Add.
Code
Description
Default
40062
rFy
Refrigerant
0(R22)
Add.
Code
Description
Default
40001
SH
Target superheat
6
Add.
Code
Description
Default
40003
b1r
Start open ratio
0
40004
Sdt
Start open ratio duration time
0
0
R22
7
R1234YF
14
R744(CO2)
21
R124
1
R404A
8
R290
15
R744(N2O)
22
R717
2
R410A
9
R450A
16
R32
23
R407H
3
R134A
10
R513A
17
R245FA
24
R454C
4
R407C
11
R448A
18
R23
25
R455A
5
R507
12
R449A
19
R407A
6
R1234ZE
13
R452A
20
R407F
d. Main parameter setting
1. Refrigerant selection
Refrigerant data is in
2. Target superheat setting
Target superheat is in
3. Start open ratio and duration time
You can find it in
Now 26 kinds refrigerants is available in controller as below:
If the target SH is too small, may cause liquid hammer in compressor; if the target value is too large, the evaporator energy
efficiency will be very low.
When controller receives compressor RUN signal, EEV will keep the start opening ratio for the duration time.