7
3.
Debugging method
1)
After all the products are installed and confirmed, turn on the power of
the fire alarm control panel, set address number for the installed fire
indicating panel, and register the corresponding fire indicating panel on
the fire alarm controller. At the same time according to the physical
location of the fire indicating panel, configure the properties of the
panel, such as districts, blocks, floors, rooms and other information.
2)
If the installation is correct and the data is configured correctly, the
COOM. Indicator will flash, indicating that the fire indicating panel has
been operating normally.
3)
Simulate reporting multiple fire (or feedback) for test, the fire
indicating panel in the same or adjacent layers (according to "roll
layer" fire alarm controller Settings) with those simulated fire(or
feedback) will receive fire (or feedback) information, lit the fire
emergency lights, at the same time show the location and time of the
fire alarm. After the test, reset the fire alarm control panel, fire
indicating panel will be reset at the same time.
.
Ⅶ
Fault Analysis and Troubleshooting
Faults
Possible Reasons
Solutions
Remarks
The power is not normal
Check the DC24V
power supply
Poor connection with the
controller cable
Check the
connection cable
The fire
indicating
panel shows
no display or
abnormal
display.
LCD or the main CPU is
damaged
Return to factory
for maintenance
Indicating
panel
communicatio
n is abnormal.
The communication line
has something wrong, or
the host did not send the
inspection data.
Check if there is
any problem with
the signal line.
Unable to
report fire
alarm.
Check if the host has
properly registered fire
indicating panel.
The host registers
the indicating
panel.