background image

 

 

 

3.

 

Debugging method 

1)

 

After all the products are installed and confirmed, turn on the power of 
the fire alarm control panel, set address number for the installed fire 
indicating panel, and register the corresponding fire indicating panel on 
the fire alarm controller. At the same time according to the physical 
location of the fire indicating panel, configure the properties of the 
panel, such as districts, blocks, floors, rooms and other information.   

2)

 

If the installation is correct and the data is configured correctly, the 

COOM. Indicator will flash, indicating that the fire indicating panel has 
been operating normally. 

3)

 

Simulate reporting multiple fire (or feedback) for test, the fire 

indicating panel in the same or adjacent layers (according to "roll 
layer" fire alarm controller Settings) with those simulated fire(or 
feedback) will receive fire (or feedback) information, lit the fire 
emergency lights, at the same time show the location and time of the 
fire alarm. After the test, reset the fire alarm control panel, fire 
indicating panel will be reset at the same time. 

 

.  

Fault Analysis and Troubleshooting 

Faults 

Possible Reasons 

Solutions 

Remarks

The power is not normal 

Check the DC24V 
power supply 

Poor connection with the 
controller cable 

Check the 
connection cable 

The fire 

indicating 

panel shows 

no display or 

abnormal 

display. 

LCD or the main CPU is 
damaged 

Return to factory 
for maintenance 

 

Indicating 

panel 

communicatio
n is abnormal. 

The communication line 
has something wrong, or 
the host did not send the 
inspection data. 

Check if there is 
any problem with 
the signal line. 

 

Unable to 

report fire 

alarm. 

Check if the host has 
properly registered fire 
indicating panel. 

The host registers 
the indicating 
panel. 

 

Содержание JB-FSD-9082

Страница 1: ...light alarm meanwhile the relevant fire alarm information will be displayed on the screen Features Beautiful and elegant appearance Easy to operate easy to install With a stable and reliable communic...

Страница 2: ...ct Usage 1 Terminal description 24V positive power input GND negative power input A signal terminal 485A B signal terminal 485B PE 2 Wiring diagram 24V GND A B SEC3002 JB FSD 9082 JB FSD 9082 JB FSD 9...

Страница 3: ...interface is as shown in Figure 4 When more than one fire alarm or feedback message is displayed the next message will be scrolled and the time interval for rolling display is 8 seconds If the current...

Страница 4: ...eceiving two or more fire alarm messages the machine will automatically scroll to display the fire alarm information Every time you press the left key it shows the last fire alarm message and each tim...

Страница 5: ...press the right key to exit Note The default address of the fire indicating panel is 01 The default language is Chinese and the default display mode is auto Product Installation and Debugging 1 Instal...

Страница 6: ...the guide groove on the back of the fire indicating panel fits the base fully Then tighten the hook on the back of the panel and the guide piece of the fixed base with supporting screws as shown in F...

Страница 7: ...fire alarm controller Settings with those simulated fire or feedback will receive fire or feedback information lit the fire emergency lights at the same time show the location and time of the fire al...

Страница 8: ...nnection etc 2 The fire indicating panel is a precision electronic product which needs to be managed by a special person 3 Please do not wipe the machine surface with alcohol Address 3 F Guangcai Xint...

Отзывы: