holder. 

 

DANGER 

Check with a current probe that no current is flowing

 

before opening and closing 

the fuse-holders.    

 

DANGER 

Wear PPE, dielectric gloves in particular, when extracting and inserting a fuse, 
as opening a fuse-holder does not ensure that both contacts of the fuse being 
replaced are properly cut off (dual power supply). 

  

 

PROHIBITION 

It is forbidden to install fuses different from those mentioned in the Installation 
Guide available for download from 

santerno.com

.

 

 

FINAL CHECKS 

  Before reclosing the cover, always  check that the inside of the SMART STRING BOX LT is free from 

condensation  or water residues; if this is not the case, the product must be placed in safety conditions, 
then thoroughly dried out.  

  Make sure that the cover is properly closed up to maintain IP65 degree of protection (no water and dust 

ingress). 

 

COMMISSIONING 

  Once the product installation is complete, carry out all final checks on the string boxes. 

  Close the disconnector on the SMART STRING BOX LT. 

  Close the cover of the SMART STRING BOX LT. 

  Restore auxiliary power supply. 

  Close the DC-switch on the inverter DC side. 

 

 

Содержание 15W00EPBA410

Страница 1: ...the Installation Guide carefully before operating the SMART STRING BOX LT products KEY TO SYMBOLS DANGER Indicates an operating procedure which if not carried out correctly may lead to injuries or ev...

Страница 2: ...he strings by operating inside the product or on strings connected to the product It is forbidden to make any technical or mechanical modifications to the product even when out of warranty DANGER Deat...

Страница 3: ...ctly forbidden to proceed with product handling and assembly operations in adverse weather conditions in snow rain or persistent fog Always check that there is no water or condensate inside the produc...

Страница 4: ...ed to the same inverter Open the cover of the SMART STRING BOX LT and open the disconnector it is NOT necessary to remove the polycarbonate panel Disconnect all the strings from the SMART STRING BOX L...

Страница 5: ...ained o Insert the functional earth cable through the dedicated cable lug o Connect the functional earth cable to the relevant terminal o Reassemble the polycarbonate panel by pressing it and tighteni...

Страница 6: ...4 board and DIP switch SW1 for termination enable disable on ES977 board M1 RS 485 IN M2 RS 485 OUT F RS 485 fuses A Rotary switch Modbus address strings 1 8 B Rotary switch Modbus address strings 9 1...

Страница 7: ...ach string on the connection screws of each fuse holder Voltage must be positive unless strings are in the shadow Extract or insert the fuse into the fuse holder DANGER Check with a current probe that...

Страница 8: ...than generally indicated UNINSTALLING THE PRODUCT Carry out the PRELIMINARY SAFETY OPERATIONS Remove the polycarbonate panel and make sure that no voltage is applied between 230 V auxiliary voltage te...

Страница 9: ...ili su santerno com Si raccomanda la lettura dell intera Guida all Installazione prima dell uso delle SMART STRING BOX LT SIMBOLOGIA PERICOLO Indica procedure operative che se non eseguite correttamen...

Страница 10: ...stringhe operando all interno del Prodotto o sulle stringhe ancora connesse al prodotto vietata qualunque modifica elettrica o meccanica interna anche fuori dal periodo di garanzia PERICOLO Pericolo d...

Страница 11: ...450 120 DIVIETO vietato procedere alle operazioni di movimentazione e montaggio del prodotto in condizioni meteo avverse presenza di neve pioggia nebbia persistente Verificare in ogni caso l assenza d...

Страница 12: ...tte le cassette stringa connesse allo stesso inverter Aprire la portella della SMART STRING BOX LT e aprire il sezionatore NON necessario rimuovere la lastra in policarbonato di protezione Scollegare...

Страница 13: ...lla terra funzionale attraverso il pressacavo dedicato o Connettere il cavo della terra funzionale al relativo morsetto o Rimontare il policarbonato di protezione premendo sul policarbonato per inseri...

Страница 14: ...sinserimento della terminazione su scheda ES977 M1 RS 485 IN M2 RS 485 OUT F Fusibili RS 485 A Rotary switch indirizzo Modbus stringhe 1 8 B Rotary switch indirizzo Modbus stringhe 9 16 SW1 DIP switch...

Страница 15: ...ibile Le stringhe devono presentare tensioni positive e simili a meno di ombreggiature Estrarre o inserire il fusibile dal portafusibile PERICOLO L apertura e la chiusura dei portafusibili non pu avve...

Страница 16: ...to a quanto prescritto DISINSTALLAZIONE Eseguire le OPERAZIONI PRELIMINARI DI MESSA IN SICUREZZA Verificare l assenza di tensione tra i morsetti di alimentazione ausiliaria 230 V tra il polo positivo...

Отзывы: