32.3. REDUCED LIST OF PARAMETERS FOR BMS INTEGRATION
Modbus
Type
Type
Modbus
Address
Bacnet
Address
NA: Not
available
Default
Value
Modbus
Value
Description
FAN CONTROL
CAV parameters
Setpoint full speed supply air fan flow.
Scale factor = 1
HR
R/W
28
AV, 30028
4500 m
3
/h
4500
SAF Manual normal flow (m
3
/h).
Scale factor = 1
Setpoint reduced speed supply air fan
flow. Scale factor = 1
HR
R/W
29
AV, 30029
2000 m
3
/h
2000
SAF Manual reduced flow (m
3
/h).
Scale factor = 1
Setpoint full speed extract air fan flow.
Scale factor = 1
HR
R/W
30
AV, 30030
4500 m
3
/h
4500
EAF Manual normal flow (m
3
/h).
Scale factor = 1
Setpoint reduced speed extract air fan
flow. Scale factor = 1
HR
R/W
31
AV, 30031
2000 m
3
/h
2000
EAF Manual reduced flow (m
3
/h).
Scale factor = 1
Running mode air unit (in CAV or COP
mode)
HR
R/W
368
MSV,
30368
Modbus
:
0=Manual off
1=Manual reduced speed (COP
and CAV modes)
2=Manual normal speed (COP
and CAV modes)
3=Auto
BACnet:
1=Manual off
2=Manual reduced speed
3=Manual normal speed
4=Auto
COP parameters
Setpoint full speed supply air fan
pressure
HR
R/W
24
AV, 30024
500 Pa
5000
SAF Manual normal pressure
(Pa)
Setpoint reduced speed supply air fan
pressure
HR
R/W
25
AV, 30025
300 Pa
3000
SAF Manual reduced pressure
(Pa)
Setpoint full speed extract air fan
pressure
HR
R/W
26
AV, 30026
500 Pa
5000
EAF Manual normal pressure
(Pa)
Setpoint reduced speed extract air fan
pressure
HR
R/W
27
AV, 30027
300 Pa
3000
EAF Manual reduced pressure
(Pa)
SAF/EAF factor
HR
R/W
447
NA
1
10
Exhaust factor if COP Supply
mode is selected
Supply factor if COP Exhaust
mode is selected
VAV parameters
Running mode air unit (in VAV mode)
HR
R/W
516
MSV,
30516
VAV working mode
Modbus:
0=Off 1=Manual
2=Auto
BACnet:
1=Off
2=Manual
3=Auto
Speed in VAV manual mode
HR
R/W
517
NA
Percentage of the speed in
Manual mode (0-100%)
SAF/EAF factor
HR
R/W
447
NA
1
10
Exhaust factor
FANS SUPERVISION
Unit Status
IR
R
3
MSV,
40003
0=Stopped
1=Starting up
2=Starting reduced speed
3=Starting full speed
4=Starting normal run
5=Normal run
9=Free cooling
10=Full speed stop
11=Stopping fan
Unit run mode status
IR
R
284
MSV,
40284
0=Off
1=Reduced speed
2=Normal speed
3=Stop because of alarm