Merlin 

 

  

 

 

 

 

 

 

Product Data Sheet 

 

 

 

 

S&S Northern Ltd

  

4  

 

             On Auto-shut down gas supply will be turned Off. There are two blue dip-switches   

             located on the inside facia of the Merlin 1000V

W+ labelled “Electric” and “Water”.   

             

They are factory set in the ‘off’ position. On installation, they can be switched to the   

             

‘on’ position. This will instruct the system to also turn off Electric and/or Water   

             services when performing Auto-shut down. 

 

2.9 

Remote Emergency Shut Off Buttons

. The terminal for remote emergency shut-off buttons 

 

is detailed on the circuit board as “EM Remote”. These connections are linked out as a factory 

 

setting. Remote emergency shut-off buttons should be volt free and wired to the Merlin    

 

 using two-core cable. 

2.10 

CO2/Gas Detected. 

The terminals detailed on the circuit board as “Gas Detector”. These 

connections are “+,-“ and ”

” these can be wired to a Merlin Natural gas, Carbon monoxide 

or LPG detector. This terminal can also be wired to a CO2 monitor to shut off the system in the 
event of High CO2 levels. If no detector is being used l

eave the link in between the “

”. 

2.11 

FS 123. 

This terminal switches 12v when the key is turned on and off. This can be linked to a 

fan switch (panel supplied separately) which can provide power to the fans when the control 
panel is switched on. 

2.12 

Fan PD Switch. 

This terminal is used to receive an input signal from external air pressure  

switches or external current monitors. This terminal is linked out as factory setting. Wiring to 
the air pd switches & current monitors should be made using a two-core cable and volt free 
connections. 

2.13 

12v DC. 

This is a permanent 12v DC output when there is power at the panel. 

2.14 

Internal Buzzer. 

Operates at 65dB measured 30cm from closed panel. 

  

Note: all low voltage connections should be made using a screened cable to 

 

avoid electrical interference should not be in the same conduit as per the low 

 

voltage directive.

 

 Operation Instructions  

3.1 

How to turn the system on and off 

1.  Turn the key switch to on position.  
2.  Gas, electric and water will flash for 10 seconds. 
3.  Press relevant service button to turn required utility on. 
4.  Turn the key switch to the off position to turn the panel off. 

  

Please Note: All services can be turned on or off only within 10 secs of the key 

 

switch being turned on. After 10 secs, all utility buttons will be disabled. The 

 

user must turn the key off and back on to adjust any services. 

3.2 

Explanation of LED status 

 

Power LED  

  

 When the system is connected to the mains supply, the Red LED of the S&S Logo 

 

 located in the bottom right corner of the panel will illuminate. When no power is    

 

 present, this LED will not light up.  

  

 RED = OK  

  

 OFF = No power to  

 

 
 

 

Содержание Merlin 1000VW+

Страница 1: ...Merlin 1000VW Product Data Sheet S S Northern Ltd 1 Gas Safety Products Merlin 1000VW Gas Proving Electric Water Isolation System Installation operating and maintenance 20 01 2017...

Страница 2: ...as Detected 4 2 11 FS 123 4 2 12 Fan PD Switch 4 2 13 12v DC 4 2 14 Internal Buzzer 4 3 Operation Instructions 4 3 1 How to turn the system on and off 4 3 2 Explanation of LED status 4 Power LED 4 Gas...

Страница 3: ...ally fused at 3 Amps 2 4 Electric Contactor An electrical output will be supplied to an electrical contactor supplied by others This will be internally fused at 3 Amps and should be connected to the t...

Страница 4: ...the fans when the control panel is switched on 2 12 Fan PD Switch This terminal is used to receive an input signal from external air pressure switches or external current monitors This terminal is li...

Страница 5: ...panel is checking the integrity of the gas installation upon start up GREEN proving the gas line do NOT operate any appliances Test Fail LED Under normal working conditions this LED is off When the p...

Страница 6: ...MS integration The Merlin 1000VW can be integrated with a BMS to make or break a circuit on gas on gas off valve open or valve closed This will tell the BMS whether or not the room has use of the gas...

Страница 7: ...acia of the Merlin 1000VW labelled Fill Time and Prove Time They are factory set in the off position Fill and prove time can be changed by turning the relevant dip switch to on position Fill time Off...

Страница 8: ...ns and Fire Alarm input wired in series purchased separately VOLT FREE INPUT 10 Methane CO or LPG Detector power supply and volt free input purchased separately CO2 Monitor purchased separately VOLT F...

Страница 9: ...ww snsnorthern com info snsnorthern com South East Division Tel 44 0 1702 291 725 Fax 44 0 1702 299 148 south snsnorthern com Rev Date Author Description 01 20 01 2017 S S Northern BT Merlin 1000VW Pr...

Отзывы: