29. INSTALLATION AND CONTROL OF EXTERNAL BATTERIES
The SLIM heat recovery units are complemented by a complete range of air treatment accessories consisting of:
• Electrical postheater module
• Hot water coil module.
• Reversible water coil module.
• Chilled water coil module.
• Direct expansion coil module
For more information about the external modules, see sections "7.2. External modules dimensions", and "11.2. External
batteries".
List of external modules by models:
Heat recovery unit
model
Electrical
postheater module
Hot water coil
module
Reversible water
coil module
Chilled water coil
module
Direct expansion
coil module
SLIM 800
R
5800040900
SL-DI 800 3 M R
5800038500
SL-DC 800 2 R
5800041700
SL-DFR 800 3 R
5800039300
SL-DF 800 5 R
5800040100
SL-DX 800 4 R
L
5800040800
SL-DI 800 3 M L
5800038400
SL-DC 800 2 L
5800041600
SL-DFR 800 3 L
5800039200
SL-DF 800 5 L
5800040000
SL-DX 800 4 L
SLIM 1200
R
5800041100
SL-DI 1200 4 M R
5800038700
SL-DC 1200 2 R
5800041900
SL-DFR 1200 3 R
5800039500
SL-DF 1200 5 R
5800040300
SL-DX 1200 4 R
L
5800041000
SL-DI 1200 4 M L
5800038600
SL-DC 1200 2 L
5800041800
SL-DFR 1200 3 L
5800039400
SL-DF 1200 5 L
5800040200
SL-DX 1200 4 L
SLIM 1600
R
5800041300
SL-DI 1600 7,5 T R
5800038900
SL-DC 1600 2 R
5800042100
SL-DFR 1600 3 R
5800039700
SL-DF 1600 5 R
5800040500
SL-DX 1600 4 R
L
5800041200
SL-DI 1600 7,5 T L
5800038800
SL-DC 1600 2 L
5800042000
SL-DFR 1600 3 L
5800039600
SL-DF 1600 5 L
5800040400
SL-DX 1600 4 L
SLIM 2000
R
5800041500
SL-DI 2000 9 T R
5800039100
SL-DC 2000 2 R
5800042300
SL-DFR 2000 3 R
5800039900
SL-DF 2000 5 R
5800040700
SL-DX 2000 4 R
L
5800041400
SL-DI 2000 9 T L
5800039000
SL-DC 2000 2 L
5800042200
SL-DFR 2000 3 L
5800039800
SL-DF 2000 5 L
5800040600
SL-DX 2000 4 L
29.1. ACCESSORIES ASSEMBLY
Accessories are installed on the supply air outlet:
The assembly can be done with the unit standing on the floor or once the unit has been hanged against ceiling. The quick
mounting system and its perfect integration with the heat recovery unit provides a considerable saving in the mounting
time comparing them with the conventional accesories.
Before getting started...
• It is required to add a sealing strip (rubber seal - not delibered from factory) all along the supply flange perimeter
to ensure the tightness of the assembling unit-external module.
Note 1:
A external module is designed to allow the fitting of another external module in a row, creating a “tra-
in- system”.
No more than 2 external modules can be installed in a row.
Note 2:
The external modules must be hanging against ceiling.
The assembling system won’t support the
weight of the external modules.
Note 3:
There are air-sense stickers in all the external modules. Check them to install the modules in the correct
possition.