SECTION 9- ROUTINE MAINTENANCE
9.0 ROUTINE MAINTENANCE
Routine inspection and testing (power source)
An inspection of the power source, an insulation resistance test and an earth resistance test should be
carried out.
a)
For transportable equipment, at least once every 3 months; and
b)
For fixed equipment, at least once every 12 months.
The owners of the equipment should keep a suitable record of the periodic tests.
The only routine maintenance required for the power supply is a thorough cleaning and inspection,
with the frequency depending on the usage and the operating environment.
WARNING:
Disconnect Primary power at the source before opening the enclosure.
Wait at least two minutes before opening the enclosure to allow the primary
capacitors to discharge.
To clean the unit, open the enclosure (see Section 9.01, Opening the Enclosure) and use a vacuum
cleaner to remove any accumulated dirt and dust. The unit should also be wiped clean, if necessary;
with solvents that are recommended for cleaning electrical apparatus.
Do not blow air into the power supply during cleaning. Blowing
air into the unit can cause metal particles to interfere with
sensitive electrical components and cause damage to the unit.
Содержание IA-3000TP-U3E
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 26: ...26 PAGE LEFT INTENTIONALLY BLANK ...
Страница 32: ...32 PAGE LEFT INTENTIONALLY BLANK ...
Страница 54: ...54 PAGE LEFT INTENTIONALLY BLANK ...
Страница 74: ...74 PAGE LEFT INTENTIONALLY BLANK ...
Страница 87: ...87 PAGE LEFT INTENTIONALLY BLANK ...
Страница 94: ...PAGE LEFT INTENTIONALLY BLANK ...
Страница 97: ...PAGE LEFT INTENTIONALLY BLANK ...